background image

 

 

24 

 

E.  UPSilon2000 for FreeBSD and Linux   

 

1.  Log in as a super-user.   
2.  Use the 'ftp' utility in MS-

DOS to copy files into the system directory “/tmp”.   

3.  Follow the instructions below to make the filename conversion after the 'ftp'   

File transfer:   
#cd/tmp 
#mv linux.z linux.Z, or   
#mv LINUX.Z linux.Z   
#chmod 755 install   

4.  Execute the installation program:   

#./install   

5.  Select a target system from the menu, and configure the UPSilon for   

Unix (Make sure no other process using the same serial port), the 
installation Program will launch the UPSilon for Unix daemon process 
automatically.   

 

5.2.2.  Important Note:   

A. The cable enclosed with the UPSilon 2000 software contents special design. 

Other sell-on-shelf cable might not work with the software properly. 

B. For more detailed setup and operation of the software, please refer to the 

user manual in the CD-R. 
 
 
 
 
 
 
 

 
 

Содержание Marathon +

Страница 1: ...1 Uninterruptible Power Supply VISION MARATHON User Manual ...

Страница 2: ...on and Operation 14 3 1 Unpacking 14 3 2 Selecting Installation Position 14 3 3 Operation Test and Installation Instruction 16 3 3 1 Start Up in Normal Mode 16 3 3 2 Start up in Battery Mode Cold Start 18 3 3 3 UPS Self test 18 3 3 4 Shut Off the UPS 19 3 3 5 Maintenance Bypass Mode 19 3 4 Output Terminal Block Explanation 20 3 4 1 SINGLE PHASE 20 3 4 2 3 PHASE 21 Chapter 4 Troubleshooting Guide 2...

Страница 3: ...ot store things on top of the UPS Keep the UPS 20 cm away from the wall Make sure the UPS is installed within the proper environment as specified 0 40 and 30 90 non condensing humidity Do not install the UPS in direct sunlight Your warranty may be void if the batteries fail Install the UPS indoors as it is not designed for installation outdoors Dusty corrosive and salty environments can do damage ...

Страница 4: ...ing function For correct setting and wiring please contact with your local agent Do not do it by yourself otherwise your warranty will be void This UPS has been designed and constructed to protect your assets from the wide range of power aberrations experienced on Utility power lines today It is your insurance for reliable clean and stable voltage supply It is worth taking care to install the syst...

Страница 5: ...ading it automatically switches to bypass mode in case loading exceeds 150 of rating It will automatically switch back to inverter mode once overload condition ceases Should the output becomes short circuited the UPS holds the system and cuts the output automatically till the short circuit situation is removed Should the unit become overheated the internal thermistor will detect the heat and switc...

Страница 6: ...as motor based devices entirely eliminating application limitation State of the Art IGBT technology and industrial grade quality ensures highest efficiency and reliability under worst operation condition Advanced Input PFC control guarantees the PF performance and maximum energy efficiency Independent over voltage trip over circuit retains full over voltage protection even during UPS failures and ...

Страница 7: ...tery Low 3 Battery Abnormal 4 UPS Overloading 5 UPS Working in Abnormal Mode 6 Wrong Phase in input cable 7 Grounding Fault 8 OFF UPS Shutoff 9 UPS Flow Chart 10 4 Digits Measurement Display 11 Indicate the item desired to be tested 12 UPS Inverter Switch 13 Page Up 14 Page Down 15 Alarm Silence ...

Страница 8: ...st 17 Er02 Output Short Circuit 18 Er04 Inverter Overheat 19 Er05 Bad or Dead Battery 20 Er06 Charger abnormal 21 Er12 Inverter Over current 22 Er13 Wrong Procedure to Enter Maintenance Mode 23 Er Other Error code ...

Страница 9: ...9 2 4 The front panel explanation SINGLE PHASE 3 PHASE ...

Страница 10: ...larm Silence By pressing the button the Alarm will be automatically in silence 9 Self Test By pressing the button the UPS will enter into Self test mode 10 LCD Display This is to indicate the measurements of the UPS including Input Voltage Output Voltage Output Frequency Load Percentage Inner Ambient Temperature Battery Voltage Fault Conditions 11 COM Port This is an interface to send signals to a...

Страница 11: ...tput and additional battery banks for longer backup time purpose Only a qualified technician is permitted to proceed the installation 18 Terminal Block 3 PHASE This terminal to be connected with input and output Only a qualified technician is permitted to proceed the installation 19 Terminal Block 3 PHASE This terminal to be connected with additional battery banks for longer backup time purpose On...

Страница 12: ...rating system such as Windows 3 1 95 98 2000 ME NT XP Novell NetWare Linux and Free BSD For other applications like Unix system or IBM AS 400 please contact your local distributor for a proper solution 2 5 1 True RS232 type 2 5 1 1 The RS232 interface settings The RS232 interface shall be set as follows Baud Rate 2400 bps Data Length 8 bits Stop Bit 1 bit Parity None 2 5 1 2 The Pin Assignments of...

Страница 13: ... 2 5 2 1 The pin assignments of the dry contact type 1 2 3 4 5 6 7 8 9 10 Pin 1 UPS on Bypass mode Pin 2 Utility abnormal Pin 3 Utility normal Pin 4 Inverter On Pin 5 Battery Low Pin 6 Battery Dead or Bad Pin 7 UPS Alarm Pin 8 Common Pin 9 Shutdown UPS positive signal Pin 10 Shutdown UPS negative signal Max power rating 250Vac 7Amp P S Expect Pin9 Pin 10 all the other pins will be Shorten with gro...

Страница 14: ...ful in unpacking and holding the unit The unit might drop accidentally and harm yourself 3 Standard Package includes 1 set of User s Manual 1 set of UPS communication software with RS232 cable 3 2 Selecting Installation Position It is necessary to select a proper environment to install the unit in order to minimize the possibility of damage to the UPS and extend the life of the UPS Please follow t...

Страница 15: ...15 4 Do not place the UPS in an environment near dust corruptive or salty material or flammable objects 5 Do not expose the UPS to outdoors Relative humidly non condensation 30 90 ...

Страница 16: ...t voltage window of the UPS 4 Connect the Utility to the input end of the terminal block of the UPS 5 Switch on the Power Breaker of the distribution panel and the Input Breaker of the UPS and then the UPS starts up Green LED lights up to show the Utility is normal and the LCD display will illustrated from drawing A to drawing B A B 6 Then the UPS is on Bypass Mode now and it will proceed self tes...

Страница 17: ...rter works normally D 9 Switch off the Input Breaker of the UPS and check whether the UPS works normally under Utility fails The LCD display shall show as Drawing E E 10 Switch on the Input Breaker of the UPS the UPS will switch back to Utility mode The LCD display shall show as drawing C 11 Leave the UPS in charging mode for at least 8 10 hours in order to charge the batteries to 90 capacity 12 Y...

Страница 18: ...to drawing B and keep awake for approx 60 seconds 3 Press the Inverter Switch of the UPS for about 3 5 seconds till the LCD display shows from drawing B to drawing E then the UPS will be in Battery Mode Make sure you will press the Inverter Switch in 60 seconds after pushing the Cold Start Switch Otherwise you have to go through step 1 to 3 once again 3 3 3 UPS Self test 1 Switch on the UPS and ma...

Страница 19: ...under unauthorized condition your warranty will be void immediately 1 When the UPS is in Normal mode press the Inverter Switch of the UPS for 3 5 seconds the LCD display shows as drawing B now the UPS is in Bypass mode 2 Remove the protecting bracket of the MTBS switch Turn the MTBS switch from INV to MTBS 3 Switch off the Input Breaker of UPS 4 Now the Utility is in Maintenance Bypass loop The te...

Страница 20: ...2 the terminals of External Battery Banks Pin 3 Pin 4 Pin 5 The terminals of UPS Output Pin 6 Pin 7 Pin 8 The terminals of UPS Input Max input current 8KVA 50 Amp 10KVA 63 Amp Please choose your external input breaker properly according to the Max input current of the UPS ...

Страница 21: ...Battery Banks Pin 3 Pin 4 Pin 5 The terminals of UPS Output Pin 6 Pin 7 Pin 8 Pin 9 Pin 10 The terminals of UPS Input Max input current 8KVA 50 Amp 10KVA 63 Amp Please choose your external input breaker properly according to the Max input current of the UPS ...

Страница 22: ...ove the objects block the ventilation holes 2 Check if the output load is abnormal 3 Check to see whether the battery voltage is normal or the Battery breaker is opened 4 Turn off the UPS to restart it once again 5 Consult your local agent for help LCD Display Overload Output overloading Please reduce some uncritical load UPS fails to offer battery backup or its back up time is shorter than it s e...

Страница 23: ...2000 Installation A UPSilon2000 for Windows 95 98 NT 2000 XP 1 From the Start Button choose Run 2 Type D Windows Setup exe 3 Choose OK B UPSilon2000 for Novell Netware V3 1x 1 Login the File Server with access rights in SYS SYSTEM 2 Execute D Netware V3 1x Install exe 3 Re boot System C UPSilon2000 for Novell Netware V4 x 1 Login the File Server with access rights in SYS SYSTEM 2 Execute D Netware...

Страница 24: ...he installation program install 5 Select a target system from the menu and configure the UPSilon for Unix Make sure no other process using the same serial port the installation Program will launch the UPSilon for Unix daemon process automatically 5 2 2 Important Note A The cable enclosed with the UPSilon 2000 software contents special design Other sell on shelf cable might not work with the softwa...

Страница 25: ...0 5Hz Free Running Crest Factor 3 1 Transfer Time Line Fault 0 ms Efficiency AC to AC 85 DC Start Yes BATTERY Type Sealed Maintenance Free Lead Acid Quantity pcs 16 Voltage Vdc 192 Recharge Time 8 Hours to 90 Supplementary Charger Optional 2000W Charger for extended back up application DISPLAY LED Utility Inverter and Fault Conditions LCD Optional Input Voltage Output Voltage Output Frequency Load...

Страница 26: ... 4 5 ALARM Audible and Visual Line Failure Battery Low Transfer to Bypass System Fault Conditions PHYSICAL Dimensions WxHxD mm 400x842x730 400x1112x730 Net Weight Kgs 160 kgs 183kgs 253 kgs Outlets IEC Local Terminal Block ENVIRONMENT Temperature 0 40 Humidity 30 90 RH Maximum Non Condensing Acoustic 60 dB at 1 meter COMPUTER INTERFACE Interface Type Standard RS232 Interface Megatec protocol SNMP ...

Отзывы: