![VIPA SLIO System FM 050-1BA10 Скачать руководство пользователя страница 36](http://html1.mh-extra.com/html/vipa/slio-system-fm-050-1ba10/slio-system-fm-050-1ba10_manual_1029237036.webp)
Chapter 3 Deployment
Manual VIPA System SLIO
3-4
HB300E - FM - RE_050-1BA10 - Rev. 10/30
Via parameterization you may define among others:
•
Interrupt behavior
•
Input filter
•
Counter operating mode res. behavior
•
Load value
and
end value
DS = Data set for access via CPU, Profibus and ProfiNET
IX = Index for access via CANopen
SX = Subindex for access via EtherCAT
Name
Bytes
Function
Default
DS
IX
SX
DIAG_EN 1 Diagnostic
interrupt*
00h
00h 3100h 01h
CH0A
1
Input frequency track A
02h
01h
3101h
02h
CH1B
1
Input frequency track B
02h
01h
3102h
03h
CH2R
1
Input frequency Reset
02h
01h
3103h
04h
CH3 1
reserved
00h
01h
3104h
05h
INT_I 1
Interrupt
behavior
00h
80h
3105h
06h
FCT_I 1
Counter
function
00h
80h
3106h
07h
MODE2_I
1
Counter mode 2
00h
80h
3107h
08h
MODE3_I
1
Counter mode 3
00h
80h
3108h
09h
END_I 4
End
value
00h
81h
3109h...310Ch
0Ah
LOAD_I 4
Load
value
00h
81h
310Dh...3110h
0Bh
HYST_I 1
Hysteresis
00h
81h 3111h 0Ch
CRES 1
reserved
00h
81h
3112h
0Dh
* This parameter may only be transferred at STOP state.
The counter is controlled via the internal gate (I gate). The I gate
corresponds to the software gate (SW gate).
SW gate: Open (activate):
in user program by edge 0-1 of
SW_GATE_SET in the
control word
.
Close (deactivate): in user program by edge 0-1 of
SW_GATE_RESET in the
control word
.
The following behavior for the
comparison bit
STS_COMP in the
counter
status
may be set via the parameterization:
•
No comparison:
Comparison bit
is not influenced
•
Counter value
≥
comparison value
:
Comparison bit
is set
•
Counter value
≤
comparison value
:
Comparison bit
is set
•
Counter value
=
comparison value
:
Comparison bit
is set
Please consider that the
comparison bit
may only be set, when the bit
STS_CTRL_COMP in the
counter status
is set.
Parameter data
Control counter
Comparison bit
Содержание SLIO System FM 050-1BA10
Страница 1: ...VIPA System SLIO FM 050 1BA10 Manual HB300E_FM RE_050 1BA10 Rev 10 30 July 2010...
Страница 4: ...Contents Manual VIPA System SLIO ii HB300E FM RE_050 1BA10 Rev 10 30...
Страница 8: ...Safety information Manual VIPA System SLIO 4 HB300E FM RE_050 1BA10 Rev 10 30...
Страница 56: ...Chapter 3 Deployment Manual VIPA System SLIO 3 24 HB300E FM RE_050 1BA10 Rev 10 30...