Water quality is extremely important for the optimum performance of your 

UV system. The following levels are recommended for installation:

•  Iron: < 0.3 ppm (0.3 mg/L)
•  Hardness*: < 7 gpg (120 mg/L)
•  Turbidity: < 1 NTU
•  Manganese: < 0.05 ppm (0.05 mg/L)
•  Tannins: < 0.1 ppm (0.1 mg/L)
•  UV Transmittance: > 75% (call factory for recommendations on 

applications where UVT < 75%)

* Where total hardness is less than 7 gpg, the UV unit should operate efficiently 

provided the quartz sleeve is cleaned periodically. If total hardness is over 7 

gpg, the water should be softened.

If your water chemistry contains levels in 

excess of those mentioned above, proper pre-treatment is recommended to 

correct these water problems prior to the installation of your UV disinfection 

system. These water quality parameters can be tested by your local dealer, or 

by most private analytical laboratories. Proper pre-treatment is essential for the 

UV disinfection system to operate as intended.

•  CAUTION, electronic ballast must be connected to a grounded receptacle 

and the lamp connector ground wire connected to the stainless steel 

reactor chamber.

•  The disinfection system is designed to be mounted vertically using the 

bracket at a single location such as the kitchen or bathroom sink.

•  The ballast should be mounted either above or beside the reactor chamber. 

This will prevent moisture caused by condensation from entering the ballast 

enclosure, causing a potential for ballast failure.

•  For safety purposes, the disinfection system should be connected to a 

ground fault interrupt circuit.

•  The disinfection system is intended for indoor use only, do not install 

disinfection system where it may be exposed to the weather.

•  Install the disinfection system on cold water line only.

WATER CHEMISTRY

INSTALLING YOUR UV DISINFECTION SYSTEM

7

CARTRIDGE REPLACEMENT

1.   Shut-off the water flow to the unit via the main line shut-off valve.
2.   Remove the filter sumps from the unit by turning counter-clockwise until the sump 

falls free from the head (be careful as the sumps will be full of water and they will 

be heavy).

3.   Discard the used cartridge and clean the sump housing as required. Make sure to 

thoroughly rinse the sump with water to get rid of any cleaning agents.

4.   Install the new cartridge in the reverse procedure as stated above turning the 

sump clockwise until the sump is tight. DO NOT OVER TIGHTEN.

5.   Plug UV unit into the applicable outlet and power-up system.
6.   Slowly turn on the water supply and allow any air that may now be present to 

bleed off from the system. This can easily be accomplished by partially opening 

a nearby faucet. Once the water runs without the presence of any air, return the 

system to use.

11.    Reinstall

 

sleeve

 

bolt with 2 new 

o-rings.

12.     Screw lamp into sleeve hand-tight. 

Caution: Over tightening will break 

the sleeve. 

1

2

13.  Push lamp plug onto end of lamp.
14.  Push safety cap into place.
15.  Turn off the shut-off valves.
16.  Check for leaks.
17.  Connect the system to the power 

source.

Содержание UVMax DWS11-A

Страница 1: ...r UV system is designed to provide you with years of trouble free operation with minimal maintenance required 425 Clair Rd W Guelph Ontario Canada N1L 1R1 t 1 519 763 1032 tf 1 800 265 7246 US and Can...

Страница 2: ...has been confirmed Hot chamber Allow UV Lamps UV Chamber to cool for a minimum of 10 minutes before handling Cut or ingestion Ensure the quartz sleeve or lamp is not broken cracked or damaged in any w...

Страница 3: ...ater Chemistry 4 Installing Your UV Disinfection System 4 5 Operating Maintenance Instructions 6 7 Manufacturer s Warranty 8 9 Specifications 10 Caution Protective Ground Electrical Warning Fragile Ey...

Страница 4: ...125 PSI 862 kPa Minimum operating pressure 4 PSI 27 5 kPa Maximum ambient air temperature 122 0 F 500 C Minimum ambient air temperature 320 F 00 C Maximum humidity 100 Maximum hardness 120 ppm 7 grain...

Страница 5: ...sis Replacement lamps and sleeves provided under warranty will be sent to your TrojanUVMax dealer This warranty on lamps and sleeves does not include shipping and handling charges which will be collec...

Страница 6: ...VMax products Ten Year Limited Warranty for TrojanUVMax UV Chamber VIQUA warrants the UV chamber on the TrojanUVMax products to be free from defects in material and workmanship for a period of ten 10...

Страница 7: ...ast enclosure causing a potential for ballast failure For safety purposes the disinfection system should be connected to a ground fault interrupt circuit The disinfection system is intended for indoor...

Страница 8: ...crew provided 7 The power source provided with your disinfection system must be located within 5 feet of an electrical outlet DO NOT USE AN OUTLET THAT CAN BE SWITCHED OFF IE A WASTE DISPOSAL OUTLET 5...

Отзывы: