background image

SPRINKLER GENERAL CARE, 

INSTALLATION, AND 

MAINTENANCE GUIDE

TECHNICAL DATA

Page 3 of 4

Form No. F_080614       18.10.11     Rev 16.1.P65

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: [email protected]

Visit the Viking website for the latest edition of this technical data page.

B. Refer to the appropriate sprinkler technical data page to determine the correct sprinkler wrench for the model of sprinkler used. 

C. Install the dry sprinkler on the piping using the special dry sprinkler wrench only, while taking care not to damage the sprinkler. 

NOTE:

 Thread the sprinkler into the fitting hand tight, plus 1/2 turn with the dry sprinkler wrench.  

D. 

For adjustable standard and adjustable recessed dry pendent and sidewall sprinklers: Escutcheons can be installed after the 

sprinklers have been installed onto the piping. Refer to the appropriate sprinkler technical data page for escutcheon installation 

instructions and illustrations.

D. Installation Instructions - Testing

4. After installation, the entire sprinkler system must be tested. The test must be conducted to comply with the installation stand-

ards. Viking 

high pressure

 sprinklers may be hydrostatically tested at a maximum of 300 psi (20.7 bar) for limited periods of time 

(two hours), for the purpose of acceptance by the Authority Having Jurisdiction.

a. Make sure the sprinkler is properly tightened. If a thread leak occurs, normally the sprinkler must be removed, new pipe-joint 

compound or tape applied, and then reinstalled. This is due to the fact that when the joint seal is damaged, the sealing 

compound or tape is washed out of the joint. Air testing [do not exceed 40 psi (2.76 bar)] the sprinkler piping prior to testing 

with water may be considered in areas where leakage during testing must be prevented. Refer to the Installation Standards 

and the Authority Having Jurisdiction. 

b. 

Remove plastic protective sprinkler caps or bulb shields AFTER the wall or ceiling finish work is completed where 

the sprinkler is installed and there no longer is a potential for mechanical damage to the sprinkler operating ele

-

ments. 

To remove the bulb shields, simply pull the ends of the shields apart where they are snapped together. To remove 

caps from frame style sprinklers, turn the caps slightly and pull them off the sprinklers. 

SPRINKLER  CAPS  OR  BULB 

SHIELDS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE! 

Retain a protective 

cap or shield in the spare sprinkler cabinet.

5. For flush style sprinklers: the ceiling ring can now be installed onto the sprinkler body. Align the ceiling ring with the sprinkler 

body and thread or push it on (depends on sprinkler model) until the outer flange touches the surface of the ceiling. Note the 

maximum adjustment is 1/4” (6.35 mm). DO NOT MODIFY THE UNIT. If necessary, re-cut the sprinkler drop nipple as required.

6. For concealed sprinklers: the cover assembly can now be attached.

a. Remove the cover from the protective box, taking care not to damage the cover plate assembly.

b. Gently place the base of the cover plate assembly over the sprinkler protruding through the opening in the ceiling.

c. Push the cover plate assembly onto the sprinkler until the unfinished brass flange of the cover plate base (or the cover 

adapter, if used) touches the surface of the ceiling.

d. Refer to the applicable technical data sheet to determin the maximum adjustment available for concealed sprinklers. DO NOT 

MODIFY THE UNIT. If necessary, re-cut the sprinkler drop nipple.

NOTE: 

If it is necessary to remove the entire sprinkler unit, the system must be taken out of service. See section 6. INSPECTIONS, 

TESTS AND MAINTENANCE and follow all warnings and instructions. 

5.  OPERATION

Refer to the appropriate sprinkler technical data page(s). During fire conditions, the operating element fuses or shatters (depending 

on the type of sprinkler), releasing the pip cap and sealing assembly. Water flowing through the sprinkler orifice strikes the sprinkler 

deflector, forming a uniform spray pattern to extinguish or control the fire.

IMPORTANT:  Always  refer  to  Bulletin  Form  No.  F_091699  -  Care  and  Handling  of  Sprinklers.  Viking 

sprinklers  are  to  be  installed  in  accordance  with  the  latest  edition  of  Viking  technical  data,  the  appro

-

priate  standards  of  NFPA,  FM  Global,  LPCB,  APSAD,  VdS  or  other  similar  organizations,  and  also  with 

the  provisions  of  governmental  codes,  ordinances,  and  standards,  whenever  applicable.  The  sprinkler 

technical  data  page  may  contain  installation  requirements  specific  for  the  sprinkler  model  selected.

 

The use of certain types of sprinklers may be limited due to occupancy and hazard. Refer to the Authority Having 

Jurisdiction prior to installation.

Содержание VK482

Страница 1: ...llowing U S Patents 8 636 075 and 10 220 231 Material Standards Sprinkler Body QM Brass Deflector Assembly Bronze UNS C22000 and Brass UNS C36000 Pin Assembly Stainless Steel UNS S30200 and Brass UNS C23000 Seat Assembly Brass UNS C31400 or UNS C31600 Belleville Spring Sealing Assembly Nickel Alloy coated on both sides with PTFE Tape Fusible Element Assembly Beryllium Nickel and Eutectic Solder El...

Страница 2: ...thority Having Jurisdiction Refer to specific installation standards 3 Part number shown is the base part number for the replacement escutcheon For complete part number refer to current Viking price list schedule Figure 1 Sprinkler Installation and Correct Use of Wrench Available Finishes And Temperature Ratings Refer to Table 1 Accessories Also refer to the Viking website Sprinkler Wrench A Dry F...

Страница 3: ...vals available at the time of printing Check with the manufacturer for any additional approvals 4 Listed by Underwriters Laboratories Inc for use in the U S 5 Painted finish consists of Polyester Baked Enamel Other paint colors are available on request with the same listings as the standard paint colors Listings and approvals apply for any paint manufacturer Contact Viking for additional informati...

Страница 4: ...baffles are installed in accordance with NFPA 13 Locate no less than 4 102 mm from walls Maximum distance from walls shall be no more than one half of the allowable distance between sprinklers The distance shall be measured per pendicular to the wall The sprinkler installation and obstruction rules contained in NFPA 13 for standard spray pendent sprinklers must be followed IMPORTANT Always refer t...

Страница 5: ...9058 Telephone 269 945 9501 Technical Services 877 384 5464 Fax 269 818 1680 Email techsvcs vikingcorp com Page 5 of 7 Form No F_081512 19 06 24 Rev 19 1 Figure 4 Recessed Flush Dry Sprinkler Seal Figure 3 Recessed Flush Dry Pendent Sprinkler Required Minimum Barrel Length Based on Ambient Temperature in the Protected Area ...

Страница 6: ...nical Services 877 384 5464 Fax 269 818 1680 Email techsvcs vikingcorp com Page 6 of 7 Form No F_081512 19 06 24 Rev 19 1 Figure 5 Recessed Flush Dry Sprinkler Escutcheon Instructions Push adapter up until stopped Rotate adapter clock wise until stopped Let adapter drop until stopped Rotate outer cup until it comes into contact with the ceiling 1 2 3 4 5 ...

Страница 7: ...n Recess Instructions Figure 7 Recessed Flush Dry Sprinkler Escutcheon Recess Instructions Measure from Escutcheon Adapter Sprinkler Base to the bottom face of Escutcheon Cup for recess measurement Also see figure 2 NOTE Do not measure from Element Assembly NOTE After installed the inner escutcheon adapter must not extend beyond the outer escutcheon cup This will result in exceeding the maximum re...

Страница 8: ...stall sprinklers onto piping at the floor level Install sprinklers after the piping is in place to prevent mechanical damage DO NOT allow impacts such as hammer blows directly to sprinklers or to fittings pipe or couplings in close proximity to sprinklers Sprinklers can be damaged from direct or indirect impacts DO NOT attempt to remove drywall paint etc from sprinklers Take care not to over tight...

Страница 9: ...D CAPS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE Figure 1 Sprinkler shield being removed from a pendent sprinkler Figure 2 Sprinkler cap being removed from a pendent sprinkler Figure 3 Sprinkler cap being re moved from and upright sprinkler HOW TO REMOVE SHIELDS AND CAPS No tools are necessary to remove the shields or caps from sprinklers DO NOT use any sharp objects to ...

Страница 10: ... these sprinklers NOTE The protective cap is temporarily removed during installation and then placed back on the sprinkler for protection until finish work is completed Do not over tighten the sprinklers into fittings during installation Do not use the sprinkler deflector to start or thread the sprinklers into fittings during installation Do not attempt to remove drywall paint etc from the sprinkl...

Страница 11: ...t the corrosion resistant properties of the sprinkler Use care when locating sprinklers near fixtures that can generate heat Do not install sprinklers where they would be exposed to temperatures exceed ing the maximum recommended ambient temperature for the temperature rating used Inspect the coated sprinklers frequently soon after installation to verify the integrity of the corrosion resistant co...

Страница 12: ...t readings to be expected In addition recognized installation rules may require a higher temperature classifica tion depending upon sprinkler location occupancy classification commodity classification storage height and other hazards In all cases the maximum expected ceiling temperature dictates the lowest allowable temperature classification Sprinklers located immediately adjacent to a heat sourc...

Страница 13: ...ly intended for installation with a concealed piping system The assembly con sists of a sprinkler installed in a decorative adjustable recessed escutcheon that minimizes the protrusion of the sprinkler beyond the ceiling or wall without adversely affecting the sprinkler distribution or sensitivity Refer to the appropriate technical data page for allowable sprinkler models temperature ratings and o...

Страница 14: ...TENANCE Refer to NFPA 25 for Inspection Testing and Maintenance requirements 7 AVAILABILITY Viking sprinklers are available through a network of domestic and international distributors See The Viking Corporation web site for the closest distributor or contact The Viking Corporation 8 GUARANTEE For details of warranty refer to Viking s current list price schedule or contact Viking directly IMPORTAN...

Страница 15: ... the sprinkler technical data page Never install any glass bulb sprinkler if the bulb is cracked or if there is a loss of liquid from the bulb A small air bubble should be present in the glass bulb Any sprinkler with a loss of liquid from the glass bulb or damage to the fusible element should be destroyed immediately Note Installing glass bulb sprinklers in direct sunlight ultraviolet light may af...

Страница 16: ...uctile iron or Nibco CPVC threaded tee fittings for wet systems that meet the dimensional requirements of ANSI B16 3 Class 150 or cast iron threaded tee fittings that meet the dimensional requirements of ANSI B16 4 Class 125 even at branch line ends The threaded end of the dry sprinkler is designed to allow the seal to penetrate and extend into the fitting to a predetermined depth This prevents co...

Страница 17: ...ther To remove caps from frame style sprinklers turn the caps slightly and pull them off the sprinklers SPRINKLER CAPS OR BULB SHIELDS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE Retain a protective cap or shield in the spare sprinkler cabinet 5 For flush style sprinklers the ceiling ring can now be installed onto the sprinkler body Align the ceiling ring with the sprinkle...

Страница 18: ...Prior to removing the system from service notify all Authorities Having Jurisdiction Consideration should be given to employment of a fire patrol in the affected area 1 Remove the system from service drain all water and relieve all pressure on the piping 2a For frame style sprinklers use the special sprinkler wrench to remove the old sprinkler by turning it counterclockwise to unthread it from the...

Страница 19: ...ction of fire protection products are provided herin as they relate to legally mandated jurisdictional regions WARNING STATE OF CALIFORNIA USA Installing or servicing fire protection products such as sprinklers valves piping etc can expose you to chemicals including but not li mited to lead nickel butadiene titaninum dioxide chromium carbon black and acrylonitrile which are known to the State of C...

Отзывы: