VT-PTZ Series
50
3.2.4 SAMPLE SCENARIO
As the priority and the functions settings may be confusing, please refer to the following
sample scenario for a better understanding.
In this scenario, let’s assume that alarms 1 through 6
are triggered simultaneously.
Alarm 1 is set to priority level 0 which will execute
Autoscan 1 titled as “Example001” when the Normally
Closed Circuit is broken.
As priority level 0 supersedes all other alarms,
Autoscan 1 will be executed before any other
functions listed with other alarms, and at the same
time, the relay 1 will be triggered.
When the alarm 1 is released after 10 seconds, alarm
2 and 3 will call PRESET 1 and PRESET 2 and relay
2 will be triggered.
Alarm 2 and 3 will alternate between the two preset
programs as long as the alarms remain active.
Alarms 4 through 6 are ignored until alarm 2 and 3
are released.