ESTAmat PFC-N
D.No.13157 - Rev. 02
Operating Instruction MV1181
Page 30 of 36
8.2 Switching on target Pf 2 via digital input
By using a switch, the ESTAmat PFC-N will be switched to target Pf 2.
Solution:
Using the temperature input as digital input.
Procedure:
Enable digital input
Set item 510 in expert menu to "YES".
Using digital input as n/o or n/c
In the menu item 511 can be determined whether the digital inputs as n/c (NO) or n/o
(YES) is used.
Features:
The temperature input is used as a digital input, shows the controller at active input "high"
and with not active input "low" instead of the temperature. The controller uses with active
digital input the target Pf 2 and will show "NT" in the display.