ESFR PENDENT SPRINKLER 

VK500 (K14.0)

TECHNICAL DATA

Page 4 of 6

Form No. F_060198    18.06.21    Rev 18.1

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501  Technical Services: 877-384-5464  Fax: 269-818-1680  Email: [email protected]

Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com

Approval Chart 2 (FM)

Quick Response Pendent Sprinkler VK500

 

Maximum 175 PSI (12 bar) WWP

Base Part 

Number

1

SIN

NPT Thread Size

Nominal K-Factor

Overall Length

FM Approvals

3,4

 

(Refer also to Design Criteria below.)

Inches

mm

U.S.

metric

2

Inches

mm

10284

VK500

3/4”

20 mm

14.0

--

2-7/8

73

A1, B1

11350

VK500

3/4”

20 mm

--

202

2-7/8

73

A1, B1

Approved Temperature Ratings

A - 165 °F (74 °C)           B - 205 °F (96 °C)

Approved Finish

1 - Brass

Footnotes

1

 Base part number shown. For complete part number, refer to the price list.

2

 Metric K-Factor measurement shown is when pressure is measured in bar. When pressure is measured in kPa, divide the metric K-Factor shown by 10.0.

3

 This chart shows the FM Approvals available at the time of printing. Other approvals may be in process. 

4

 FM Approved as a quick response pendent 

Non-Storage

 sprinkler and also FM Approved as a quick response pendent 

Storage

 sprinkler. Refer to 

Design Criteria below.

DESIGN CRITERIA - FM 

(Also refer to Approval Chart 2 above.)

FM Approval Requirements:

1.  Sprinkler VK500 is FM Approved as a quick response pendent 

Storage

 sprinkler as indicated in the FM Approval Guide. 

• 

For specific application and installation requirements, reference the latest applicable FM Loss Prevention Data Sheets (including Data Sheets 

2-0 and 8-9). 

2.  Sprinkler VK500 is also FM Approved as a quick response pendent 

Non-Storage

 sprinkler as indicated in the FM Approval Guide. 

• 

For specific application and installation requirements, reference the latest applicable FM Loss Prevention Data Sheets (including Data Sheet 2-0). 

FM Global Loss Prevention Data Sheets contain guidelines relating to, but not limited to: minimum water supply requirements, hydraulic design, ceiling 

slope and obstructions, minimum and maximum allowable spacing, and deflector distance below the ceiling.

NOTE: The FM installation guidelines may differ from cULus and/or NFPA criteria.

IMPORTANT:  Always  refer  to  Bulletin  Form  No.  F_091699  -  Care  and  Handling  of  Sprinklers.  Viking  ESFR 

Pendent Sprinklers are to be installed in accordance with the latest edition of Viking technical data, the latest 

applicable FM Global Loss Prevention Data Sheets (including 2-0 and 8-9), the latest standards of VdS, NFPA, and 

any other Authorities Having Jurisdiction, and also with provisions of governmental codes, ordinances, and stan

-

dards whenever applicable.

Содержание VK500

Страница 1: ...eria on pages 3 4 for cULus Listing and FM Approval requirements that must be followed In addition some storage arrangements of rolled paper aerosols and rubber tires may be protected by Viking ESFR Pendent Sprinkler VK500 2 LISTINGS AND APPROVALS cULus Listed Category VNWH FM Approved Class 2008 NYC Approved MEA 89 92 E Volume 18 VdS Approved Certificate G4010001 CE Certified Standard CUAP11 03 0...

Страница 2: ... Suffix 165 F 74 C C 205 F 96 C E For example sprinkler 10284 with a Brass finish and a 165 F 74 C temperature rating Part No 10284AC Available Finishes And Temperature Ratings Refer to Table 1 Accessories Also refer to the Viking website Sprinkler Wrench Part No 13635WB double ended wrench Use Side A Side B is for use with K25 2 ESFR Pendent Sprinkler VK510 Available since 2006 Sprinkler Cabinet ...

Страница 3: ... Sprinkler 10284 is cULus Listed as indicated in Approval Chart 1 for installation in accordance with the latest appropriate NFPA stan dards including NFPA 13 for ESFR Pendent K14 0 202 bar Sprinklers Maximum Roof or Ceiling Slope 2 in 12 167 mm m or 9 5 degrees Sprinkler Position Approved for use only in the pendent position Align the deflector parallel with the ceiling or roof System Type Wet sy...

Страница 4: ...er Refer to Design Criteria below DESIGN CRITERIA FM Also refer to Approval Chart 2 above FM Approval Requirements 1 Sprinkler VK500 is FM Approved as a quick response pendent Storage sprinkler as indicated in the FM Approval Guide For specific application and installation requirements reference the latest applicable FM Loss Prevention Data Sheets including Data Sheets 2 0 and 8 9 2 Sprinkler VK50...

Страница 5: ...sealing compound or tape is washed out of the joint Immediately replace any damaged units using the special sprinkler wrench only F After installation and testing and repairing of all leaks remove the protective caps from the sprinklers DO NOT use any type of tool to remove the cap Remove the cap by hand turn it slightly and pull it off the sprinkler When removing caps use care to prevent dislodgi...

Страница 6: ...e instructions Prior to removing the system from service notify all Authorities Having Jurisdiction Consideration should be given to employment of a fire patrol in the affected area 1 Remove the system from service drain all water and relieve all pressure on the piping 2 Using the special sprinkler wrench remove the old sprinkler and install the new unit Care must be taken to ensure that the repla...

Отзывы: