Chapter 3 Deployment
Manual VIPA System SLIO
3-4
HB300E - FM - RE_050-1BB00 - Rev. 10/30
The counter is controlled via the internal gate (I gate). The I gate
corresponds to the software gate (SW gate).
SW gate: Open (activate):
in user program by edge 0-1
SW_GATE_SET in the
control word
.
Close (deactivate): in user program by edge 0-1
SW_GATE_RESET in the
control word
.
The following behavior for the
comparison bit
STS_COMP in the
counter
status
may be set via the parameterization:
•
No comparison:
Comparison bit
is not influenced
•
Counter value
≥
comparison value
:
Comparison bit
is set
•
Counter value
≤
comparison value
:
Comparison bit
is set
•
Counter value
=
comparison value
:
Comparison bit
is set
Please consider that the
comparison bit
may only be controlled, when the
bit STS_CTRL_COMP in the
counter status
is set.