MANUAL (T RA NSL A TION)
RAY- LG 35X X
Page 12
RAY-LG 35XX
Version: 1.0
PNP / NPN
Power supply USP
10…30 VDC
Power supply GND
0 V
Test input HIGH
> 10 VDC
Test input LOW
< 2 VDC
Output HIGH
> USP - 2 VDC
Output LOW
< 2 VDC
OSE output HIGH
3.4…4.2 VDC
OSE Output LOW
< 1 VDC
Table 3:
General value table
Start-up
1.
The door must be opened completely, and
the monitored area must be unobstructed.
2.
Switch on main power supply and power up
the door control unit. The LEDs blink during
power up.
3.
Check the LED on both sensor bars (power,
status).
4.
Test if the system is working correctly by
letting the door open and close, interrupting
the light during the opening and closing
process.
LED Status Description Receiver Edge
green LED red LED Sensor status
Light curtain free
Light curtain interrupted
Start-Up (slow blinking)
Internal Malfunction (fast
blinking)
No Power or light curtain
defective
LED on
LED off
LED blinking
Table 4:
LED status description receiver edge
LED Status Description Emitter Edge
green LED Sensor status
Power ok
No Power or not within the limits or
edge is defective
LED on
LED off
Table 5:
LED status description emitter edge