Visonic POWERART Скачать руководство пользователя страница 4

4

DE5458

  D .  

Remove the screw that secures the lid (see Figure 3),
swing the lid up and pull it away. You now have access
to the battery holder (see Figure 4).

  E .  

Pull out the battery holder and check that the battery
type selection jumper is positioned in accordance with
the type of batteries being installed (see Figure 4). For
alkaline (dry) cells, the jumper should be mounted on
the two lower pins. For Nickel Cadmium (rechargeable)
cells - on the two upper pins.

CAUTION! Verify that the jumper is at the
correct position for the actual battery cells
being installed.

Figure 4.

 Battery Type Selection Jumper

F.

Insert all 6 battery cells - 3 at the top and 3 at the bottom.

Make sure that the flat (–) end of each cell is pressed

against a circular spring and the capped (+) end of each

cell is pressed against a flat contact.

Figure 5.

 Battery Holder in Place with Batteries Installed

G.

Put the battery holder back in, re-mount the battery

compartment lid and re-attach it using the screw.

Disregard any trouble indications that may appear

(due to lack of AC or lack of telephone line connection).

H.

Put back the battery area cover - insert the angled legs

at the left edge into their holes and then press the right

edge of the cover against the cabinet surface until the

catches click into place.

3.3 Programming  

It pays off to plan ahead - use the tables in appendices A

and B at the end of this guide to register the intended

location of each detector, the holder and assignment of

each transmitter and the control plan for the X-10 units.
Gather up all transmitters and detectors used in the

system and mark each one in accordance with your

deployment plan.

Program the system now as instructed in the

PowerArt™ programming Guide (Publication DE5450P).

3.4 Mounting the Bracket

A. Detaching the Bracket from the Cabinet

A notable advantage of the PowerArt™ is that the unit can

be mounted without having to open its cabinet. All

connectors and terminals are accessible through a

rectangular opening at the rear, and wiring channels are

provided across the rear of the cabinet. Quick mounting of

the PowerArt™ is possible by virtue of a special bracket

and a unique mechanical coupling / locking mechanism.
The control panel comes with the bracket in place at the

rear. The bracket lock at the front (see Figure 5) is left

open. Since a catch at the lower end of the bracket is

trapped within the cabinet, a special plastic key (supplied

in the kit) must be used to release it  - see Figures 6 & 7.

Figure 6.

 Releasing the Bottom Catch from the Trap

Figure 7.

 Detaching the Bracket

 

B. Getting Acquainted with the Bracket

Having detached the bracket successfully, put it on a desk
and observe its design - see Figure 8 for identification of
its various parts.
The upper and lower mounting holes are intended for
regular attachment to the wall with screws and anchors.
A special “

ring and cam

” piece is connected to the bottom

leg of the bracket by 3 breakable plastic joints. A large
plastic washer supplied with the bracket must be inserted
into the ring to allow fastening the ring to the wall. With the
washer in place, a fourth screw can be used to secure the
ring and cam piece to the wall.
Once the control panel is mounted in place, the cam
enters a slot in the control panel’s rear part and maintains
the built in tamper switch pressed. Separating the control

Содержание POWERART

Страница 1: ... handed over to the master user after testing the system Appendices A and B to the installation instructions will help you prepare an installation plan Please take time to fill out the forms your job will become much easier and confusion will be prevented Filling out the forms will also help you create a list of detectors and transmitters that must be obtained for the particular application Compat...

Страница 2: ... Siren Signals Continuous intrusion 24 hours panic triple pulse pause triple pulse fire Siren Timeout Programmable 4 minutes by default Internal Sounder Output at least 85 dBA at 10 ft 3 m Supervision Programmable time frame for inactivity alert Special Functions Speech and sound control Powerline Carrier Device Control up to seven X 10 brand units by various factors as programmed Chime zones Diag...

Страница 3: ...ay 3 3 3 3 INSTALLATION INSTALLATION INSTALLATION INSTALLATION 3 1 Unpacking the Equipment Open the cardboard packing box and check whether all items have been included If you find out that an item is missing contact your vendor or dealer immediately 3 2 Supplying Power to the Unit Enrolling the transmitting devices ID codes in the Power Max memory will be easier if carried out before actual insta...

Страница 4: ...used in the system and mark each one in accordance with your deployment plan Program the system now as instructed in the PowerArt programming Guide Publication DE5450P 3 4 Mounting the Bracket A Detaching the Bracket from the Cabinet A notable advantage of the PowerArt is that the unit can be mounted without having to open its cabinet All connectors and terminals are accessible through a rectangul...

Страница 5: ... wall with 4 screws Be sure to insert the special plastic washer into the ring as shown in Figure 8 3 5 Wiring All terminals and connectors are accessible within the opening at the back of the PowerArt see Figure 9 All screw terminal blocks except for EARTH can be pulled out wired appropriately and plugged back in WARNING When plugging terminals back into place be sure to align them carefully with...

Страница 6: ...vertheless refer to Figure 11 and proceed as follows A Hold the cabinet with its top slightly slanted toward yourself and align the trap at the bottom of the cabinet with the dual prong catch at the bottom of the bracket Figure 11 Cabinet to Bracket Assembly Top View B Allow the dual prong catch to enter the trap as far as it will go while slanting the cabinet towards your stomach C Using the dual...

Страница 7: ...napproved by UL A photoelectric smoke detector equipped with a PowerCode type transmitter If enrolled to a fire zone it initiates a fire alarm upon detection of smoke Figure 20 MCT 423 F Wireless Glass Break Detector MCT 501 Fig 21 An acoustic detector equipped with a PowerCode type trans mitter Since it restores automatically after detection this unit does not send a restoral message to the alarm...

Страница 8: ...module The X 10 siren is ready to function upon connection to an electrical power outlet without re programming the Power Max You only have to set the HOUSE CODE and the UNIT CODE selectors on the X 10 siren as follows House Code Set this selector to the letter that follows by alphabetical order the letter that you programmed as a house code for the protected premises For example if the programmed...

Страница 9: ...nd verify that the display shows B Y T I M E R O N and B Y S E N S O R O N A dark box at the extreme right means that these functions are enabled The easiest way to test timed activation is to select the ninth item in the installer s menu 9 USER SETTINGS and set the system clock a few minutes before the relevant start time Do not forget to return the clock to the correct time after completion of t...

Страница 10: ...er the MEMORY message will now blink in the display caused by the tamper alarm you triggered when opening the battery compartment lid Clear it by arming the system and immediately disarming 5 3 Fuse Replacement The PowerArt has two fuses which can burn out Battery Fuse 1A time delay type UL recognized exists in U S variants only Siren Fuse 0 5 A time delay type UL recognized in the U S A or 0 5 A ...

Страница 11: ... 24 h silent 6 24 h audible 7 Fire 8 Non alarm 9 Emergency Zone Locations Note down the intended location for each detector When programming you may select one of 26 available zone names plus 3 custom zone names that you can add see Figure 3 in the Programming Guide A2 Keyfob Transmitter List Transmitter Data AUX button Assignments No Type Holder Status or Arming instant PGM Control X 10 Unit Cont...

Страница 12: ...t Tx Transmitter Type Enrolled to Zone Name of holder 1 2 3 4 5 6 7 8 9 10 A4 SPD 1000 Wireless Detector List SPD 1000 No Enrolled to Zone Location Painting Name 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 ...

Страница 13: ...itter Type Enrolled to Zone Name of holder Assignment 1 2 3 4 5 6 7 8 9 10 APPENDIX B X 10 Unit Assignments Unit Controlled ON ON ON ON ON by Timer ON by Zone No No Appliance by Arming by Memory by Delay by Keyfob ON Time OFF Time a b c 1 2 3 4 5 6 7 ...

Страница 14: ...any This equipment uses the following jacks An RJ31X is used to connect this equipment to the telephone network The REN is used to determine the quantity of devices which may be connected to the telephone line Excessive RENs on the telephone line may result in the devices not ringing in response to an incoming call In most but not all areas the sum of the RENs should not exceed five 5 0 To be cert...

Страница 15: ...DE5458 15 ...

Страница 16: ...others including batteries used in conjunction with the Products The Manufacturer does not represent that its Product may not be compromised and or circumvented or that the Product will prevent any death personal and or bodily injury and or damage to property resulting from burglary robbery fire or otherwise or that the Product will in all cases provide adequate warning or protection User understa...

Отзывы: