HEC-Series Service Manual
INSTALLING YOUR TUBE-ICE MACHINE
10/21/01
3-8
Air-Cooled Condenser Installation Instructions.
! WARNING !
Using a non-Vogt condenser will void the compressor warranty.
! WARNING !
Certain installation guidelines must be followed to obtain reliable operation from air-cooled ice
machines. If these guidelines are not followed, the compressor warranty will not be honored. Any
exceptions to this policy must be obtained in writing prior to installation and operation of the ice
machine.
1. Outdoor condensers
must
be installed with vertical air flow. Indoor condensers used for heat
recovery may be installed with either horizontal or vertical air flow.
2. The preferred condenser location is above the ice machine, with liquid refrigerant from the
condenser outlet draining freely (1/4” per foot slope) in the direction of normal operating flow
(back to the ice machine) with no traps in the liquid line.
3. If it is absolutely necessary to install the condenser below the ice machine, certain conditions
MUST be met. The refrigerant connections on the condenser must be no more than 6 feet below
the refrigerant connections on the ice machine. The return liquid line from the condenser must
rise no more than 12 feet before dropping back down to the elevation of the ice machine. When
the condenser is located below the ice machine, expect a 16 psig increase in head pressure and at
least 3% reduction in capacity.
4. Flooding head pressure controls such as Alco Headmaster are
not
to be used, since they cause
excessive subcooling of the returned liquid refrigerant and interfere with reliable ice harvest.
5. The discharge and liquid lines must be insulated with 1/2” thick Armaflex insulation or equal.
6.
Horizontal runs in the discharge
line should slope 1/4” per foot in the normal direction of flow
(away from the ice machine).
7. Traps must be installed in discharge lines at the base of all vertical risers. There should be no
intentional traps in liquid lines. Trap volume should be kept to a minimum. Typical details are
shown in FIGURE 3-8.
8. Use only ACR grade copper pipe, Type L. Recommended line sizes are shown in TABLE 3-2.
9. Distance between ice machine and condenser must not exceed 150 equivalent feet. Refer to
Condenser Equivalent Line Size worksheet.
10. Condensers must be provided with a cold weather valve kit per FIGURE 3-7. These valves
allow one-half of the condenser to be disabled in cold weather. Running the ice machine with
one half the condenser in cold weather makes it easier to maintain minimum necessary
condensing pressure, particularly in windy conditions.
Содержание HEC-10
Страница 1: ...HEC SERVICE MANUAL ...
Страница 12: ...HEC Series Service Manual INTRODUCTION 10 24 01 1 5 FIGURE 1 2A Assembly Model HEC 30 Air Cooled Front View ...
Страница 13: ...HEC Series Service Manual INTRODUCTION 10 24 01 1 6 FIGURE 1 2B Assembly Model HEC 30 Air Cooled Rear View ...
Страница 14: ...HEC Series Service Manual INTRODUCTION 10 24 01 1 7 FIGURE 1 2C Assembly Model HEC 30 Water Cooled Front View ...
Страница 15: ...HEC Series Service Manual INTRODUCTION 10 24 01 1 8 FIGURE 1 3B Assembly Model HEC 30 Water Cooled Rear View ...
Страница 45: ...HEC Series Service Manual INITIAL START UP AND OPERATION 10 21 01 5 4 FIGURE 5 2 Piping Schematic Air Cooled ...
Страница 46: ...HEC Series Service Manual INITIAL START UP AND OPERATION 10 21 01 5 5 FIGURE 5 3 Piping Schematic Water Cooled ...
Страница 95: ...HEC Series Service Manual SERVICE OPERATIONS 10 21 01 9 13 FIGURE 9 9 Cutter Water Tank Parts ...
Страница 96: ...HEC Series Service Manual SERVICE OPERATIONS 10 21 01 9 14 FIGURE 9 10 Cutter Drive Parts ...
Страница 97: ...HEC Series Service Manual SERVICE OPERATIONS 10 21 01 9 15 FIGURE 9 11 Cutter Parts ...
Страница 106: ...HEC Series Service Manual MODEL NUMBER STRUCTURE 10 21 01 10 1 10 Model Number Structure ...