INSTALLATION INSTRUCTIONS
Hydrosense Conventional Water Detection System
Document Part No. 3500012 REV03
Page | 8 of 27
It should be positioned in an accessible place as agreed with the end user.
Suitable fixings should be used at all fixing points such that the control panel is securely
mounted and is not liable to move once fixed.
The control panel should not be mounted in another enclosure or near sources of excessive
heat.
Cables should be connected using suitable cable glands fitted to the knockouts provided. If
additional cable entry points are required, all swarf and debris caused by drilling of additional
cable entries must be cleared before power is applied to the panel.
Figure 1
G
P
E4
E4
5mm DIAMETER SCREWS
FIX TO FLAT SURFACE USING
SUITABLE WALL PLUGS
SIDE VIEW
FRONT VIEW
Sufficient room should be available to the left of the panel to allow the front door to be
opened as per diagram below;
Removing the front facia
Open the cabinet with the supplied key, before the fascia can be removed it will be
necessary to unplug the three way terminal block on the left hand side of the PCB. The
fascia of the control panel is held in place by countersunk screws. Undo the two screws and