4.4 Setup (Quick start menu)
To commission the control settings are not needed. When you start the auto-initialization the
ESTAmat PFC-N checks the connection of the measurement and the outputs. With these data,
the control starts automatically. However, the ESTAmat PFC-N offers some option's for
optimal adaptation to the conditions in the system and display system data.
1.00
i
1.00
i
INFO
1.00
i MANUAL
Un = nominal voltage
Setting of nominal voltage. From
this value the upper and lower limits
for voltage monitoring is calculated
1.00
i SETUP
1.00
SETUP
Un
SETUP
400
ct
SETUP
20
Input current transformer CT ratio
e.g 250/5 = 50
pt
SETUP
1
Input voltage transformer ratio
when no VT is used the value is 1
ai
SETUP
no
"Yes" the controller performs the
auto-initialization
pfc
SETUP
on
"ON" automatic control
OFF" automatic control off
"HOLD" freeze control
cpi
SETUP
1
Target PF of control
st
SETUP
10
Latency between switching the
steps