background image

                                                       

 

                       

 

- 18 -

temperature 
too high and 
running 
continually   

c.  Ambient temperature too high 
d.  Exhaust restricted  
 
 
 
e. Malfunctioning 

fans 

 
f. 

Improper evaporator or 
condenser airflow 

g. Dirty 

Condenser 

h. Iced 

evaporator 

i. Sealed 

system 

problem 

 
j. 

Undercharge or overcharge 

 

c.  Check for installation location 
d.  Leave minimum 3 ft clearance for 

the exhaust side and leave minimum 
1 foot clearance for the fresh air 
intake side  

e. Check for both evaporator and 

condenser fans  

f. 

Check for air restrictions 

 
g. Clean 

condenser 

h.  Defrost and reset temperature 
i.  Call service for checking loss of 

refrigerant or restrictions 

j.  Call service to add or remove 

refrigerant 

 

6.Unit running 

too long 

 

a.  Improper room insulation & seal 
 
b. Exhaust restricted 
 
 
 
c.  Room too large 
d. Ambient  temperature  extremely 

high 

e. Dirty Condenser 
 

a.  Check for insulation, gasket and door 

opening 

b.  Leave minimum 3 ft clearance for the 

exhaust side and leave minimum 1 
foot clearance for the fresh air intake 
side 

c.  Check for excessive size   
d. Check for installation location or 

increase setting 

e. Clean condenser 
 

7.Evaporator  

freezing up

 

a.  Evaporator air flow restriction 
b.  Unit not stopping due to air leak, 

high ambient temperature or low 
setting 

c.  Low ambient temperature 
d.  Bad thermostat or sensor 
e.  Refrigerant low or leak 
f. 

Expansion valve blockage 

a.  Check for fans, CFM 
b. Check for seal, door opening, 

ambient temperature and setting 

 
c.  Defrost the unit 
d.  Check for thermostat and sensor 
e.  Check for sealed system leakage 
f. 

Check for low side pressure 

 

8.Water leak 

a.  Unit not level  
b.  Drain line restricted 
c.  Drip tray leak 
 
d.  Very high humidity 
e.  Wine room air leak 

a.  Check for installation 
b.  Check drain line 
c.  Check for if water leak but no 

overflow 

d. Use 

dehumidifier 

e. Check for air leak and if 

 

condensation on the cooling unit 

9.Circuit 

tripping 

 

a.  Incorrect fuse or breaker 
b. Incorrect 

wirings 

c.  Overcharge of refrigerant 
d.  Condenser air restriction 
e. Failed 

components 

 

a.  Check for proper fuse or breaker 
b.  Check for wirings and connections 
c.  Call service for removing refrigerant 
d.  Check condenser fan 
e.  Call service  
 

Содержание WINE-MATE WM-1500SS

Страница 1: ...w ww ww w w wi in ne em ma at te e c co om m WINE MATE Split System Installation Operation Care Manual WM 1500SS WM 1900SS w ww ww w v vi in no ot te em mp p c co om m READ AND SAVE THESE INSTRUCTIONS...

Страница 2: ...Important Safety Information 2 Cellar Construction 3 Features Specifications 4 Installer s Instruction 7 Electrical Wiring 13 Temperature Control 15 Care Guide 16 User Troubleshooting 17 Customer Sup...

Страница 3: ...2 Important Safety Information WARNING DO NOT USE A GROUND FAULT INTERRUPTER GFI A DEDICATED 20 AMP CIRCUIT IS REQUIRED...

Страница 4: ...erature surrounding the enclosure shall not exceed the temperature of the cellar by more than 25 F No cellar wall shall receive direct sun or strong wind Lighting shall be of low wattage with a timer...

Страница 5: ...led on the wall The dimensions in inches and capacities are specified as follows MODE L EVAP UNIT COND UNIT BTU H CF M 55 F 90 F CAPACITY 55 F 75 F REFRIGERANT ELECTRICAL EVAP UNIT COND UNIT WEIGHT lb...

Страница 6: ...and suction valves installed Liquid Filter Liquid Indicator Evaporator Unit liquid line solenoid valve and expansion valve installed Temperature Controller Air Sensor Fig 1 WM15SFC Evaporator Unit Fi...

Страница 7: ...6 Fig 3 WM 150SCU Condensing Unit Fig 4 Liquid Filter Fig 5 Liquid Indicator...

Страница 8: ...for the distance between the two units After the units and the lines are installed the system must be pressure tested If no leaks are found evacuate and charge system Refrigerant amount will vary depe...

Страница 9: ...on Line 4 Pressure Control 3 Evaporator Unit The WM 15SFC evaporator units shall be installed for ceiling mount with the air supply towards horizontally and air return on the bottom The WM 19SFC evapo...

Страница 10: ...ion valve and then back to condensing unit 2 If the condensing unit is located below the evaporator unit use inverted U trap to prevent liquid from flooding back to the compressor if the elevation dif...

Страница 11: ...OD 1 2 OD R134a 15 OZ WM 1900SS 75 FT 1 4 OD 3 8 OD 3 8 OD R134a 15 OZ 5 Use of the adjustable pressure control if applicable for pump down Suction pressure setting Cut out 5 psig Cut in 25 psig Diffe...

Страница 12: ...OFF THE COMPRESSOR BEFORE POWER THE CONDENSING UNIT ONLY TURN ON THE COMPRESSOR AFTER THE CONDENSING UNIT HAS BEEN POWERED FOR 24 HOURS 9 Pressure Superheat and Subcooling Readings CAUTION THE VALVES...

Страница 13: ...subcooling o low to normal suction pressure and high head pressure Normal to high superheat and high subcooling f High room temperature high evaporator load g Undercharge h Liquid line restricted aft...

Страница 14: ...ON USE MINIMUM 14 GAUGE WIRE S IF EQUIPPED WITH LOW AMBIENT CONDITION KIT USE LOW AMBIENT TEMPERATURE WIRING DIAGRAMS A SAFETY SWITCH IS ALWAYS RECOMMENDED FOR THE CONDENSING UNIT Fig 11 WM 1500 1900S...

Страница 15: ...14 Fig 12 Low Ambient Temperature WM 1500 1900SS Electrical Wiring Diagram...

Страница 16: ...ime required to reach the desired temperature will vary depending on the quantity of bottles temperature setting and surrounding temperature Allow 24 hours to stabilize the temperature for each new te...

Страница 17: ...need to be cleaned at least every 6 months Unplug the system or disconnect power Use a vacuum cleaner with an extended attachment to clean the coil when it is dusty or dirty Plug in cooling system or...

Страница 18: ...re is 57 F and then the wine temperature is around 57 0 5 F The air is light enough to change so quickly that it maintains relatively constant average temperature that would prevent wine bottle temper...

Страница 19: ...resh air intake side c Check for excessive size d Check for installation location or increase setting e Clean condenser 7 Evaporator freezing up a Evaporator air flow restriction b Unit not stopping d...

Страница 20: ...high ambient temperatures or airflow restriction d Malfunctioning components a Add support to improve installation b Check fans cabinet washers tubing contact and loose screws c Check for airflow bloc...

Страница 21: ...20 Customer Support If you still have problems please contact us at Vinotemp International 17631 South Susana Road Rancho Dominguez CA 90221 Tel 310 886 3332 Fax 310 886 3310 Email info vinotemp com...

Страница 22: ...ties express or implied including any of fitness for a particular purpose In no event shall VINOTEMP be responsible for any consequential damages what is so ever Any modification of VINOTEMP products...

Страница 23: ...USE OF THE UNIT LOSS OF TIME OR COMMERCIAL LOSS ANY OUTER DAMAGES WHETHER INCIDENTAL CONSEQUENTIAL OR OTHERWISE THIS WARRANTY IS EXCLUSIBE AND IS IN LIEU OF ALL OTHER WARRANTIES EXPRESSED OR INPLIED...

Отзывы: