background image

                                                       

 

                       

 

- 9 -

4. Piping, Evacuating, Charging and Starting 

 

CAUTION:  

 

ALWAYS USE THE SUPERHEAT AND SUBCOOLING, PRESSURE 
READINGS TO CHARGE REFRIGERANT PROPERLY, THE LISTED 
CHARGES ARE FOR REFERENCE ONLY.  

 

CHARGE 15% MORE REFRIGERANT IF THE UNIT IS EQUIPPED WITH A 
LOW AMBIENT CONDITION KIT AND INSTALLED IN THE SUMMER.  

 
NOTES: 

 

THE LINE CONNECTION SIZES OF LIQUID FILTER & INDICATOR, THE 
VALVE CONNECTION SIZES OF CONDENSING UNIT AND THE LINE 
CONNECTION SIZES OF EVAPORATOR UNIT ARE NOT NECESSARY 
THE SAME AS THE ABOVE SPECIFIED LINE SIZES. 

 

IF THE CONDENSING UNIT IS INSTALLED ABOVE THE EVAPORATOR 
UNIT, USE THE SUCTION LINE ONE LISTED SIZE SMALLER. 

 

EXPANSION VALVE AND SOLENOID VALVE ARE INSTALLED ON 
LIQUID LINE IN THE EVAPORATOR UNIT. 
 

1)  The installation order starts from condensing unit (including receiver and 

discharge valve), liquid line filter-drier, moisture-liquid indicator, liquid line, 
to evaporator unit (including liquid line connection, solenoid valve, 
expansion valve, and suction line connection), returning to insulated 
suction line, suction valve and then back to condensing unit. 

2)  If the condensing unit is located below the evaporator unit, use inverted U 

trap to prevent liquid from flooding back to the compressor; if the elevation 
difference is more than 10 ft or the line set exceeds 75 ft, use both 
inverted U trap and suction accumulator. 

3)  If the condensing unit is located more than 10 ft above the evaporator unit, 

use U trap to aid oil returning to the compressor. 

4) Complete pipe brazing, check solenoid valve and expansion valve 

restrictions and test leak. 

5)  Hook up the drain line and check if water drains. 
6)  Both discharge and suction valves must be in the middle positions during 

evacuating and charging.  

7)  Charge the system after pipe brazing, leak testing and evacuating. Liquid 

must always be charged into the hide side. 

8)  The subcooling at the condensing unit shall be around 10°F. The charge 

may be complete when there are no more bubbles forming in the liquid 
indicator. 

9) Head pressure range: 125 ~ 150 psig at 70 ~ 90 °F condensing unit 

ambient temperature. 

10) The evaporator superheat is set around 8 ~ 10 °F at factory.  
11) Suction pressure: 30 ~ 35 psig. 
12) The temperature split crossing the evaporator shall be 8 ~ 10°F at 55°F 

wine room temperature. 

Содержание WINE-MATE WM-1500SS

Страница 1: ...w ww ww w w wi in ne em ma at te e c co om m WINE MATE Split System Installation Operation Care Manual WM 1500SS WM 1900SS w ww ww w v vi in no ot te em mp p c co om m READ AND SAVE THESE INSTRUCTIONS...

Страница 2: ...Important Safety Information 2 Cellar Construction 3 Features Specifications 4 Installer s Instruction 7 Electrical Wiring 13 Temperature Control 15 Care Guide 16 User Troubleshooting 17 Customer Sup...

Страница 3: ...2 Important Safety Information WARNING DO NOT USE A GROUND FAULT INTERRUPTER GFI A DEDICATED 20 AMP CIRCUIT IS REQUIRED...

Страница 4: ...erature surrounding the enclosure shall not exceed the temperature of the cellar by more than 25 F No cellar wall shall receive direct sun or strong wind Lighting shall be of low wattage with a timer...

Страница 5: ...led on the wall The dimensions in inches and capacities are specified as follows MODE L EVAP UNIT COND UNIT BTU H CF M 55 F 90 F CAPACITY 55 F 75 F REFRIGERANT ELECTRICAL EVAP UNIT COND UNIT WEIGHT lb...

Страница 6: ...and suction valves installed Liquid Filter Liquid Indicator Evaporator Unit liquid line solenoid valve and expansion valve installed Temperature Controller Air Sensor Fig 1 WM15SFC Evaporator Unit Fi...

Страница 7: ...6 Fig 3 WM 150SCU Condensing Unit Fig 4 Liquid Filter Fig 5 Liquid Indicator...

Страница 8: ...for the distance between the two units After the units and the lines are installed the system must be pressure tested If no leaks are found evacuate and charge system Refrigerant amount will vary depe...

Страница 9: ...on Line 4 Pressure Control 3 Evaporator Unit The WM 15SFC evaporator units shall be installed for ceiling mount with the air supply towards horizontally and air return on the bottom The WM 19SFC evapo...

Страница 10: ...ion valve and then back to condensing unit 2 If the condensing unit is located below the evaporator unit use inverted U trap to prevent liquid from flooding back to the compressor if the elevation dif...

Страница 11: ...OD 1 2 OD R134a 15 OZ WM 1900SS 75 FT 1 4 OD 3 8 OD 3 8 OD R134a 15 OZ 5 Use of the adjustable pressure control if applicable for pump down Suction pressure setting Cut out 5 psig Cut in 25 psig Diffe...

Страница 12: ...OFF THE COMPRESSOR BEFORE POWER THE CONDENSING UNIT ONLY TURN ON THE COMPRESSOR AFTER THE CONDENSING UNIT HAS BEEN POWERED FOR 24 HOURS 9 Pressure Superheat and Subcooling Readings CAUTION THE VALVES...

Страница 13: ...subcooling o low to normal suction pressure and high head pressure Normal to high superheat and high subcooling f High room temperature high evaporator load g Undercharge h Liquid line restricted aft...

Страница 14: ...ON USE MINIMUM 14 GAUGE WIRE S IF EQUIPPED WITH LOW AMBIENT CONDITION KIT USE LOW AMBIENT TEMPERATURE WIRING DIAGRAMS A SAFETY SWITCH IS ALWAYS RECOMMENDED FOR THE CONDENSING UNIT Fig 11 WM 1500 1900S...

Страница 15: ...14 Fig 12 Low Ambient Temperature WM 1500 1900SS Electrical Wiring Diagram...

Страница 16: ...ime required to reach the desired temperature will vary depending on the quantity of bottles temperature setting and surrounding temperature Allow 24 hours to stabilize the temperature for each new te...

Страница 17: ...need to be cleaned at least every 6 months Unplug the system or disconnect power Use a vacuum cleaner with an extended attachment to clean the coil when it is dusty or dirty Plug in cooling system or...

Страница 18: ...re is 57 F and then the wine temperature is around 57 0 5 F The air is light enough to change so quickly that it maintains relatively constant average temperature that would prevent wine bottle temper...

Страница 19: ...resh air intake side c Check for excessive size d Check for installation location or increase setting e Clean condenser 7 Evaporator freezing up a Evaporator air flow restriction b Unit not stopping d...

Страница 20: ...high ambient temperatures or airflow restriction d Malfunctioning components a Add support to improve installation b Check fans cabinet washers tubing contact and loose screws c Check for airflow bloc...

Страница 21: ...20 Customer Support If you still have problems please contact us at Vinotemp International 17631 South Susana Road Rancho Dominguez CA 90221 Tel 310 886 3332 Fax 310 886 3310 Email info vinotemp com...

Страница 22: ...ties express or implied including any of fitness for a particular purpose In no event shall VINOTEMP be responsible for any consequential damages what is so ever Any modification of VINOTEMP products...

Страница 23: ...USE OF THE UNIT LOSS OF TIME OR COMMERCIAL LOSS ANY OUTER DAMAGES WHETHER INCIDENTAL CONSEQUENTIAL OR OTHERWISE THIS WARRANTY IS EXCLUSIBE AND IS IN LIEU OF ALL OTHER WARRANTIES EXPRESSED OR INPLIED...

Отзывы: