Chapter 3 Deployment
Manual VIPA System SLIO
3-22
HB300E - IM - RE_053-1DP00 - Rev. 11/03
Note!
To connect this EasyConn plug, please use the standard PROFIBUS cable
type A (EN50170). Starting with release 5 you also can use highly flexible
bus cable: Lapp Kabel order no.: 2170222, 2170822, 2170322.
With the order no. 905-6AA00 VIPA offers the "EasyStrip" de-isolating tool
that makes the connection of the EasyConn much easier.
11
6
Dimensions in mm
The "EasyConn" bus connector is provided with a switch that is used to
activate a terminating resistor.
Attention!
The terminating resistor is only effective, if the connector
is installed at a slave and the slave is connected to a
power supply.
Note!
A complete description of installation and deployment of
the terminating resistors is delivered with the connector.
•
Loosen the screw.
•
Lift contact-cover.
•
Insert both wires into the ducts
provided (watch for the correct
line color as below!)
•
Please take care not to cause a
short circuit between screen and
data lines!
•
Close the contact cover.
•
Tighten screw
(max. tightening torque 4Nm).
The
green
line must be connected to
A
, the
red
line to
B
!
Termination with
"EasyConn"
Assembly
Please note: