30
Thermostat
Communication objects and ETS parameters
ETS text
Values available
Comment
[
Default value
]
Relay
0 = General Use
For general use or control of
solenoid valve from radiator
system associated with
thermostat A and B
1 = Channel A: Fan coil
Speed V1
2 = Channel B: Fan coil
Speed V1
[0]
Mode
0 = Normal
Normal = step-step
Timed = one-position stable
1 = Timed
[0]
On Delay
0...60min
Mode = Normal
[10 sec]
Off Delay
0...60min
[10 sec]
Duration
0...60min
Mode = Timed
[10 sec]
Relay
0 = Normally open
Status of thermostat output
at rest
1 = Normally closed
[1]
N.B. The relay can be paired with the speed of the fan
coil only in the case of 3-speed fan coils or proportional
3-speed fan coils but NOT in the case of proportional fan
coils.
Relay
The output can be configured as a normal switch or for the fan,
with speed V1.
Relay parameters
Relay parameters