Chapter 3 Deployment
Manual VIPA System SLIO
3-12
HB300E - FM - RE_050-1BA10 - Rev. 10/30
No main counting direction
•
The counter counts once starting with the
load value
.
•
You may count forward or backwards.
•
The count limits are set to the maximum count range.
•
At over- or under
flow
at the count limits, the counter jumps to the
according other count limit and the internal gate is automatically closed
and the status bits STS_OFLW respectively STS_UFLW are set. If
enabled additionally a process interrupt is triggered.
•
To restart the count process, you have to re-open the internal gate.
•
At interrupting gate control, the count process continuous with the last
recent
counter value
.
•
At aborting gate control, the counter starts with the
load value
.
Limits
Valid value range
Lower count limit
-2 147 483 648 (-2
31
)
Upper count limit
+2 147 483 647 (2
31
-1)
Interrupting gate control:
end value
lower
counter limit
load value
0
gate start
overflow
underflow
time
counter value
gate stop
automatically
gate start
gate stop
automatically
Aborting gate control:
end value
lower
counter limit
load value
0
gate start
overflow
underflow
time
counter value
gate stop
automatically
gate start
gate stop
automatically
Count Once
Содержание SLIO System FM 050-1BA10
Страница 1: ...VIPA System SLIO FM 050 1BA10 Manual HB300E_FM RE_050 1BA10 Rev 10 30 July 2010...
Страница 4: ...Contents Manual VIPA System SLIO ii HB300E FM RE_050 1BA10 Rev 10 30...
Страница 8: ...Safety information Manual VIPA System SLIO 4 HB300E FM RE_050 1BA10 Rev 10 30...
Страница 56: ...Chapter 3 Deployment Manual VIPA System SLIO 3 24 HB300E FM RE_050 1BA10 Rev 10 30...