Manual VIPA System SLIO
Chapter 3 Deployment
HB300E - IM - RE_053-1DP00 - Rev. 11/03
3-13
Project engineering
For project engineering a DP master engineering tool can be used like the
Siemens SIMATIC manager. Here you assign the according PROFIBUS
DP slave modules to the DP master.
A direct assignment takes place via the PROFIBUS address that you set at
the DP slave address selector.
By installing the corresponding GSD file the IM 053-1DP00 is listed at the
hardware catalog as "VIPA_053-1DP00 (DP-V0 or DP-V1)".
You'll find this at:
PROFIBUS DP
> Additional Field devices > I/O > VIPA_SLIO
For every PROFIBUS slave from VIPA there is a GSD file available. This
file may either be found on the supplied storage media or at the download
area of www.vipa.de.
The assignment of the GSD-file to your slave is shown in the following
table:
SLIO order number
GSD-file
VIPA 053-1DP00(DP-V0)
VI000C19.gsd
VIPA 053-1DP00(DP-V1)
VI010C19.gsd
Please install the required files into your configuration tool. Details on the
installation of the GSD and/or type files are available from the manual
supplied with your configuration tool.
After the installation of the GSD file you will find this entry e.g. the DP-V1
slave in the hardware catalog from Siemens at:
PROFIBUS DP >Additional field devices > I/O > VIPA_SLIO >
VIPA 053-1DP00 (DPV1)
•
Mount your PROFIBUS system.
•
Start your project engineering tool with a new project.
•
Configure a master system and create a new PROFIBUS subnet.
•
For the project engineering of the IM 053-1DP00 take the "VIPA 053-
1DP00 (DPV0)" or "VIPA 053-1DP00 (DPV1)" for each functionality from
the hardware catalog and drag it to the DP master subnet.
•
Enter a PROFIBUS address between 1 and 125 into the properties of
the DP slave and set the same address at the address switch.
•
Parameterize the DP slave (see parameters).
•
Transfer your project to the PLC.
General
GSD- file
Project
engineering