4. TECHNICAL SPECIFICATIONS
Model
1000VA/h
1500VA/h
2000VA/h
3000VA/h
Real power rating
600W
900W
1200W
1800W
Display
Indicator on panel
LED / LCD plus LED display
AC-Mode
Types of load
Ancillary equipment such as PC, display, group computers, etc.
Input voltage
100V/110V/120V/220V/230V/240V ±25%: (-35%+25% optional)
Input frequency
45-65Hz (transfer to battery mode if out of this range)
Output voltage
100V/110V/120V/220V/230V/240V ±25%
Input PF(AC/DC)
98%
Efficiency
≥96% (AC-Mode)
Overload in AC-Mode
110% transfer to bypass within 60s
120% transfer to bypass within 30s
Automatic recovering if the load capacity becomes normal
Short circuit
Protected by input fuse
Inverter-Mode
Output voltage
100V/110V/120V/220V/230V/240V ±5%
Output frequency
50Hz/60Hz ±1% self-adaptive
Output PF
=0.6
Waveform distortion
≤5% linear load
Battery backup time
≥10min (PC load)
Transfer time
Typical value: 5ms, max : 8ms
Efficiency
≥80% (INV mode)
Overload in INV mode
110% shut down within 60s
120% shut down within 5s
Auto shut down with no load (optional)
<5% shut down within 1min
Short circuit
System shuts down automatically
Alarm
AC abnormal
Once per 4s, silent after 40s
Battery low
Once per 0.2s
Overload
Once per 1s
Battery
DC voltage
24V
24V
36V 48V(H) 48V
configuration (standard UPS)
2 x 12V7Ah
2 x 12V8Ah
3 x 12V8Ah
4 x 12V8Ah
Recharge time
90% capacity after 8 hours
Charging current (long backup)
10A, maximum
Communication (charging option)
RS232 / USB / SNMP (can be programmed with automatic UPS turn
on/off)
Miscellaneous
Output sockets
Customized, on request
Surge protection
Optional
EMC
EN62040-2:2006; EN61000-3-2:2006; EN61000-3-3:2008
IP level
IP20
Ambient temperature
0°C ~ 40°C
Ambient humidity
10% ~ 90% (no condensing)
Noise level
≤45dB
Dimensions (mm) D*W*H
355x145x215
Dimensions (mm)
D*W*H
355x145x215
Packing dimensions D*W*H (mm)
427x325x245
Packing dimensions
D*W*H (mm)
427x325x245
Net weight (kg)
14.5
Net weight (kg) 14.5
Net weight (kg)
Gross weight (kg)
15.5
Gross weight
(kg)
15.5
Gross weight
(kg)
Notes:
1)
Data with «(H)» indicate, that the UPS is a long backup type with external battery.
2)
Above named data are concerning UPS standard units, which can vary in accordance with the special units from
customers.