QR RECESSED FLUSH
DRY SPRINKLER
VK482 (K5.6)
TECHNICAL DATA
The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058
Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: [email protected]
Page 3 of 7
Form No. F_081512 19.06.24 Rev.19.1
Approval Chart
Quick Response Recessed Flush Dry Sprinkler VK482
Maximum 175 PSI
(
12 bar) WWP
Base Part
Number
1
SIN
Thread Size
Nominal
K-Factor
Maximum
Water
Working
Pressure
Order Length Increment
Listings and Approvals
3
(Refer also to Design Criteria on
page 111d.)
NPT
BSP
U.S
Metric
2
Inches
mm
UL
4
FM
Quick Response Applications
18385
VK482
1”
25mm
5.6
80.6
175 psi
(12bar)
1/4”
6.35
A1
--
Approved Temperature Ratings
A - 165 °F (74 °C) and 205 °F (96 °C)
Approved Finishes and “A” Dimensions
5
1 - White Polyester with “A” dimensions 4-1/2” to 48” (114 mm to 1,219 mm)
Footnotes
1
Base part number is shown. For complete part number, refer to Viking’s current price schedule.
2
Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.
3
This table shows the listings and approvals available at the time of printing. Check with the manufacturer for any additional approvals.
4
Listed by Underwriters Laboratories Inc. for use in the U.S.
5
Painted finish consists of Polyester Baked Enamel. Other paint colors are available on request with the same listings as the standard paint colors.
Listings and approvals apply for any paint manufacturer. Contact Viking for additional information. Custom colors are indicated on a label on the
sprinkler body.
5. OPERATION
During fire conditions, when the fusible element reaches its operating temperature, the element cover, fusible element and lever
assembly fall away. The deflector is suspended below the ceiling. Water flowing through the sprinkler orifice strikes the deflector,
forming a uniform spray pattern over a specific area of coverage determined by the water supply pressure at the sprinkler to ex-
tinguish or control the fire.
6. INSPECTIONS, TESTS AND MAINTENANCE
Refer to NFPA 25 for Inspection, Testing and Maintenance requirements.
7. AVAILABILITY
Viking Sprinkler VK482 is available through a network of domestic and international distributors. See The Viking Corporation web
site for the closest distributor or contact The Viking Corporation.
8. GUARANTEE
For details of warranty, refer to Viking’s current list price schedule or contact Viking directly.