ESTAmat PFC-N
D.No.13157 - Rev. 02
Operating Instruction MV1181
Page 6 of 36
1.2 Connection data
Supply voltage
Measurement voltage
Range 90-300VAC.
Terminals L / N
Range 90-690V.
Terminals UM1 / UM2
With using of VT's a ratio can be adjusted.
Range 1-350
Current measurement
Current measurement
Range 15mA – 6A,
Measurement transformer types x/1A or also x/5A can be used.
Terminals K (S1) / L (S2)
CT ratio is 1-9600
(Devices with Firmware before 1.04 had the adjustable range
from 1-4000)
Regulation Outputs
Assembly with 6 or 12 Regulation Outputs possible.
Regulation Outputs volt free with common root.
Terminals A 1-12
max. breaking capacity 5A/250VAC
Alarm contact
Opens in case of alarm and grid failure (Life Contact).
Terminals M / MS
max. breaking capacity 5A/250VAC
Temperature sensor / Digital
Input
Temperature measurement or Digital Input to switch over to
second target Pf.
Terminals T1 / T2
Setting are explained in the Alarm menu.