Installation
1
2
3
1
2
3
4
5
6
7
on
VIKING
©
MODEL RC-2A
REMOTE TOUCH TONE
RELAY CONTROLLER
VIKING
ELECTRONICS
HUDSON, WI 54016
RELA
Y
CONT
ACTS
N.O.
COM
N.C.
POWER 12V DC
1
2
3
ENTRY CODE
PROGRAMMING
SWITCHES
EARTH
GND
PWR IN/OUT
12-24V AC/DC
LINE IN
2
3
1
4
5
6
7
8
12V DC
Adapter
included
120V AC
C.O. Line or Analog
PABX/KSU Station
Phone(s)
N.C. Relay Contact
N.O. Relay Contact
Rotary Entry
Code Switches
Doorstrike/Magnetic Lock
E-30
(not included)
or
Gate controllers do not
typically require power.
* Earth Ground
(optional)
** 12-24V AC/DC Alternative Power Input
(from door strike adapters, etc.) or use as
an output for powering multiple RC-2As
COM Relay Contact
Power LED
Relay LED (ON while
relay is activated)
or
or
The RC-2A's LINE IN terminals
connect in parallel on the line.
5A @ 30V DC maximum
(not included)
IMPORTANT:
Electronic devices are susceptible to lightning and power station electrical surges from both the AC
outlet and the telephone line. It is recommended that a surge protector be installed to protect against such surges.
2
** Note:
The 12V DC adapter (model
PS-2
) supplied with the unit can power up to (4)
RC-2A
’s and a Viking model
PS-1A
, 13.8V AC adapter, can be used to power up to (8)
RC-2A
’s. A
PS-1A
(13.8V AC adapter) may be purchased
separately. Go to
www.vikingelectronics.com
and click on “
Spare Parts
”.
Modes
IMPORTANT:
Please read the following sections to determine which
RC-2A
mode works best for your application.
The
RC-2A
has two operational modes built in, called the Legacy and Alternative modes. The Legacy mode is
the standard mode of operation that has existed in all previous versions of the
RC-2A
. The Alternative mode is a
second mode of operation that increases the
RC-2A
's flexibility in some applications. The operational mode you
should use depends on the exact application for the
RC-2A
. Here are some general guidelines, but in some ap-
plications, the opposite mode may be needed (also see section
B-C
on page 3 describing the advantages and
disadvantages of each operational mode):
A. Choosing a Mode
Application Description
Recommended Mode Additional Programming
* Use with a Viking
W-1000
,
W-2000A
, or
W-3000
handsfree doorbox.
Legacy Mode
(traditional software)
Set one code switch to
D
and set DIP
switch
5
to
OFF
.
Use with a Viking
E-30
or
1600A Series
hands-free phone.
Alternative Mode
(new software)
Set at least one code switch to
B
, set DIP
switch
5
to
ON
and DIP switch
7
to
OFF
.
On a dedicated telephone line or PBX ex-
tension (no other phones on the same line
or extension).
Legacy Mode
(traditional software)
Set one code switch to
C
, set DIP switch
2
to
ON
and DIP switch
5
to
OFF
.
Wired across a telephone line in a residen-
tial application (sharing the line with other
phones), to control lights, door or gate.
Legacy Mode
(traditional software)
Set DIP switch
5
to
OFF
and do not set any
code switches to
C
or
D
.
* Caution:
For increased security, Viking recommends using a Viking model
SRC-1
or
C-1000B
Controller with
W-Series
Doorboxes.