Manual VIPA System SLIO
Chapter 3 Deployment
HB300E - IM - RE_053-1DN00 - Rev. 11/21
3-9
All stations on the bus must be uniquely identified by means of an
ID address.
The setting of the DeviceNet address happens with the following
proceeding:
•
Switch the power supply to PowerOFF.
•
Set switch 1 to "0" (address).
•
Preset the DeviceNet address with switch 2 ... 7 as a binary value.
Note!
Please regard each DeviceNet address is taken once at the bus between a
number of 0 ... 63!
No. Value
Example
setting
Address
1 Configuration
0
2 2
0
= 1
1
3 2
1
= 2
1
4 2
2
= 4
0
5 2
3
= 8
0
6 2
4
= 16
0
7 2
5
= 32
1
C
1
2
4
8
16
32
--
1
0
1
2
3
4
5
6
7
8
8 not
used
---
1+2+32=35
Address: 35
•
Switch on the Power supply. The preset DeviceNet address is stored in
the RAM.
With a wrong or already used address after PowerON the SF LED (red)
lights up.
Setting the
DeviceNet
address
Settings
LED indication
SF LED
Содержание SLIO IM 053-1DN00
Страница 1: ...VIPA System SLIO IM 053 1DN00 Manual HB300E_IM RE_053 1DN00 Rev 11 21 May 2011...
Страница 4: ...Contents Manual VIPA System SLIO ii HB300E IM RE_053 1DN00 Rev 11 21...
Страница 8: ...Safety information Manual VIPA System SLIO 4 HB300E IM RE_053 1DN00 Rev 11 21...
Страница 28: ...Chapter 1 Basics and Assembly Manual VIPA System SLIO 1 20 HB300E IM RE_053 1DN00 Rev 11 21...