 JUPITER PRO 1-3KVA   -   UPS    

www.visionups.com 

2. WORKING PRINCIPLE

 

 

2.1.  System circuit diagram 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
2.2.  Normal power supplies 

When  the  UPS  works  in  normal  condition,  miscellaneous  waves  of  high-frequency  are  eliminated  by  wave  filter  and  the 
batteries are charged by the charger and maintained like this in full power condition.  The output voltage is regulated via 
autotransformer in case of fluctuations in mains voltage. 
 
 
 
 
 
 
 
 
 
 
 
 

 

 
2.3.  Main power off

 

In main power off condition, the batteries are promptly supplying current to the inverter.  Then – after passing through the 
wave filter – the power can be sent to user’s equipment without interruption.  

 

2.4.  Power supply by bypass

 

The bypass mode only happens in the following conditions: 

1.

 

overload;

 

2.

 

UPS failure;

 

3.

 

Switch-on: keep pressing the ON button for 3 seconds, the UPS will be in process of soft starting within 15 seconds; 

 

4.

 

Switch-off: keep pressing the OFF button for 3 seconds and the UPS turns to bypass mode.

 

MAINS

Load

BATTERY

Filter

Transformer

Bypass

CHARGER

AVR

INVERTER

 

Load

MAINS

INVERTER

AVR

CHARGER

Bypass

Transformer

Filter

BATTERY

 

BATTERY

Filter

Transformer

Bypass

CHARGER

AVR

INVERTER

MAINS

Load

 

Содержание jupiter pro series

Страница 1: ...User Manual Jupiter Pro series 1 3KVA Uninterruptible Power Supply ...

Страница 2: ...achieve maximum lifetime of your UPS This manual explains the principle of inner operation and the corresponding protective functions It also contains information about the use of the equipment Please follow the given instructions and warning notices in this manual or on the unit itself Only operate the appliance after you have completely read and understood all the safety and operating instructio...

Страница 3: ...nel 7 3 7 Automatic switch off in inverter mode when no load is available optional 7 3 8 Automatic distinction of the output frequency 7 3 9 Battery detection 7 3 10 Intelligent communication ports with intelligent PC assisted monitoring function optional 7 4 Technical specifications 8 5 Product components 9 5 1 Front panel 9 5 2 Back panel 9 6 Installation and operating 10 6 1 Installation of the...

Страница 4: ...wall and UPS to avoid any overheating in areas free from flammable gas fume corrosive materials excessive dust conductive contaminants sparks strong vibrations to avoid damages in an interior room with controlled temperature the appliance is not suited for outdoor use no high or low temperatures above 40 C or below 0 C and or with high non condensing humidity above 90 for maintaining the battery l...

Страница 5: ...ies are promptly supplying current to the inverter Then after passing through the wave filter the power can be sent to user s equipment without interruption 2 4 Power supply by bypass The bypass mode only happens in the following conditions 1 overload 2 UPS failure 3 Switch on keep pressing the ON button for 3 seconds the UPS will be in process of soft starting within 15 seconds 4 Switch off keep ...

Страница 6: ...nging frequency 5 times per second when the batteries are nearly exhausted in order to remind the persons that the batteries are used up and that the UPS will soon cut out When the batteries are almost used up the UPS shuts down automatically to protect the batteries 3 4 Protective functions of the Online UPS Overload on main power condition if the load amounts more than 110 on mains condition the...

Страница 7: ...ency 50Hz or 60Hz was before the mains collapsed 3 9 Battery detection The product can work with monitoring software to capture the battery at a certain time In the case of any error message such as an open circuit of battery cable or battery failure the unit can catch the error information through the communication ports to advise the user Meanwhile the UPS has a self protection function by shutt...

Страница 8: ...t down within 5s Auto shut down with no load optional 5 shut down within 1min Short circuit System shuts down automatically Alarm AC abnormal Once per 4s silent after 40s Battery low Once per 0 2s Overload Once per 1s Battery DC voltage 24V 24V 36V 48V H 48V configuration standard UPS 2 x 12V7Ah 2 x 12V8Ah 3 x 12V8Ah 4 x 12V8Ah Recharge time 90 capacity after 8 hours Charging current long backup 1...

Страница 9: ...when the UPS is working 4 UPS working condition indicator the green light is on when there is main power input the red light is on when there is no mains flowing 5 AC indicator orange the light is on when there is input main power 6 ON starting button start the UPS by pressing the button for 3 seconds The UPS produces output power normally within 15 seconds when starting daily 7 OFF shut down butt...

Страница 10: ...n on the front panel for 3 seconds The UPS switches to bypass mode when the mains in on In this moment the bypass LED is illuminated otherwise the UPS shuts down its operating Precautions 1 When starting the computer take care of starting first the UPS and only after then the load of the computer And when switching off turn off first the computer and afterwards the UPS 2 Normally it s not necessar...

Страница 11: ...utput power Then cut the main power supply off The UPS transfers automatically to battery mode before shutting down Take note of the discharging time in order to refer it later The total of the load current consumption is calculated in the unit Watt If the marking on the UPS just shows the power capacity in the unit VA then multiply the VA rating with the power factor PF 0 6 for calculating the ra...

Страница 12: ...cannot work Whether the battery is not charged or the UPS is not switched on When power has failing computer stops to work Start the UPS when mains is normal Charge the battery during more than 10 hours and then start the UPS When the mains is connected the UPS beeps for 60 seconds and transfers then to bypass When no main power is entering the UPS shuts itself down automatically after 60 seconds ...

Отзывы: