background image

TECHNICAL DATA

September 17, 2009

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501  Technical Services: 877-384-5464  Fax: 269-818-1680  Email: [email protected]

MODEL VKFD25U

PRE-ASSEMBLED FLEXIBLE 

SPRINKLER DROP

ASSEMBLIES 

(UNBRAIDED)  

Sprinkler 138j

Figure 2:  Flexible Sprinkler Drop - Drawing

Figure 1:  Flexible Sprinkler Drop Installed

Figure 3:  Flexible Sprinkler Drop Support System

4.  INSTALLATION

Viking Flexible Sprinkler Drop Assemblies are manufactured and tested to meet the latest rigid requirements of the approving 
agencies. They are designed and tested to be installed in accordance with the Approved and Listed installation instructions as 
provided with the product and the recognized installation standards. Deviations from these standards or any alterations to the sup-
port system or sprinkler after leaving the factory including, but not limited to painting, plating, coating or modification may render 
the sprinkler inoperative or the support system non-compliant, automatically nullifying the approvals and any guarantee made by 
The Viking Corporation. The use of certain types of sprinklers may be limited due to occupancy and hazard. Refer to the Authority 
Having Jurisdiction prior to installation.

For complete installation instructions for this product, please refer to the Viking Flex Drop Installation and Design Manual, Form 
No. F_112107.

NOTE: Keep sprinklers with protective shields or caps contained within the shields or caps during installation and testing, and any 
time the sprinkler is shipped or handled.

The sprinklers are factory installed onto the outlet reducer fittings along with the outlet reducer support bracket and are pressure 
tested.     

Содержание VKFD25U

Страница 1: ...klers the mounting bracket system and special outlet fit tings provide a generous amount of adjustment both laterally and vertically for flush and precise sprinkler installation Note The brackets must be attached to the ceiling s main tee bar supports not to the cross support rail members The unique assembly of the Viking Flexible Sprinkler Drop to the piping system and the outlet sprinkler fittin...

Страница 2: ...port bracket bracket square nut and wing bolt assembled over straight outlet fitting sprinklers see Table 1 installed and leak tested into the outlet fitting as speci fied 10 per kit Instructions 1 For frame style sprinkler VK302 add the sprinkler Finish and Temperature Rating Suffix to the Sprinkler Base Part No A For Chrome sprinkler rated 135 F 57 C Add the suffix FA For White sprinkler rated 1...

Страница 3: ...rder Separately Optional 4 Bend Radius Gauge Tool Part No 15450 plastic Optional 4 Fixed Radius Clip Part No 14403 plastic The Following Kits are Available for Replacement Components Note These kits may be ordered in addition to the above for replacing components as required A 49 3 16 1 250 mm long support bar is available when the main support beams are spaced at 4 ft 1 219 mm These must be order...

Страница 4: ...tandards Deviations from these standards or any alterations to the sup port system or sprinkler after leaving the factory including but not limited to painting plating coating or modification may render the sprinkler inoperative or the support system non compliant automatically nullifying the approvals and any guarantee made by The Viking Corporation The use of certain types of sprinklers may be l...

Страница 5: ...inspection requirements that must be followed A Sprinklers must be inspected on a regular basis for corrosion mechanical damage obstructions paint etc The frequency of inspections may vary due to corrosive atmospheres water supplies and activity around the device B Sprinklers that have been field painted or mechanically damaged must be replaced immediately Sprinklers showing signs of corrosion sha...

Страница 6: ...nspect for proper bend radii and maximum quantity of bends as indicated in the table Refer to the Viking Flex Drop Installation and Design Manual Form No F_112107 for proper application and installation of Flexible Sprinkler Drops NOTE Refer to the specific sprinkler data page for the sprinkler model used with the Flexible Sprinkler Drop CAUTIONS Minimum Inside Bend Radius 4 102 mm Static cULus un...

Отзывы: