ESTAmat PFC-N
D.No.13157 - Rev. 02
Operating Instruction MV1181
Page 13 of 36
5 EXPERT MENU ESTAmat PFC-N
To open the expert menu of ESTAmat PFC-N, choose menu item "SETUP" and hold
(
)
button until "100" appears. By using the
buttons the submenus can be selected. The
expert menu of ESTAmat PFC-N is divided into six groups, where the menu items are
logically grouped together. The following groups exist:
5.1
100
Quick start menu
Contains all important points for commission:
100
Quick start menu
MENU
FUNCTION
RANGE
Un
Nominal voltage measurement = phase voltage
100...241500
V
Setting the correct nominal voltage is needed because from this
value the upper and lower limits for voltage monitoring is calculated
(See. tolerance Nominal voltage). The Step sizes stored in Step
database relate to the adjusted nominal voltage.
Ct
Current transformer ratio
1...9600
Setting the CT factor.
Value must be entered as the ratio (eg 1000 / 5 = 200)
At devices with software version 1.04 is the adjustment range from
1-4000.
Pt
Voltage transformer ratio
1...350
Stetting the VT factor.
Value must be entered as the ratio. If the device is directly
connected to the measurement the value 1 has to be used.
Ai
Auto-Initializing Start
Yes/No
"YES" starts auto-initializing
"NO" nothing happen
If the auto-initializing starts, the controller is testing all step's with
step type "AUTO" and "FOFF" again and the step type is newly
stored in the step database. Steps that are programmed to "FON" or
"AL" will be not considered in case of new auto-initialization.
At devices with software revision before 1.04, stages which are set
to "FOFF" were not retested.