INSTALLATION INSTRUCTIONS
Hydrosense Conventional Water Detection System
Document Part No. 3500012 REV03
Page | 15 of 27
Table 1
Code
FUNCTION
COMMENTS
UXX
CONFIGURATION UPDATE COUNT
Number incremented each time access level 3 config
changed
C00
SOUNDER DELAY TIME = 30 SECONDS
Introduces a time delay before sounders operate.
C01
SOUNDER DELAY TIME = 1 MINUTE
C02
SOUNDER DELAY TIME = 2 MINUTES
C03
SOUNDER DELAY TIME = 3 MINUTES
C04
SOUNDER DELAY TIME = 4 MINUTES
C05
SOUNDER DELAY TIME = 5 MINUTES
C06
SOUNDER DELAY TIME = 6 MINUTES
C07
SOUNDER DELAY TIME = 7 MINUTES
C08
SOUNDER DELAY TIME = 8 MINUTES
C09
SOUNDER DELAY TIME = 9 MINUTES
C10
COMMON ALARM MODE
All sounders operate upon any alarm condition.
C11
2 STAGE MODE
Continuous sounders in alarm zone, others pulsed.
C12
ZONAL MODE
Only sounders connected to zone in alarm operate.
C21
DISABLE BUZZER
Buzzer will not operate in alarm condition.
C22
DISABLE FAULT OUTPUT
Fault relay will only operate under total power loss.
C23
DISABLE EARTH FAULT MONITORING
Earth fault conditions will show a fault condition.
C24
PULSE R0V OUTPUT
0V pulses when alarm triggered.
C27
REMOVE AUX 24V ON SYSTEM RESET
24V supply switches off for 5s when panel reset
C28
INDICATE CALL POINT ACTIVATION
C29
DO NOT RE-SOUND ALARMS FROM ANOTHER ZONE
Silenced sounders do not re-sound with further zone
activations.
C31
ZONE 1 ALARM FROM DETECTOR DELAYED
Sounder outputs will be delayed by time set at options
0-9 when selected zone(s) triggered by Hydrowire or
Floor Probe only.
C32
ZONE 2 ALARM FROM DETECTOR DELAYED
C33
ZONE 3 ALARM FROM DETECTOR DELAYED
C34
ZONE 4 ALARM FROM DETECTOR DELAYED
C35
ZONE 5 ALARM FROM DETECTOR DELAYED
C36
ZONE 6 ALARM FROM DETECTOR DELAYED
C37
ZONE 7 ALARM FROM DETECTOR DELAYED
C38
ZONE 8 ALARM FROM DETECTOR DELAYED
C41
ZONE 1 ALARM FROM CALL POINT DELAYED
Sounder outputs will be delayed by time set at options
0-9 when selected zone(s) triggered by call point only
C42
ZONE 2 ALARM FROM CALL POINT DELAYED
C43
ZONE 3 ALARM FROM CALL POINT DELAYED
C44
ZONE 4 ALARM FROM CALL POINT DELAYED
C45
ZONE 5 ALARM FROM CALL POINT DELAYED
C46
ZONE 6 ALARM FROM CALL POINT DELAYED
C47
ZONE 7 ALARM FROM CALL POINT DELAYED
C48
ZONE 8 ALARM FROM CALL POINT DELAYED
C71
ZONE 1 SHORT CIRCUIT INDICATES ALARM
Changes the trigger threshold of the zone so that the
control panel can be used on older systems that uses
short circuit to trigger the alarm
C72
ZONE 2 SHORT CIRCUIT INDICATES ALARM
C73
ZONE 3 SHORT CIRCUIT INDICATES ALARM
C74
ZONE 4 SHORT CIRCUIT INDICATES ALARM
C75
ZONE 5 SHORT CIRCUIT INDICATES ALARM
C76
ZONE 6 SHORT CIRCUIT INDICATES ALARM
C77
ZONE 7 SHORT CIRCUIT INDICATES ALARM
C78
ZONE 8 SHORT CIRCUIT INDICATES ALARM
C81
ZONE 1 NON-LATCHING
Renders the zone self-resetting so that it can be used
to receive signals from other systems and will reset
when the input is removed.
Note: It can take up to 20 seconds for zone to reset
itself when sounders are operating.
C82
ZONE 2 NON-LATCHING
C83
ZONE 3 NON-LATCHING
C84
ZONE 4 NON-LATCHING
C85
ZONE 5 NON-LATCHING
C86
ZONE 6 NON-LATCHING
C87
ZONE 7 NON-LATCHING
C88
ZONE 8 NON-LATCHING
C91
ZONE 1 NON- SOUNDER MODE
Prevents the zone from operating the two common
sounder outputs.
C92
ZONE 2 NON- SOUNDER MODE
C93
ZONE 3 NON- SOUNDER MODE