Manual VIPA System SLIO
Chapter 3 Deployment
HB300E - FM - RE_050-1BB00 - Rev. 10/30
3-17
The activation res. de-activation of the counter happens via an internal gate
(I gate). The I gate corresponds to the software gate (SW gate).
The
SW gate
is opened (activated) via your user application by an edge 0-1
of the bit SW_GATE_SET of the
control word
in the
output area
. The
software gate is closed (de-activated) by an edge 0-1 of the bit
SW_GATE_RESET. If the I gate was automatically closed at "counting
once", so this may only be opened with an edge 0-1 on SW_GATE_SET.
The following states influence the I gate:
SW gate
influences I gate
0 0
1
1
with edge 0-1
1
Gate function abort and interrupt
The parameterization defines if the gate interrupts or aborts the counter
process.
•
At
abort function
the counter starts counting with the
load value
after
gate restart.
load value
gate start
time
counter value
gate stopp
gate start
•
At
interrupt function
, the counter starts counting with the recent
counter
value
after gate restart.
load value
gate start
time
gate stopp
gate start
counter value
Gate function