Thermostat

Communication objects and ETS parameters

Proportional/Integral (PI) control

This type of control uses a more advanced algorithm that keeps 
the temperature inside the room more stable, increasing comfort. 
This algorithm works by switching the system on and off so as 
to be like a gradual increase or decrease in the system's thermal 
(or refrigerating) power. To obtain optimal performance you need 
to perform the calibration according to the type of room and 
heating system.
Define the variables:
- Ta = room temperature
- Sp = current setpoint
- Kp = coefficient of the proportional component
- Ki = coefficient of the integral component
- Bp = proportional band
- Ti = integrative time
the algorithm is characterised by the following parameters:
• 

Proportional band

: used to calculate the coefficient Kp = 100 

/ Bp and corresponds to the breadth of the proportional control 
band. Starting from the set temperature, this value is the 
temperature range in which the system power goes from 0% 
to 100%. 

For example

: with the (heating) temperature set to 

20.0°C and Band (P) =4.0°C, the thermostat runs the heating 
system at 100% when Ta is <= 16.0°C; as this temperature 
increases, the system power is consequently lowered down 
to 0% when Ta reaches 20°C. The value must be set taking 
account of the thermal capacity of the room to control; in 
general, it is recommended to use small values for rooms with 
a good level of thermal insulation and vice versa.

• 

Integrative time

: used to calculate the coefficient Ki = Kp / Ti 

and corresponds to the time passed which, when equal to the 
deviation from the setpoint (error), the integrative component 
generates a contribution equal to that generated by the 
proportional component. The integral contribution reduces the 
error on full operation if thermal energy is lost in the room to 
be controlled, as this contribution increases according to the 
time during which the setpoint is not reached. If this value is not 
set correctly, it can cause transients with variations around the 
setpoint or it may take longer to reach the setpoint.

Proportional integral PWM: 

PI control with On/Off valve

Continuous integral proportional:

 PI control with proportional 

valve

The parameters of the proportional and integral coefficients Kp 
and Ki are set using the ETS software: the proportional coefficient 
Kp for heating corresponds to the “

Heating Proportional Value

” 

parameter while the coefficient for cooling is set using the 

Cooling Proportional Value

” parameter. The integral time Ti 

is set with the "

Heating Integral Value

” and “

Cooling Integral 

Value

” parameters for heating and cooling, respectively.

The PI control parameters should be set according to the type 
of heating or cooling system used, the size of the room and its 
thermal insulation.

IMPORTANT

: Generally, when using fan coils, PI control is not 

used. The valve is typically managed with On/Off control and On/
Off valve or proportional valve (0%-100%); the fine adjustment is 
then made using the fan speed.

COMMUNICA

TION OBJECTS

Содержание 02952

Страница 1: ...Installer manual BUILDING AUTOMATION 02952 KNX touch thermostat ...

Страница 2: ...Index ...

Страница 3: ...GENERAL CHARACTERISTICS AND FUNCTIONS from page 5 COMMUNICATION OBJECTS AND ETS PARAMETERS from page 7 FAQ from page 31 COMMUNICATION OBJECTS GENERAL CHARACTERISTICS AND FUNCTIONS FAQ ...

Страница 4: ...4 For all the details about the Well contact Plus system refer to the installer manual that can be downloaded from the Software Product Software Well contact Plus section of the website www vimar com ...

Страница 5: ...t and the speed of the fan coil the configuration of the operating modes and the selection of thermostat A or B to view control it has an RGB backlit display whose colours can be adjusted via parameters with ETS Display icons Note In 4 pipe systems the display may show errors E1 E2 E3 E4 as illustrated on the next page Behaviour after bus power on off Bus power off Bus power on the status will be ...

Страница 6: ...oint with the and buttons on the thermostat will also cause a change to the value of the Shift Setpoint resulting in a shift of the two current summer winter setpoint values the room temperature will therefore not become the one set by the guest but that of the summer winter setpoint which at that moment is closest to the value of the current temperature in the room Between the two summer winter s...

Страница 7: ...0 11 should be used 2 byte C W U Low 8 External Temperature 7 KNX probe temperature on bus To see the temperature read by a KNX sensor con nected to the bus to see the temperatures measured by thermostats A B with Well Contact Suite software objects nos 10 11 should be used 2 byte C W U Low 9 External Temperature 8 KNX probe temperature on bus To see the temperature read by a KNX sensor con nected...

Страница 8: ...Winter Standby setpoint 2 byte C R W T U Low 27 Winter Energy Saving A Setpoint status control To read and set the Winter Economy setpoint 2 byte C R W T U Low 28 Winter Protected A Setpoint status control To read and set the Winter Antifreeze setpoint 2 byte C R W T U Low 29 Summer Comfort A Setpoint status control To read and set the Summer Comfort setpoint 2 byte C R W T U Low 30 Summer Standby...

Страница 9: ...TO if the selected fan has 3 speeds 1 bit C W U Low 44 Proportional 0 100 A Fan Outputs Used to read the proportional speed of the fan coil fan if the selected fan is proportional with 3 speeds with the 8 Bit Object Proportional 0 100 This object is used for controlling proportional actuators 1 byte C R T Low 45 Off A Fan Outputs Used to read the deactivation status of all 3 speeds if the selected...

Страница 10: ...rating mode by sending a Byte 1 Comfort 2 StandBy 3 Economy 4 Protection If you use supervision with Well Contact Suite this object must be associated with a group 1 byte C W U Low 64 Thermostat Mode B Mode status To read the set operating mode by sending a Byte 1 Comfort 2 StandBy 3 Economy 4 Protection If you use supervision with Well Contact Suite this object must be associated with a group 1 b...

Страница 11: ...R T Low 81 Cooling Heating Valve B Valve If the Valve parameter is set for 2 pipe proportional systems for proportional valve management to be used to control the head of a radiating system or for the proportional valve of a fan coil 1 byte C R T Low 81 Cooling Valve B Valve If the Valve parameter is set for 4 pipe proportional systems for Summer valve management to be used to control the head of ...

Страница 12: ...V2 speed B Fan Disable To disable speed V2 if the selected fan has 3 speeds 1 bit C R W T U Low 98 V3 speed B Fan Disable To disable speed V3 if the selected fan has 3 speeds 1 bit C R W T U Low Thermostat B window 99 Window Sensor B Window Object to be paired with the input to which a win dow contact is connected so that the thermostat switches to OFF PROTECTED when the window is opened depending...

Страница 13: ...by a KNX probe connected to the bus 2 byte C W U Low 115 Setpoint shift increase Setpoint To control an increase equivalent to setpoint shift step of the current current setpoint setpoint set by ETS on the thermostat for the various operating modes CMF STBY etc The temperature shift permitted is limited to the range set by the parameter Guest Control Permitted 1 bit C W U Low 116 Setpoint shift de...

Страница 14: ...y of disa bling the heating icon on the display No Yes Cooling icon visible Yes Possibility of disabling the air conditioning icon on the display No Yes Button Activation 0 Enable You can choose whether to make the thermostat buttons operative 1 Disable 0 Temperature units 0 Celsius Only for the display 1 Fahrenheit 0 Enable Menu 0 Disable If enabled the thermostat operating mode can be changed Th...

Страница 15: ... Disable Button Activation Enable Display Current Temperature Setpoint Current Display Off View Difference Setpoint Note In View Setpoint Difference mode the difference between the Setpoint set via configuration by ETS and the Setpoint modified locally by the user is displayed When the set Setpoint is the design Setpoint the thermostat displays 0 0 COMMUNICATION OBJECTS ...

Страница 16: ...ar Colour customisation Ecometer Mode ETS text Values available Comment Default value Input Function 0 General Use If set as General use it also sends 0 1 over the bus towards a supervisor 1 Window Sensor 0 Function for gener al use 0 Switching on Rising Edge Rising edge close contact 1 Toggle on Rising Edge Falling edge open contact 2 Switching on Falling Edge Switching sends a 1 bit value On Off...

Страница 17: ...Vimar wired NTC probe if present and the KNX probes this determines the relative importance for calcu lating the weighted average of the measured temperatures 0 Cyclic Send Time 0 Off Sets the frequency in minutes with which the ther mostat A B must send the measured temperature value or the weighted average of the probes over the bus to a supervisor Activates cyclic send of object no 10 and 11 Cu...

Страница 18: ... Sets the minimum temper ature change made by the guest with respect to the setpoint that results in the current setpoint being sent over the bus towards a supervisor 0 1 C 0 2 C 0 3 C 0 4 C 0 5 C 0 6 C 0 7 C 0 8 C 0 9 C 1 0 C 0 Off Reset Setpoint Shift in Economy Mode Yes By selecting Yes when the thermostat goes into Energy Saving Economy mode the setpoint set by the user in Comfort and Standby ...

Страница 19: ...hermostat goes to in Protected mode if you set Off when the thermostat is in Protected mode it will turn off tempera ture control and will not send the current setpoint temperature 1 Control On 1 On Sensor parameters Temp C 5 6 7 8 9 10 11 12 13 14 15 Temp C 16 17 18 19 20 21 22 23 24 25 26 Temp C 27 28 29 30 31 32 33 34 35 36 37 Temp C 38 39 40 41 42 43 44 45 Setpoint range Note In the case of a ...

Страница 20: ...S text Values available Comment Default value Temperature Control 0 Control On Off Set according to the type of control required for the heat ing air conditioning system 1 Integral Band 2 Proportional Integral Band 0 Proportional Cooling Value 1 0 C To be set according to the characteristics of the system and the room consult a heating engineer 1 1 C 1 2 C 1 3 C 1 4 C 1 5 C 1 6 C 1 7 C 1 8 C 2 0 C...

Страница 21: ...f thermal insulation and vice versa Integrative time used to calculate the coefficient Ki Kp Ti and corresponds to the time passed which when equal to the deviation from the setpoint error the integrative component generates a contribution equal to that generated by the proportional component The integral contribution reduces the error on full operation if thermal energy is lost in the room to be ...

Страница 22: ...min 20 min Proportional Heating Value 0 Off 1 0 C 1 1 C 1 2 C 1 3 C 1 4 C 1 5 C 1 6 C 1 7 C 1 8 C 2 0 C 2 2 C 2 5 C 3 0 C 3 5 C 4 0 C 4 5 C 5 0 C 3 0 C Integral Heating Value 0 Off 5 min 6 min 7 min 8 min 9 min 10 min 12 min 15 min 17 min 20 min 25 min 30 min 40 min 50 min 60 min 90 min 120 min 20 min Differential Coefficient 0 1 1 0 C For On Off type control set the thermostat A B hysteresis that...

Страница 23: ...nd Time in Cooling 0 Off 30 min Sets the valve status send time to the associated actu ators parameter required for certain types of valves for example Theben proportion al valves etc 0 Cyclic Send Time in Heating 0 Off 30 min 0 2 Pipe Circuit On Off A B Valve parameters Proportional 2 Pipe Circuit A B Proportional 4 Pipe Circuit A B M M Installation of 2 pipe fan coil solenoid valve Installation ...

Страница 24: ...Off Control Control with object that sends on off for valve status Enable 2 point Control 0 100 Control with object that sends 0 for valve off status and 100 for valve on status Cooling Threshold 0 5 C 1 0 C 1 5 C 2 0 C 2 5 C 3 0 C 3 5 C 4 0 C 4 5 C 5 0 C Value of the trigger threshold in cooling mode 2nd Stage Heating Valve Disabled Second heating stage off Enable 2 point On Off Control Control w...

Страница 25: ...ilable Comment Default value Time in Fan Man Mode min 0 255 Duration of Manual Forcing for the fan speed if the guest has forced the speed after this time the thermostat returns to automatic mode If the parameter is set to 0 it is interpreted as Time infinite and the fan speed set manually stays on To restore automatic opera tion the guest must return the fan speed to AUTO by manually operating on...

Страница 26: ...2 and Threshold for the Speed of Fan 3 while speed 1 is active when the valve is turned on and the Switching time between speeds min has passed An example of operation is shown in the following figure where SV2 and SV3 are respectively Threshold for the Speed of Fan 2 and Threshold for the Speed of Fan 3 ΔTR is instead the Differential Coefficient of the on off setting Note In the example shown in...

Страница 27: ... the setpoint and the temperature measured in the room The greater the difference the higher the set proportional value of the speed When this difference exceeds the value of the Threshold for Speed at 100 the proportional output of the fan is set to the highest possible speed that is 100 when the difference is minimal the proportional speed is set to Minimum Fan Speed The operation of the proport...

Страница 28: ...rio 16 0 disabled To define the operating mode when the scenario is called up 1 Comfort 2 Standby 3 Energy saving 4 Protected 0 Scenario A B 16 scenarios are available 16 different scenarios can therefore be saved on the device output With Enable Scenario Learning you can also set the status of the output for the desired scenario with a message from the bus scene learn Scenario parameters A B Scen...

Страница 29: ...ature Channel 0 Disabled Limitation disabled 1 Internal Sensor The internal sensor is used for temperature limitation 2 External Sensor The external sensor is used for tempera ture limitation 3 External Temper ature 1 The External Tem perature 1 is used for temperature limitation 4 External Temper ature 2 The External Tem perature 2 is used for temperature limitation 5 External Temper ature 3 The ...

Страница 30: ...ep step Timed one position stable 1 Timed 0 On Delay 0 60min Mode Normal 10 sec Off Delay 0 60min 10 sec Duration 0 60min Mode Timed 10 sec Relay 0 Normally open Status of thermostat output at rest 1 Normally closed 1 N B The relay can be paired with the speed of the fan coil only in the case of 3 speed fan coils or proportional 3 speed fan coils but NOT in the case of proportional fan coils Relay...

Страница 31: ...e other hand also inhibits Too Hot and Antifreeze and should never be used in normal installations The Off Mode object turns off the thermostat even if the temperature falls below zero i e it does not activate Heating Air conditioning It is advisable to use the Protected object which switches the thermostat to Off or protected Antifreeze depending on how the relevant parameters are set summer or w...

Страница 32: ... one when it is closed If an N C contact is used it will be necessary to set Off for the falling edge opening of window and contact and On for the rising edge closing of the window and contact If the contact is an N O type the two parameters must be set respectively to On and Off when the window is opened the contact is closed and vice versa If you set the input as Window Sensor opening the window...

Страница 33: ...Suite software what communication objects need to be set YOU have to set to Read the relevant flags of objects from 25 to 32 and from 72 to 79 for each 02952 thermostat 17 What is the parameter Time in Manual Fan Mode used for It is a time indicated in the parameters for which the ther mostat remains in Manual forcing if the guest has manually forced the temperatures or speed of the fan coil when ...

Страница 34: ... of the temperatures that can be associated are used to read respectively the current temperatures of thermostats A B and not objects 0 and 9 of the device which are the precise measurement data for the individual internal external probes 25 Is it possible to eliminate the adjustment range in Comfort mode which can be expanded at the most to 5 C It is possible by setting the parameter Guest Contro...

Страница 35: ...heating head and then another group with object no 18 summer winter status of the associated thermostat together with the object Logic 1 of relay 01523 In functional terms in winter the logic 1 of 01523 group is activated so when the other group i e that of object no 38 46 of the thermo stat relay On Off control also goes to 1 the relay 01523 will switch towards the head In summer the first of the...

Страница 36: ...e set setpoint and the room temperature so it will activate the heating cooling or remain in the neutral zone depending on the heating and air conditioning setpoints of the current mode 42 You cannot change the thermostat mode from the Well Contact Suite software neither from supervision nor from the Master thermostat What can be done To send mode messages to the thermostats the Well contact Suite...

Страница 37: ...ing OFF of the fans to work around this problem in the ETS project you can remove the U flag of the object of CMF STBY and reprogram the thermostat so that the response sent from the pocket to the Well contact Suite software is ignored 51 Is it possible for the icon not to appear on the bottom left that allows viewing and controlling thermostat B Yes For the icon not to be displayed it is sufficie...

Страница 38: ...Viale Vicenza 14 36063 Marostica VI Italy www vimar com 02952IEN 01 2010 ...

Отзывы: