Visonic POWERART Скачать руководство пользователя страница 7

DE5458

7

3.8 PowerArt™-Compatible Detectors

Each detector compatible with the PowerArt™ system is

packed with its own installation instructions. Read them

carefully and install as indicated.

A. SPD-1000

SPD-1000 (Fig. 14) is a
wireless detector, used for
protection of paintings,
sculptures and other artwork,
in museums, galleries, private
artwork collections, etc.

Figure 14. 

SPD-1000

B. PIR Motion Detectors

The wireless passive infrared (PIR) motion detectors used

in the system are of the PowerCode type. The PowerArt™

is capable of “learning” each detector’s identification code

and linking it to a specific zone (see Section 3 in the

Programming Manual). Some units are shown below:

Figure 15.

MC/PIR-2000

Figure 16. 

MC/PIR-3000

or K-940MCW

 

Figure 17.

K-980MCW

Note:

 K-940 MCW and K-980MCW are pet immune units.

In addition to its unique 24-bit identification code, each

detector transmits a message, containing status information:

 •  

The detector is in alarm (or not).

 •  

The detector is being tampered with (or not).

 •  

The battery voltage is low (or normal).

 •  

“This is a supervisory message”.

If any of these detectors detects motion, it sends out a

message to the alarm control panel. If the system is in the

armed state, an alarm will be triggered.

C. Magnetic Contact Transmitter

MCT-302 (Figure 18) is a PowerCode
magnetic-contact transmitter used to
detect the opening of a door or a window.
The alarm contacts are closed as

 

long as

the door or window remain

 

closed.

Figure 18.

MCT-302

The unit has an extra alarm input that acts as if it were a

separate wireless transmitter. It sends (or does not send)

a “restored to normal“ message to the alarm system,

depending on the setting of an on-board “DIP” switch. The

“restore” message informs you, through the control panel’s

display, whether the door or window is open or closed.

D. Wireless Adapter for Wired Detectors

MCT-100 (Fig. 19) is a PowerCode device

used mainly as a wireless adapter for 2

regular magnetic switches installed on 2

windows in the same room. The unit has

two inputs, behaving as separate wireless

transmitters and transmitting different

PowerCode IDs. Each input sends (or

does not send) a “restored“ message to

the alarm system, depending on the

setting of an on-board “DIP” switch.

 

Figure 19.

MCT-100

E. Wireless Smoke Detector

MCT-423 

(unapproved by UL)

.

A photoelectric smoke detector

equipped with a PowerCode-type

transmitter. If enrolled to a fire

zone, it initiates a fire alarm upon

detection of smoke.

Figure 20.

 MCT-423

F. Wireless Glass Break Detector

MCT-501 

(Fig. 21). An acoustic detector

equipped with a PowerCode-type trans-

mitter.  Since it restores automatically after

detection, this unit does not send a restoral

message to the alarm control panel.

Figure 21.

MCT-501

3.9 PowerArt-Compatible Transmitters

Note:

 Each transmitter is packed with its own instructions

for battery installation and use. Be sure to pass these
documents on to the “Master User“ of the alarm system.

The PowerArt™ system is compatible with multi-button
and single button key-ring and hand-held transmitters that
use PowerCode and CodeSecure coding methods.
Multi-button PowerCode transmitters transmit the same
code each time the same button is pressed. They can be
used for emergency signaling, or for activating the PGM
output or for controlling appliances via X-10 units. 

They

can not be used for arming / disarming.

CodeSecure transmitters are of the rolling code type - they
transmit a new code each time the same button is
pressed. This provides a higher security level, especially
in arming / disarming applications, because the code can
not be copied (“grabbed”) by unauthorized people.
Following are the basic details of several compatible

transmitters. The possible applications for each push-

button are indicated in each drawing.

A. MCT-234 

(Fig 22): ‘Keyfob’

transmitter - one unit is
supplied with the PowerArt.
You can program the AUX
(auxiliary) button to perform
various tasks, in accordance
with the user’s needs.

Figure 22.

 MCT-234

B. MCT-231 / MCT-201

 (Fig.

23): Single-button pendant
units. The MCT-231 (Code-
Secure) and the MCT-201
(PowerCode) can be enrolled
to perform functions as
shown. Both units look alike.

Figure 23

. MCT-231 / 201

C. MCT-134 / MCT-104

 (Fig.

24):

 

4-button hand-held units.

MCT-134 (CodeSecure) can
replace the MCT-234 keyfob.
MCT-104 (PowerCode) can
perform emergency and non-
alarm functions. Both units
look alike.

Figure 24. 

MCT-134

 / 

104

D. MCT-132 / MCT-102

 (Fig.

25): 2-button units. MCT-132
(CodeSecure) Can perform
functions as shown.

 

MCT-102

(PowerCode) can perform
emergency and non-alarm
functions. Both units look
alike.  

Figure 25. 

MCT-132

 / 

102

E. MCT-131 / MCT-101

 (Fig.

26): Single-button units. The
MCT-131 (CodeSecure) and
the MCT-101 (PowerCode)
can be enrolled to perform
functions as shown. Both
units look alike.

Figure 26. 

MCT-131

 / 

101

Содержание POWERART

Страница 1: ... handed over to the master user after testing the system Appendices A and B to the installation instructions will help you prepare an installation plan Please take time to fill out the forms your job will become much easier and confusion will be prevented Filling out the forms will also help you create a list of detectors and transmitters that must be obtained for the particular application Compat...

Страница 2: ... Siren Signals Continuous intrusion 24 hours panic triple pulse pause triple pulse fire Siren Timeout Programmable 4 minutes by default Internal Sounder Output at least 85 dBA at 10 ft 3 m Supervision Programmable time frame for inactivity alert Special Functions Speech and sound control Powerline Carrier Device Control up to seven X 10 brand units by various factors as programmed Chime zones Diag...

Страница 3: ...ay 3 3 3 3 INSTALLATION INSTALLATION INSTALLATION INSTALLATION 3 1 Unpacking the Equipment Open the cardboard packing box and check whether all items have been included If you find out that an item is missing contact your vendor or dealer immediately 3 2 Supplying Power to the Unit Enrolling the transmitting devices ID codes in the Power Max memory will be easier if carried out before actual insta...

Страница 4: ...used in the system and mark each one in accordance with your deployment plan Program the system now as instructed in the PowerArt programming Guide Publication DE5450P 3 4 Mounting the Bracket A Detaching the Bracket from the Cabinet A notable advantage of the PowerArt is that the unit can be mounted without having to open its cabinet All connectors and terminals are accessible through a rectangul...

Страница 5: ... wall with 4 screws Be sure to insert the special plastic washer into the ring as shown in Figure 8 3 5 Wiring All terminals and connectors are accessible within the opening at the back of the PowerArt see Figure 9 All screw terminal blocks except for EARTH can be pulled out wired appropriately and plugged back in WARNING When plugging terminals back into place be sure to align them carefully with...

Страница 6: ...vertheless refer to Figure 11 and proceed as follows A Hold the cabinet with its top slightly slanted toward yourself and align the trap at the bottom of the cabinet with the dual prong catch at the bottom of the bracket Figure 11 Cabinet to Bracket Assembly Top View B Allow the dual prong catch to enter the trap as far as it will go while slanting the cabinet towards your stomach C Using the dual...

Страница 7: ...napproved by UL A photoelectric smoke detector equipped with a PowerCode type transmitter If enrolled to a fire zone it initiates a fire alarm upon detection of smoke Figure 20 MCT 423 F Wireless Glass Break Detector MCT 501 Fig 21 An acoustic detector equipped with a PowerCode type trans mitter Since it restores automatically after detection this unit does not send a restoral message to the alarm...

Страница 8: ...module The X 10 siren is ready to function upon connection to an electrical power outlet without re programming the Power Max You only have to set the HOUSE CODE and the UNIT CODE selectors on the X 10 siren as follows House Code Set this selector to the letter that follows by alphabetical order the letter that you programmed as a house code for the protected premises For example if the programmed...

Страница 9: ...nd verify that the display shows B Y T I M E R O N and B Y S E N S O R O N A dark box at the extreme right means that these functions are enabled The easiest way to test timed activation is to select the ninth item in the installer s menu 9 USER SETTINGS and set the system clock a few minutes before the relevant start time Do not forget to return the clock to the correct time after completion of t...

Страница 10: ...er the MEMORY message will now blink in the display caused by the tamper alarm you triggered when opening the battery compartment lid Clear it by arming the system and immediately disarming 5 3 Fuse Replacement The PowerArt has two fuses which can burn out Battery Fuse 1A time delay type UL recognized exists in U S variants only Siren Fuse 0 5 A time delay type UL recognized in the U S A or 0 5 A ...

Страница 11: ... 24 h silent 6 24 h audible 7 Fire 8 Non alarm 9 Emergency Zone Locations Note down the intended location for each detector When programming you may select one of 26 available zone names plus 3 custom zone names that you can add see Figure 3 in the Programming Guide A2 Keyfob Transmitter List Transmitter Data AUX button Assignments No Type Holder Status or Arming instant PGM Control X 10 Unit Cont...

Страница 12: ...t Tx Transmitter Type Enrolled to Zone Name of holder 1 2 3 4 5 6 7 8 9 10 A4 SPD 1000 Wireless Detector List SPD 1000 No Enrolled to Zone Location Painting Name 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 ...

Страница 13: ...itter Type Enrolled to Zone Name of holder Assignment 1 2 3 4 5 6 7 8 9 10 APPENDIX B X 10 Unit Assignments Unit Controlled ON ON ON ON ON by Timer ON by Zone No No Appliance by Arming by Memory by Delay by Keyfob ON Time OFF Time a b c 1 2 3 4 5 6 7 ...

Страница 14: ...any This equipment uses the following jacks An RJ31X is used to connect this equipment to the telephone network The REN is used to determine the quantity of devices which may be connected to the telephone line Excessive RENs on the telephone line may result in the devices not ringing in response to an incoming call In most but not all areas the sum of the RENs should not exceed five 5 0 To be cert...

Страница 15: ...DE5458 15 ...

Страница 16: ...others including batteries used in conjunction with the Products The Manufacturer does not represent that its Product may not be compromised and or circumvented or that the Product will prevent any death personal and or bodily injury and or damage to property resulting from burglary robbery fire or otherwise or that the Product will in all cases provide adequate warning or protection User understa...

Отзывы: