SPRINKLER OVERVIEW

Page 2 of 3

Form No. F_080814       18.12.06       Rev 14.1.P65

VERTICAL SIDEWALL (VSW) SPRINKLER: A sprinkler intended for installation near the wall and ceiling. The deflector provides a 

water spray pattern outward in a quarter-spherical pattern and can be installed in the upright or pendent position with the flow 

arrow in the direction of discharge. Marked “SIDEWALL” on the deflector with an arrow and the word “FLOW”. (Note: Some 

vertical sidewall sprinklers can only be installed in the upright or pendent position—in this case, the sprinkler will also be marked 

“UPRIGHT” or “PENDENT”.)

HORIZONTAL SIDEWALL (HSW) SPRINKLER: A sprinkler intended for installation near the wall and ceiling. The special deflector 

provides a water spray pattern outward in a quarter-spherical pattern. Most of the water is directed away from the nearby wall 

with a small portion directed at the wall behind the sprinkler. The top of the deflector is oriented parallel with the ceiling or roof. 

The flow arrows point in the direction of discharge. Marked “SIDEWALL” and “TOP” with an arrow and the word “FLOW”.

EXTENDED COVERAGE (EC) SPRINKLER: A spray sprinkler designed to discharge water over an area having the maximum 

dimensions indicated in the individual listings. Maximum area of coverage, minimum flow rate, orifice size, and nominal K-Factor 

are specified in the individual listings. EC sprinklers are intended for Light-Hazard occupancies with smooth, flat, horizontal ceil-

ings unless otherwise specified. In addition to the above markings, the sprinkler is marked “EC”.

QUICK RESPONSE (QR) SPRINKLER: A spray sprinkler with a fast- actuating operating element. The use of quick response 

sprinklers may be limited due to occupancy and hazard. Refer to the Authority Having Jurisdiction (AHJ) prior to installing.

QUICK RESPONSE EXTENDED COVERAGE (QREC) SPRINKLER: A spray sprinkler designed to discharge water over an area 

having the maximum dimensions indicated in the individual listing. This is a sprinkler with an operating element that meets the 

criteria for quick response. QREC sprinklers are only intended for Light Hazard occupancies. The sprinkler is marked “QREC”.

FLUSH SPRINKLER: A decorative spray sprinkler intended for installation with a concealed piping system. The unit is mounted 

flush with the ceiling or wall, with the fusible link exposed. Upon actuation, the deflector extends beyond the ceiling or wall to 

distribute water discharge. The sprinkler is marked “SSP”, “PEND”, or “SIDEWALL” and “TOP”.

CONCEALED SPRINKLER: A decorative spray sprinkler intended for installation with a concealed piping system. The sprinkler is 

hidden from view by a cover plate installed flush with the ceiling or wall. During fire conditions, the cover plate detaches, and 

upon sprinkler actuation, the deflector extends beyond the ceiling or wall to distribute water discharge. The sprinkler is marked 

“SSP”, “PEND”, or “SIDEWALL” and “TOP”.  

RECESSED SPRINKLER: A spray sprinkler assembly intended for installation with a concealed piping system. The assembly con-

sists of a sprinkler installed in a decorative adjustable recessed escutcheon that minimizes the protrusion of the sprinkler beyond 

the ceiling or wall without adversely affecting the sprinkler distribution or sensitivity. Refer to the appropriate technical data page 

for allowable sprinkler models, temperature ratings, and occupancy classifications. DO NOT RECESS ANY SPRINKLER NOT 

LISTED FOR USE WITH THE ESCUTCHEON.

CORROSION-RESISTANT SPRINKLER: A special service sprinkler with non-corrosive protective coatings, or that is fabricated 

from non-corrosive material, for use in atmospheres that would normally corrode sprinklers.

DRY SPRINKLER: A special-service sprinkler intended for installation on dry pipe systems or wet pipe systems where the sprinkler 

is subject to freezing temperatures. The unit consists of a sprinkler permanently secured to an extension nipple with a sealed 

inlet end to prevent water from entering the nipple until the sprinkler operates. The unit MUST be installed in a tee fitting. Dry 

upright sprinklers are marked with the “B” dimension [distance from the face of the fitting (tee) to the top of the deflector]. Dry 

pendent and sidewall sprinklers are marked with the “A” dimension [the distance from the face of fitting (tee) to the finished 

surface of the ceiling or wall].

LARGE DROP SPRINKLER: A type of special application sprinkler used to provide fire control of specific high-challenge fire haz-

ards. Large drop sprinklers are designed to produce an umbrella-shaped spray pattern downward with a higher percentage of 

“large” water droplets than standard spray sprinklers. The sprinkler has an extra-large orifice with a nominal K-Factor of 11.2. 

Marked “HIGH CHALLENGE” and “UPRIGHT”.

EARLY SUPPRESSION FAST-RESPONSE (ESFR) SPRINKLER: A sprinkler intended to provide fire suppression of specific high-

challenge fire hazards through the use of a fast response fusible link, 14.0, 16.8, or 25.2 nominal K-Factor, and special deflector. 

ESFR sprinklers are designed to produce high-momentum water droplets in a hemispherical pattern below the deflector. This 

permits penetration of the fire plume and direct wetting of the burning fuel surface while cooling the atmosphere early in the 

development of a high-challenge fire. Marked “ESFR” and “UPRIGHT” or “PEND”.

INTERMEDIATE LEVEL/RACK STORAGE SPRINKLER: A standard spray sprinkler assembly designed to protect its operating 

element from the spray of sprinklers installed at higher elevations. The assembly consists of a standard or large orifice upright 

or pendent sprinkler with an integral upright or pendent water shield and guard assembly. Use only those sprinklers that have 

been tested and listed for use with the assembly. Refer to the technical data page for allowable sprinkler models.

RESIDENTIAL SPRINKLER: A sprinkler intended for use in the following occupancies: one- and two-family dwellings with the fire 

protection sprinkler system installed in accordance with NFPA 13D; residential occupancies up to four stories in height with the 

fire protection system installed in accordance with NFPA 13R; and where allowed by the Authority Having Jurisdiction in resi-

dential portions of any occupancy with the fire protection system installed in accordance with NFPA 13.

Содержание VK482

Страница 1: ...llowing U S Patents 8 636 075 and 10 220 231 Material Standards Sprinkler Body QM Brass Deflector Assembly Bronze UNS C22000 and Brass UNS C36000 Pin Assembly Stainless Steel UNS S30200 and Brass UNS C23000 Seat Assembly Brass UNS C31400 or UNS C31600 Belleville Spring Sealing Assembly Nickel Alloy coated on both sides with PTFE Tape Fusible Element Assembly Beryllium Nickel and Eutectic Solder El...

Страница 2: ...thority Having Jurisdiction Refer to specific installation standards 3 Part number shown is the base part number for the replacement escutcheon For complete part number refer to current Viking price list schedule Figure 1 Sprinkler Installation and Correct Use of Wrench Available Finishes And Temperature Ratings Refer to Table 1 Accessories Also refer to the Viking website Sprinkler Wrench A Dry F...

Страница 3: ...vals available at the time of printing Check with the manufacturer for any additional approvals 4 Listed by Underwriters Laboratories Inc for use in the U S 5 Painted finish consists of Polyester Baked Enamel Other paint colors are available on request with the same listings as the standard paint colors Listings and approvals apply for any paint manufacturer Contact Viking for additional informati...

Страница 4: ...baffles are installed in accordance with NFPA 13 Locate no less than 4 102 mm from walls Maximum distance from walls shall be no more than one half of the allowable distance between sprinklers The distance shall be measured per pendicular to the wall The sprinkler installation and obstruction rules contained in NFPA 13 for standard spray pendent sprinklers must be followed IMPORTANT Always refer t...

Страница 5: ...9058 Telephone 269 945 9501 Technical Services 877 384 5464 Fax 269 818 1680 Email techsvcs vikingcorp com Page 5 of 7 Form No F_081512 19 06 24 Rev 19 1 Figure 4 Recessed Flush Dry Sprinkler Seal Figure 3 Recessed Flush Dry Pendent Sprinkler Required Minimum Barrel Length Based on Ambient Temperature in the Protected Area ...

Страница 6: ...nical Services 877 384 5464 Fax 269 818 1680 Email techsvcs vikingcorp com Page 6 of 7 Form No F_081512 19 06 24 Rev 19 1 Figure 5 Recessed Flush Dry Sprinkler Escutcheon Instructions Push adapter up until stopped Rotate adapter clock wise until stopped Let adapter drop until stopped Rotate outer cup until it comes into contact with the ceiling 1 2 3 4 5 ...

Страница 7: ...n Recess Instructions Figure 7 Recessed Flush Dry Sprinkler Escutcheon Recess Instructions Measure from Escutcheon Adapter Sprinkler Base to the bottom face of Escutcheon Cup for recess measurement Also see figure 2 NOTE Do not measure from Element Assembly NOTE After installed the inner escutcheon adapter must not extend beyond the outer escutcheon cup This will result in exceeding the maximum re...

Страница 8: ...stall sprinklers onto piping at the floor level Install sprinklers after the piping is in place to prevent mechanical damage DO NOT allow impacts such as hammer blows directly to sprinklers or to fittings pipe or couplings in close proximity to sprinklers Sprinklers can be damaged from direct or indirect impacts DO NOT attempt to remove drywall paint etc from sprinklers Take care not to over tight...

Страница 9: ...D CAPS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE Figure 1 Sprinkler shield being removed from a pendent sprinkler Figure 2 Sprinkler cap being removed from a pendent sprinkler Figure 3 Sprinkler cap being re moved from and upright sprinkler HOW TO REMOVE SHIELDS AND CAPS No tools are necessary to remove the shields or caps from sprinklers DO NOT use any sharp objects to ...

Страница 10: ... these sprinklers NOTE The protective cap is temporarily removed during installation and then placed back on the sprinkler for protection until finish work is completed Do not over tighten the sprinklers into fittings during installation Do not use the sprinkler deflector to start or thread the sprinklers into fittings during installation Do not attempt to remove drywall paint etc from the sprinkl...

Страница 11: ...t the corrosion resistant properties of the sprinkler Use care when locating sprinklers near fixtures that can generate heat Do not install sprinklers where they would be exposed to temperatures exceed ing the maximum recommended ambient temperature for the temperature rating used Inspect the coated sprinklers frequently soon after installation to verify the integrity of the corrosion resistant co...

Страница 12: ...t readings to be expected In addition recognized installation rules may require a higher temperature classifica tion depending upon sprinkler location occupancy classification commodity classification storage height and other hazards In all cases the maximum expected ceiling temperature dictates the lowest allowable temperature classification Sprinklers located immediately adjacent to a heat sourc...

Страница 13: ...ly intended for installation with a concealed piping system The assembly con sists of a sprinkler installed in a decorative adjustable recessed escutcheon that minimizes the protrusion of the sprinkler beyond the ceiling or wall without adversely affecting the sprinkler distribution or sensitivity Refer to the appropriate technical data page for allowable sprinkler models temperature ratings and o...

Страница 14: ...TENANCE Refer to NFPA 25 for Inspection Testing and Maintenance requirements 7 AVAILABILITY Viking sprinklers are available through a network of domestic and international distributors See The Viking Corporation web site for the closest distributor or contact The Viking Corporation 8 GUARANTEE For details of warranty refer to Viking s current list price schedule or contact Viking directly IMPORTAN...

Страница 15: ... the sprinkler technical data page Never install any glass bulb sprinkler if the bulb is cracked or if there is a loss of liquid from the bulb A small air bubble should be present in the glass bulb Any sprinkler with a loss of liquid from the glass bulb or damage to the fusible element should be destroyed immediately Note Installing glass bulb sprinklers in direct sunlight ultraviolet light may af...

Страница 16: ...uctile iron or Nibco CPVC threaded tee fittings for wet systems that meet the dimensional requirements of ANSI B16 3 Class 150 or cast iron threaded tee fittings that meet the dimensional requirements of ANSI B16 4 Class 125 even at branch line ends The threaded end of the dry sprinkler is designed to allow the seal to penetrate and extend into the fitting to a predetermined depth This prevents co...

Страница 17: ...ther To remove caps from frame style sprinklers turn the caps slightly and pull them off the sprinklers SPRINKLER CAPS OR BULB SHIELDS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE Retain a protective cap or shield in the spare sprinkler cabinet 5 For flush style sprinklers the ceiling ring can now be installed onto the sprinkler body Align the ceiling ring with the sprinkle...

Страница 18: ...Prior to removing the system from service notify all Authorities Having Jurisdiction Consideration should be given to employment of a fire patrol in the affected area 1 Remove the system from service drain all water and relieve all pressure on the piping 2a For frame style sprinklers use the special sprinkler wrench to remove the old sprinkler by turning it counterclockwise to unthread it from the...

Страница 19: ...ction of fire protection products are provided herin as they relate to legally mandated jurisdictional regions WARNING STATE OF CALIFORNIA USA Installing or servicing fire protection products such as sprinklers valves piping etc can expose you to chemicals including but not li mited to lead nickel butadiene titaninum dioxide chromium carbon black and acrylonitrile which are known to the State of C...

Отзывы: