INSTALLATION INSTRUCTIONS 
Hydrosense Conventional Water Detection System 

  

 

 

Document Part No. 3500012 REV03 

Page | 15 of 27 

 

Table 1

 

Code 

FUNCTION 

COMMENTS 

UXX 

CONFIGURATION UPDATE COUNT 

Number  incremented  each  time  access  level  3  config 
changed 

C00 

SOUNDER DELAY TIME = 30 SECONDS 

Introduces a time delay before sounders operate. 

C01 

SOUNDER DELAY TIME = 1 MINUTE 

C02 

SOUNDER DELAY TIME = 2 MINUTES 

C03 

SOUNDER DELAY TIME = 3 MINUTES 

C04 

SOUNDER DELAY TIME = 4 MINUTES 

C05 

SOUNDER DELAY TIME = 5 MINUTES 

C06 

SOUNDER DELAY TIME = 6 MINUTES 

C07 

SOUNDER DELAY TIME = 7 MINUTES 

C08 

SOUNDER DELAY TIME = 8 MINUTES 

C09 

SOUNDER DELAY TIME = 9 MINUTES 

C10 

COMMON ALARM MODE 

All sounders operate upon any alarm condition. 

C11 

2 STAGE MODE 

Continuous sounders in alarm zone, others pulsed. 

C12 

ZONAL MODE 

Only sounders connected to zone in alarm operate. 

C21 

DISABLE BUZZER 

Buzzer will not operate in alarm condition. 

C22 

DISABLE FAULT OUTPUT 

Fault relay will only operate under total power loss. 

C23 

DISABLE EARTH FAULT MONITORING 

Earth fault conditions will show a fault condition. 

C24 

PULSE R0V OUTPUT 

0V pulses when alarm triggered. 

C27 

REMOVE AUX 24V ON SYSTEM RESET 

24V supply switches off for 5s when panel reset 

C28 

INDICATE CALL POINT ACTIVATION 

 

C29 

DO NOT RE-SOUND ALARMS FROM ANOTHER ZONE 

Silenced  sounders  do  not  re-sound  with  further  zone 
activations. 

 

 

 

C31 

ZONE 1 ALARM FROM DETECTOR DELAYED 

Sounder outputs will be delayed by time set at options 
0-9  when  selected  zone(s)  triggered  by  Hydrowire  or 
Floor Probe only. 

C32 

ZONE 2 ALARM FROM DETECTOR DELAYED

 

C33 

ZONE 3 ALARM FROM DETECTOR DELAYED

 

C34 

ZONE 4 ALARM FROM DETECTOR DELAYED 

C35 

ZONE 5 ALARM FROM DETECTOR DELAYED 

C36 

ZONE 6 ALARM FROM DETECTOR DELAYED 

C37 

ZONE 7 ALARM FROM DETECTOR DELAYED 

C38 

ZONE 8 ALARM FROM DETECTOR DELAYED 

 

 

 

C41 

ZONE 1 ALARM FROM CALL POINT DELAYED 

Sounder outputs will be delayed by time set at options 
0-9 when selected zone(s) triggered by call point only 

C42 

ZONE 2 ALARM FROM CALL POINT DELAYED

 

C43 

ZONE 3 ALARM FROM CALL POINT DELAYED

 

C44 

ZONE 4 ALARM FROM CALL POINT DELAYED

 

C45 

ZONE 5 ALARM FROM CALL POINT DELAYED

 

C46 

ZONE 6 ALARM FROM CALL POINT DELAYED

 

C47 

ZONE 7 ALARM FROM CALL POINT DELAYED

 

C48 

ZONE 8 ALARM FROM CALL POINT DELAYED

 

 

 

 

C71 

ZONE 1 SHORT CIRCUIT INDICATES ALARM 

Changes  the  trigger  threshold  of  the  zone  so  that  the 
control panel can be used on older systems that uses 
short circuit to trigger the alarm 

C72 

ZONE 2 SHORT CIRCUIT INDICATES ALARM

 

C73 

ZONE 3 SHORT CIRCUIT INDICATES ALARM

 

C74 

ZONE 4 SHORT CIRCUIT INDICATES ALARM 

C75 

ZONE 5 SHORT CIRCUIT INDICATES ALARM 

C76 

ZONE 6 SHORT CIRCUIT INDICATES ALARM 

C77 

ZONE 7 SHORT CIRCUIT INDICATES ALARM 

C78 

ZONE 8 SHORT CIRCUIT INDICATES ALARM 

 

 

 

C81 

ZONE 1 NON-LATCHING 

Renders the zone self-resetting so that it can be used 
to receive signals from other systems and will reset 
when the input is removed.  
Note: It can take up to 20 seconds for zone to reset 
itself when sounders are operating. 
 

C82 

ZONE 2 NON-LATCHING 

C83 

ZONE 3 NON-LATCHING 

C84 

ZONE 4 NON-LATCHING 

C85 

ZONE 5 NON-LATCHING 

C86 

ZONE 6 NON-LATCHING 

C87 

ZONE 7 NON-LATCHING 

C88 

ZONE 8 NON-LATCHING 

 

 

 

C91 

ZONE 1 NON- SOUNDER MODE 

Prevents the zone from operating the two common 
sounder outputs.  
 

C92 

ZONE 2 NON- SOUNDER MODE 

C93 

ZONE 3 NON- SOUNDER MODE

 

www.acornfiresecurity.com

www.acornfiresecurity.com

Содержание hydrosense HSFPI-100

Страница 1: ...Delivering a New Standard in Water Leak Detection Installation Instructions 3500012 Rev 03 June 2020 By www acornfiresecurity com www acornfiresecurity com...

Страница 2: ...rowire Cable 6 System Installation Notes 6 Panel Installation 7 Safety 7 Panel Mounting 7 Removing the front facia 8 Control relays 12 Access level 2 configuration options 13 Access level 3 configurat...

Страница 3: ...t will continuously monitor the potential hazards 24 hours a day and has the facility for 24 hours battery standby in the event of power failures Any water penetration detected will be signalled to a...

Страница 4: ...d to the panel through the Connection Interface As soon as the cable detects moisture this will trigger an alarm For the cable to measure water on the surface then it is recommended that the cable is...

Страница 5: ...eads are available in 1m HY ZB01 3m HY ZB03 and 10m HY ZB10 lengths Control and Indicating Equipment of a Hydrosense System Control Panel 2 to 8 Zones HSCP Series This panel is available in 2 4 and 8...

Страница 6: ...0 Banshee Excel Lite Combined white sounder and blue strobe 8581800 Design Planning Design Notes Water finds its own level so careful consideration must be given to slopes and dips in the area to be p...

Страница 7: ...tres Recommended pitch between cable for area protection 2 metres Minimum bend radius 150mm Note Do not mix probes and Hydrowire on the same zone System Installation Notes 1 Check design with the kit...

Страница 8: ...from either 110V or 230V 50Hz mains supplies depending upon model and is of class 1 construction As such it must be connected to a protective earthing conductor in the fixed wiring of the installatio...

Страница 9: ...ional cable entry points are required all swarf and debris caused by drilling of additional cable entries must be cleared before power is applied to the panel Figure 1 G P E4 E4 5mm DIAMETER SCREWS FI...

Страница 10: ...e must not exceed 25 ohms Wiring should enter the enclosure at the top of the panel using the knockouts provided and be formed tidily to the appropriate terminals leaving enough wire to ensure that th...

Страница 11: ...nnect the RS485 bus and power to each repeater panel Up to 7 repeater panels may be connected and each board has terminals for the incoming cables and outgoing cables All except the last RS485 device...

Страница 12: ...n panel wait for a few seconds and the main panel will show the addresses of the ancillary boards that were found on the display for instance o1 indicates that an ancillary board at address 1 has been...

Страница 13: ...be exceeded under any circumstances Typically the Aux 24V output of the control panel is switched through these relays and used to control other systems Fault relay The fault relay is normally energis...

Страница 14: ...end upon panel d1 8 Disable Zone 1 8 total number of zones will depend upon panel db Disable Sounders Ad Activate Alarm Delays t1 8 Test zone Selecting t1 through to t8 puts respective zone into test...

Страница 15: ...e 6 Figure 6 Configuration options are simple to enter using the codes in Table 1 below When the control panel is at Access Level 3 the sub text of the Mode and Select buttons is used to enter a numbe...

Страница 16: ...FROM DETECTOR DELAYED C34 ZONE 4 ALARM FROM DETECTOR DELAYED C35 ZONE 5 ALARM FROM DETECTOR DELAYED C36 ZONE 6 ALARM FROM DETECTOR DELAYED C37 ZONE 7 ALARM FROM DETECTOR DELAYED C38 ZONE 8 ALARM FROM...

Страница 17: ...e control panel fails to carry out its operation correctly it will attempt to restart itself This process is called a watchdog and the control panel must record and indicate these events If a watchdog...

Страница 18: ...equipment This LED indicates that fuse protecting the R0V output has operated and the rating of this output has been exceeded The fuse is a self resetting type and the supply will resume when the fau...

Страница 19: ...two Hydrowires is no more than 2 metres For localised protection of sources of potential water leakage such as air conditioning and water filled radiators the distance between Hydrowires may be greate...

Страница 20: ...e discarded It is advisable to leave the lid off the control panel until all testing is complete NOTE The Connection Interfaces cannot be daisy chained together only one Connection Interface can be co...

Страница 21: ...e forefinger and thumb into a cup of tap water shaking off the excess drips and then gripping the Hydrowire firmly whilst rolling it slowly This should produce an alarm condition at the control panel...

Страница 22: ...etection cable Part Number Description Quantity HSCP S 4 230 4 Zone Control panel 1 HYDW 10 Hydrowire cable 10m 8 HS HWCI EOL End Of Line Device 2 HS HWCI Hydrowire Connection Interface 2 HS WLDP Hydr...

Страница 23: ...d installed on the last Junction box 2 Unplug the Floor Probe s and check that a Fault is reported 3 Remove power from the Control Panel Disconnect the Floor Probe s and store ready for installation 4...

Страница 24: ...5mm2 2 core cable HYLCB to the Z and Z terminals at the control panel Figure 10 Floor Probe Remote Lamp Connection In some installations particularly in floor voids it is desirable to identify the are...

Страница 25: ...oor Probe Testing 1 This is best achieved by wetting both of the brass contacts simultaneously with fresh water 2 This should produce an immediate reaction at the control panel the LED mounted on top...

Страница 26: ...25 of 27 Probe Layout Figure 11 Part Number Description Quantity HSCP S 2 230 2 Zone Control panel 1 HS WLDP Hydrosense Floor Probe 20 HS WLJB Hydrosense Junction Box 20 HSVS Voice Sounder 1 Y7 12 7A...

Отзывы: