ESFR PENDENT SPRINKLER 

VK500 (K14.0)

TECHNICAL DATA

Page 2 of 6

Form No. F_060198    18.06.21    Rev 18.1

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501  Technical Services: 877-384-5464  Fax: 269-818-1680  Email: [email protected]

Visit the Viking website for the latest edition of this technical data page: www.vikinggroupinc.com

Seat for Sprinkler 11350: Stainless Steel UNS-S31603

  Seat and Insert Assembly for Sprinkler 10284: Copper UNS-C11000 and Stainless Steel UNS-S30400

Belleville Spring Sealing Assembly: Nickel Alloy, coated on both sides with PTFE Tape

Compression Screw: Stainless Steel UNS-S31603

Trigger and Support: Stainless Steel UNS-S31600

Fusible Element Assembly: Beryllium Nickel, coated with black acrylic paint.

Ejector Spring (Sprinkler Base Part No. 11350 only): 17-7 Stainless Steel 

Ordering Information:

 (Also refer to the current Viking price list.)

Order ESFR Pendent Sprinkler VK500 by first adding the appropriate suffix for the sprinkler finish and then the appropriate suffix 

for the temperature rating to the sprinkler base part number.

Finish Suffix: Brass = A

Temperature Suffix: 165 °F (74 °C) = C, 205 °F (96 °C) = E

For example, sprinkler 10284 with a Brass finish and a 165 °F (74 °C) temperature rating = Part No. 10284AC. 

Available Finishes And Temperature Ratings:

 Refer to Table 1.

Accessories:

 (Also refer to the Viking website.)

Sprinkler Wrench:

Part No. 13635WB (double-ended wrench - Use Side A. Side B is for use with K25.2 ESFR Pendent Sprinkler VK510) Available 

since 2006.

Sprinkler Cabinet:

Twelve-head capacity: Part No. 01725A (available since 1971)

TABLE 1: AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES

Sprinkler Temperature 

Classification

Sprinkler Nominal

 

Temperature Rating

1

Maximum Ambient

 

Ceiling Temperature

2

Frame Paint 

Color

Ordinary

165 °F (74 °C)

100 °F (38 °C)

None

Intermediate

3

205 °F (96 °C)

150 °F (65 °C)

White

Sprinkler Finish:

 Brass

Footnotes

1

 The sprinkler temperature rating is stamped on the deflector. 

2

 Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having Jurisdiction. 

Refer to specific installation standards.

3

 The intermediate temperature rating is available for Sprinkler Base Part No. 10284 only.

Figure 2:  ESFR Pendent Sprinkler VK500 Dimensions

Sprinkler 10284 Shown

Figure 1:  ESFR Pendent Sprinkler Wrench 13635WB

Use Side A for VK500

Wrench flat

Protective 

Sprinkler 

Cap

2-7/8”

(74 mm)

1-3/4”

(45 mm)

1-7/16”

(37 mm)

1-7/16”

(37 mm)

Содержание VK500

Страница 1: ...eria on pages 3 4 for cULus Listing and FM Approval requirements that must be followed In addition some storage arrangements of rolled paper aerosols and rubber tires may be protected by Viking ESFR Pendent Sprinkler VK500 2 LISTINGS AND APPROVALS cULus Listed Category VNWH FM Approved Class 2008 NYC Approved MEA 89 92 E Volume 18 VdS Approved Certificate G4010001 CE Certified Standard CUAP11 03 0...

Страница 2: ... Suffix 165 F 74 C C 205 F 96 C E For example sprinkler 10284 with a Brass finish and a 165 F 74 C temperature rating Part No 10284AC Available Finishes And Temperature Ratings Refer to Table 1 Accessories Also refer to the Viking website Sprinkler Wrench Part No 13635WB double ended wrench Use Side A Side B is for use with K25 2 ESFR Pendent Sprinkler VK510 Available since 2006 Sprinkler Cabinet ...

Страница 3: ... Sprinkler 10284 is cULus Listed as indicated in Approval Chart 1 for installation in accordance with the latest appropriate NFPA stan dards including NFPA 13 for ESFR Pendent K14 0 202 bar Sprinklers Maximum Roof or Ceiling Slope 2 in 12 167 mm m or 9 5 degrees Sprinkler Position Approved for use only in the pendent position Align the deflector parallel with the ceiling or roof System Type Wet sy...

Страница 4: ...er Refer to Design Criteria below DESIGN CRITERIA FM Also refer to Approval Chart 2 above FM Approval Requirements 1 Sprinkler VK500 is FM Approved as a quick response pendent Storage sprinkler as indicated in the FM Approval Guide For specific application and installation requirements reference the latest applicable FM Loss Prevention Data Sheets including Data Sheets 2 0 and 8 9 2 Sprinkler VK50...

Страница 5: ...sealing compound or tape is washed out of the joint Immediately replace any damaged units using the special sprinkler wrench only F After installation and testing and repairing of all leaks remove the protective caps from the sprinklers DO NOT use any type of tool to remove the cap Remove the cap by hand turn it slightly and pull it off the sprinkler When removing caps use care to prevent dislodgi...

Страница 6: ...e instructions Prior to removing the system from service notify all Authorities Having Jurisdiction Consideration should be given to employment of a fire patrol in the affected area 1 Remove the system from service drain all water and relieve all pressure on the piping 2 Using the special sprinkler wrench remove the old sprinkler and install the new unit Care must be taken to ensure that the repla...