background image

MICROFAST

®

 QUICK 

RESPONSE FUSIBLE 

ELEMENT UPRIGHT 

SPRINKLER VK328 (K4.2)

TECHNICAL DATA

Page 3 of 3

Form No. F_071114     21.03.05    Rev 21.1

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501 Technical Services: 877-384-5464 Fax: 269-818-1680 Email: [email protected]

Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com.

Approval Chart 1 (UL)

Microfast

®

 Quick Response Fusible Element

 

Upright Sprinkler VK328

 

Maximum 175 PSI (12 bar) WWP

Base Part 

Number

1

SIN

Thread Size

Nominal K-Factor

Overall Length

Listings and Approvals

3

NPT

BSPT

U.S.

metric

2

Inches

mm

cULus

VdS

LPCB

      

21270

6

VK328

1/2”

15 mm

4.2

57

2-3/16

56

A1, A2

--

--

--

Approved Temperature Ratings

A - 165 °F (74 °C), 205 °F (96 °C), 280 °F (138 °C)

Approved Finishes

1 - Brass, Chrome, White Polyester

5

 and  Black Polyester

5

2 - ENT

7

Footnotes

Base part number is shown. For complete part number, refer to Viking’s current price schedule.

Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 10.0.

This table shows the listings and approvals available at the time of printing. Check with the manufacturer for any additional approvals.

4

 Listed by Underwriters Laboratories Inc. for us in the U.S. and Canada

5

 Other colors are available on request with the same Listings and Approvals as the standard colors.

6

 Listings and Approvals limited to Light Hazard Occupancies where allowed by the installation standards being applied, with hydraulically calculated wet systems only.

7

 cULus Listed as corrosion resistant.

DESIGN CRITERIA - UL

 

(Also refer to Approval Chart 1 above.)

cULus Listing Requirements:

 

Quick Response Fusible Element Upright Sprinkler VK328 is cULus Listed as indicated in the Approval Chart for installation in accordance with the 

latest edition of NFPA 13 for standard spray sprinklers.

• 

Small orifice sprinklers are limited to Light Hazard where allowed by the installation standards being applied, with hydraulically calculated wet sys-

tems only. Exception: 4.2K sprinklers may be installed on hydraulically calculated dry pipe systems where piping is corrosion resistant or internally 

galvanized.

• 

The sprinkler installation rules contained in NFPA 13 for standard spray upright sprinklers must be followed.

IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to Form No. F_080614 

for general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the latest 

edition of Viking technical data, the appropriate standards of NFPA, FM Global, LPCB, APSAD, VdS or other similar organiza-

tions, and also with the provisions of governmental codes, ordinances, and standards, whenever applicable. 

Replaces Form No. F_071114 Rev 20.1

(Removed bushed part numbers)

Содержание MICROFAST VK328

Страница 1: ...a minimum of 7 psi 0 5 bar The minimum operating pressure for LPCB and CE Approvals ONLY is 5 psi 0 35 bar Material Standards Frame Casting Brass UNS C84400 Deflector Brass UNS C23000 or Copper UNS C19500 Bushing Brass UNS C36000 Fusible Element Assembly Nickel Alloy Trigger and Support UNS S31603 Belleville Spring Sealing Assembly Nickel Alloy coated on both sides with PTFE Tape Seat and Insert A...

Страница 2: ...TURE RATINGS AND FINISHES Sprinkler Temperature Classification Sprinkler Nominal Temperature Rating1 Maximum Ambient Ceiling Temperature2 Frame Paint Color Ordinary 165 F 74 C 100 F 38 C None Intermediate 205 F 96 C 150 F 65 C White High 280 F 138 C 225 F 107 C Blue Sprinkler Finishes Brass Chrome White Polyester5 Black Polyester5 and ENT3 4 Corrosion Resistant Sprinkler Coatings ENT3 4 Footnotes ...

Страница 3: ...are available on request with the same Listings and Approvals as the standard colors 6 Listings and Approvals limited to Light Hazard Occupancies where allowed by the installation standards being applied with hydraulically calculated wet systems only 7 cULus Listed as corrosion resistant DESIGN CRITERIA UL Also refer to Approval Chart 1 above cULus Listing Requirements Quick Response Fusible Eleme...

Страница 4: ...stall sprinklers onto piping at the floor level Install sprinklers after the piping is in place to prevent mechanical damage DO NOT allow impacts such as hammer blows directly to sprinklers or to fittings pipe or couplings in close proximity to sprinklers Sprinklers can be damaged from direct or indirect impacts DO NOT attempt to remove drywall paint etc from sprinklers Take care not to over tight...

Страница 5: ...D CAPS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE Figure 1 Sprinkler shield being removed from a pendent sprinkler Figure 2 Sprinkler cap being removed from a pendent sprinkler Figure 3 Sprinkler cap being re moved from and upright sprinkler HOW TO REMOVE SHIELDS AND CAPS No tools are necessary to remove the shields or caps from sprinklers DO NOT use any sharp objects to ...

Страница 6: ... these sprinklers NOTE The protective cap is temporarily removed during installation and then placed back on the sprinkler for protection until finish work is completed Do not over tighten the sprinklers into fittings during installation Do not use the sprinkler deflector to start or thread the sprinklers into fittings during installation Do not attempt to remove drywall paint etc from the sprinkl...

Страница 7: ...t the corrosion resistant properties of the sprinkler Use care when locating sprinklers near fixtures that can generate heat Do not install sprinklers where they would be exposed to temperatures exceed ing the maximum recommended ambient temperature for the temperature rating used Inspect the coated sprinklers frequently soon after installation to verify the integrity of the corrosion resistant co...

Страница 8: ...ction of fire protection products are provided herin as they relate to legally mandated jurisdictional regions WARNING STATE OF CALIFORNIA USA Installing or servicing fire protection products such as sprinklers valves piping etc can expose you to chemicals including but not li mited to lead nickel butadiene titaninum dioxide chromium carbon black and acrylonitrile which are known to the State of C...

Отзывы: