Delivering a New Standard in Water Leak Detection

Installation Instructions

3500012  Rev 03  June 2020

By

www.acornfiresecurity.com

www.acornfiresecurity.com

Содержание hydrosense HSFPI-100

Страница 1: ...Delivering a New Standard in Water Leak Detection Installation Instructions 3500012 Rev 03 June 2020 By www acornfiresecurity com www acornfiresecurity com...

Страница 2: ...rowire Cable 6 System Installation Notes 6 Panel Installation 7 Safety 7 Panel Mounting 7 Removing the front facia 8 Control relays 12 Access level 2 configuration options 13 Access level 3 configurat...

Страница 3: ...t will continuously monitor the potential hazards 24 hours a day and has the facility for 24 hours battery standby in the event of power failures Any water penetration detected will be signalled to a...

Страница 4: ...d to the panel through the Connection Interface As soon as the cable detects moisture this will trigger an alarm For the cable to measure water on the surface then it is recommended that the cable is...

Страница 5: ...eads are available in 1m HY ZB01 3m HY ZB03 and 10m HY ZB10 lengths Control and Indicating Equipment of a Hydrosense System Control Panel 2 to 8 Zones HSCP Series This panel is available in 2 4 and 8...

Страница 6: ...0 Banshee Excel Lite Combined white sounder and blue strobe 8581800 Design Planning Design Notes Water finds its own level so careful consideration must be given to slopes and dips in the area to be p...

Страница 7: ...tres Recommended pitch between cable for area protection 2 metres Minimum bend radius 150mm Note Do not mix probes and Hydrowire on the same zone System Installation Notes 1 Check design with the kit...

Страница 8: ...from either 110V or 230V 50Hz mains supplies depending upon model and is of class 1 construction As such it must be connected to a protective earthing conductor in the fixed wiring of the installatio...

Страница 9: ...ional cable entry points are required all swarf and debris caused by drilling of additional cable entries must be cleared before power is applied to the panel Figure 1 G P E4 E4 5mm DIAMETER SCREWS FI...

Страница 10: ...e must not exceed 25 ohms Wiring should enter the enclosure at the top of the panel using the knockouts provided and be formed tidily to the appropriate terminals leaving enough wire to ensure that th...

Страница 11: ...nnect the RS485 bus and power to each repeater panel Up to 7 repeater panels may be connected and each board has terminals for the incoming cables and outgoing cables All except the last RS485 device...

Страница 12: ...n panel wait for a few seconds and the main panel will show the addresses of the ancillary boards that were found on the display for instance o1 indicates that an ancillary board at address 1 has been...

Страница 13: ...be exceeded under any circumstances Typically the Aux 24V output of the control panel is switched through these relays and used to control other systems Fault relay The fault relay is normally energis...

Страница 14: ...end upon panel d1 8 Disable Zone 1 8 total number of zones will depend upon panel db Disable Sounders Ad Activate Alarm Delays t1 8 Test zone Selecting t1 through to t8 puts respective zone into test...

Страница 15: ...e 6 Figure 6 Configuration options are simple to enter using the codes in Table 1 below When the control panel is at Access Level 3 the sub text of the Mode and Select buttons is used to enter a numbe...

Страница 16: ...FROM DETECTOR DELAYED C34 ZONE 4 ALARM FROM DETECTOR DELAYED C35 ZONE 5 ALARM FROM DETECTOR DELAYED C36 ZONE 6 ALARM FROM DETECTOR DELAYED C37 ZONE 7 ALARM FROM DETECTOR DELAYED C38 ZONE 8 ALARM FROM...

Страница 17: ...e control panel fails to carry out its operation correctly it will attempt to restart itself This process is called a watchdog and the control panel must record and indicate these events If a watchdog...

Страница 18: ...equipment This LED indicates that fuse protecting the R0V output has operated and the rating of this output has been exceeded The fuse is a self resetting type and the supply will resume when the fau...

Страница 19: ...two Hydrowires is no more than 2 metres For localised protection of sources of potential water leakage such as air conditioning and water filled radiators the distance between Hydrowires may be greate...

Страница 20: ...e discarded It is advisable to leave the lid off the control panel until all testing is complete NOTE The Connection Interfaces cannot be daisy chained together only one Connection Interface can be co...

Страница 21: ...e forefinger and thumb into a cup of tap water shaking off the excess drips and then gripping the Hydrowire firmly whilst rolling it slowly This should produce an alarm condition at the control panel...

Страница 22: ...etection cable Part Number Description Quantity HSCP S 4 230 4 Zone Control panel 1 HYDW 10 Hydrowire cable 10m 8 HS HWCI EOL End Of Line Device 2 HS HWCI Hydrowire Connection Interface 2 HS WLDP Hydr...

Страница 23: ...d installed on the last Junction box 2 Unplug the Floor Probe s and check that a Fault is reported 3 Remove power from the Control Panel Disconnect the Floor Probe s and store ready for installation 4...

Страница 24: ...5mm2 2 core cable HYLCB to the Z and Z terminals at the control panel Figure 10 Floor Probe Remote Lamp Connection In some installations particularly in floor voids it is desirable to identify the are...

Страница 25: ...oor Probe Testing 1 This is best achieved by wetting both of the brass contacts simultaneously with fresh water 2 This should produce an immediate reaction at the control panel the LED mounted on top...

Страница 26: ...25 of 27 Probe Layout Figure 11 Part Number Description Quantity HSCP S 2 230 2 Zone Control panel 1 HS WLDP Hydrosense Floor Probe 20 HS WLJB Hydrosense Junction Box 20 HSVS Voice Sounder 1 Y7 12 7A...