Chapter 2 Deployment TD 03
Manual VIPA HMI
2-2
HB116E - TD03 - Rev. 07/50
Fast introduction
Build the CPU system and install the TD 03. For the installation in
operating tables and control cabinet fronts a front panel cutting of
156mmx78mm (LxW) is needed.
From the software side the connection to the CPU system happens by a
data block. This may be produced by the configuration tool TD Wizard from
VIPA.
•
Start the TD-Wizard via double click on
.
•
Type a file name for the DB into "Destination File". It is stored as STL
file. Enter the data block number into "Data Block ID". Click on
.
•
Set the language and character set. Click on
→
.
•
If wanted, activate further menu options and the password protection.
Click on
.
•
Set the bit memory byte that is accessible for the function keys and the
telegram polling rate. Click on
.
•
Enter the standard size and the number of your messages. Click on
.
•
In the appearing dialog window you can choose the areas where your
data is stored in the DB. Here normally no changes are necessary. Click
on
.
•
Now you reach the input window for your messages. Enter the
according message texts. If you want to include process data, click on
. In the now following dialog window you can enter the
data format of the process data and information about the storage path
in the DB. Confirm with
and return back to the message
window.
•
To enter more message texts, click on
.
•
Click on
to store the project at the preset path as STL file
and close TD-Wizard.
•
Start the Siemens SIMATIC manager with your project.
•
Select the folder "Sources" in the user program and select
Insert
>
External Source
.
•
Navigate to the STL file and compile this with
Edit
>
Compile
. The
corresponding DB may now be found in the folder "Blocks".
Installation
Configuration
Deployment
TD Wizard
Transfer STL into
the project
Содержание TD 03
Страница 1: ...Manual VIPA HMI TD 03 Order no VIPA HB116E_TD03 Rev 07 50...
Страница 2: ...Lerrzeichen...
Страница 6: ...Contents Manual VIPA HMI ii HB116E TD03 Rev 07 50...
Страница 40: ...Chapter 2 Deployment TD 03 Manual VIPA HMI 2 24 HB116E TD03 Rev 07 50...
Страница 54: ...Index Manual VIPA HMI A 2 HB116E TD03 Rev 07 50 M Stich...