6.  INSPECTIONS, TESTS AND MAINTENANCE

A. The sprinklers must be inspected on a regular basis for corrosion, mechanical damage, obstructions, paint, etc. The frequency 

of inspections may vary due to corrosive atmosphere, water supplies, and activity around the device.

B. Sprinklers that have been painted or mechanically damaged must be replaced immediately. Sprinklers showing signs of cor-

rosion shall be tested and/or replaced immediately as required. Installation standards require sprinklers to be tested and, if 

necessary, replaced after a specified term of service. For Viking ESFR Pendent Sprinklers, refer to the Installation Standards (e.g., 

NFPA 25) and the Authorities Having Jurisdiction for the specified period of time after which testing and/or replacement is required. 

Sprinklers that have operated cannot be reassembled or reused, but must be replaced. When replacing sprinklers, use only new 

sprinklers.

C. The sprinkler discharge pattern is critical for proper fire protection. Therefore, nothing should be hung from, attached to, or 

otherwise obstruct the discharge pattern. All obstructions must be immediately removed or, if necessary, additional sprinklers 

installed.

D. When replacing existing sprinklers, the system must be removed from service. Refer to the appropriate system description and/

or valve instructions. Prior to removing the system from service, notify all Authorities Having Jurisdiction. Consideration should 

be given to employment of a fire patrol in the affected area.

1. Remove the system from service, drain all water, and relieve all pressure on the piping.

2. Using the special sprinkler wrench, remove the old sprinkler and install the new unit. Care must be taken to ensure that the 

replacement sprinkler is the proper model and style, with the correct orifice size, temperature rating, and response charac-

teristics. A fully stocked spare sprinkler cabinet should be provided for this purpose.

3. Place the system back in service and secure all valves. Check the replaced sprinklers and repair all leaks.

E. Sprinkler systems that have been subject to a fire must be returned to service as soon as possible. The entire system must 

be inspected for damage and repaired or replaced as necessary. Sprinklers that have been exposed to corrosive products of 

combustion, but have not operated, should be replaced. Refer to the Authorities Having Jurisdiction for minimum replacement 

requirements.

7.  AVAILABILITY

The Viking Model VK500 Sprinkler is available through a network of domestic and international distributors. See The Viking 

Corporation web site for the closest distributor or contact The Viking Corporation.

8.  GUARANTEE

For details of warranty, refer to Viking’s current list price schedule or contact Viking directly.

NOTICE

The  owner  is  responsible  for  maintaining  the  fire  protection  system  and  devices  in  proper  operating  condition.  For 

minimum maintenance and inspection requirements, refer to the NFPA standard that describes care and maintenance 

of sprinkler systems. In addition, the Authorities Having Jurisdiction may have additional maintenance, testing, and 

inspection requirements that must be followed.

Replaces Form No. F_060198 Rev 17.1

(Revised  mages.)      

Содержание VK500

Страница 1: ...eria on pages 3 4 for cULus Listing and FM Approval requirements that must be followed In addition some storage arrangements of rolled paper aerosols and rubber tires may be protected by Viking ESFR Pendent Sprinkler VK500 2 LISTINGS AND APPROVALS cULus Listed Category VNWH FM Approved Class 2008 NYC Approved MEA 89 92 E Volume 18 VdS Approved Certificate G4010001 CE Certified Standard CUAP11 03 0...

Страница 2: ... Suffix 165 F 74 C C 205 F 96 C E For example sprinkler 10284 with a Brass finish and a 165 F 74 C temperature rating Part No 10284AC Available Finishes And Temperature Ratings Refer to Table 1 Accessories Also refer to the Viking website Sprinkler Wrench Part No 13635WB double ended wrench Use Side A Side B is for use with K25 2 ESFR Pendent Sprinkler VK510 Available since 2006 Sprinkler Cabinet ...

Страница 3: ... Sprinkler 10284 is cULus Listed as indicated in Approval Chart 1 for installation in accordance with the latest appropriate NFPA stan dards including NFPA 13 for ESFR Pendent K14 0 202 bar Sprinklers Maximum Roof or Ceiling Slope 2 in 12 167 mm m or 9 5 degrees Sprinkler Position Approved for use only in the pendent position Align the deflector parallel with the ceiling or roof System Type Wet sy...

Страница 4: ...er Refer to Design Criteria below DESIGN CRITERIA FM Also refer to Approval Chart 2 above FM Approval Requirements 1 Sprinkler VK500 is FM Approved as a quick response pendent Storage sprinkler as indicated in the FM Approval Guide For specific application and installation requirements reference the latest applicable FM Loss Prevention Data Sheets including Data Sheets 2 0 and 8 9 2 Sprinkler VK50...

Страница 5: ...sealing compound or tape is washed out of the joint Immediately replace any damaged units using the special sprinkler wrench only F After installation and testing and repairing of all leaks remove the protective caps from the sprinklers DO NOT use any type of tool to remove the cap Remove the cap by hand turn it slightly and pull it off the sprinkler When removing caps use care to prevent dislodgi...

Страница 6: ...e instructions Prior to removing the system from service notify all Authorities Having Jurisdiction Consideration should be given to employment of a fire patrol in the affected area 1 Remove the system from service drain all water and relieve all pressure on the piping 2 Using the special sprinkler wrench remove the old sprinkler and install the new unit Care must be taken to ensure that the repla...

Отзывы: