The one or two digit code stored in the Relay Activation Command is the touch tone command that the person being
called must enter on their phone in order to actuate relay 1 or 2 to control a doorstrike, mag-lock, gate controller, or
other device. The code can contain the numbers 0 - 9, 00 - 99, ## or 

,,

. The code cannot match a relay latching or

toggle command (11, 10, 1#, 21, 20, or 2#). The code must be entered while the remote phone is communicating with
the Entry phone. The Entry phone determines which direction the touch tone is coming from and only responds to
touch tones from the called phone.  

Factory Setting:

Relay 1 - 

,,

, Relay 2 - 

,

2

18. Relay 1 or 2 Act (Activation) Command 

The value stored in the Relay 1 or 2 Activation Time is the amount of time relay 1 or 2 will be energized after a correct
momentary touch tone command is entered, “#” plus a valid keyless entry code or a proximity card was scanned that
is programmed to momentarily activate the relay. This number can range from 0.5 - 99 seconds. 

NOTE:

This also

affects timing in Doorbell Mode.  

Factory Setting:

5 seconds

19. Relay 1 or 2 Activation Time 

17. Relay Mode 

20. Relay Activation Delay

A relay activation delay of 0.5 - 99 seconds can be programmed in the

K-1205-IP

. A relay activation delay is useful in

two door vestibule entrance applications. This allows you to program a delay time from when relay 1 (outside door) is
activated to when relay 2 (inside door) is activated. The programmed delay time should be set to the average time it
takes a person to walk from the outside door to the inside door.

When a request for exit (REX) is activated, relay 2 will activate first, then after the programmed delay relay 1 will
activate.  

Factory Setting:

Disabled

The relay activation tone is a buzzing sound that is heard at the Entry phone when the door strike relay is activated.
After the called party enters the correct relay activation command, the called party will hear 2 short confirmation beeps
and the entry phone will output a buzzing sound (relay activation tone) while the door strike relay is activated. The tone
(buzz) length will match the relay activation time up to a maximum of 5 seconds. The tone (buzz) can be programmed
to three different volume settings 1 = Low, 2 = Medium, 3 = High or it can be disabled.  

Factory Setting:

3

21. Relay Buzz Volume

Doorstrike Mode (Factory Setting):  

When programmed for Doorstrike Mode the relay will momentarily activate for

the preprogrammed relay activation time after detecting the correct relay activation command (one or two digit touch
tone) from the called party.

Outbound Call Mode: 

When programmed for Outbound Call Mode the relay will activate continuously for the duration

of any outbound call from the Entry phone. 

Inbound/Outbound Call Mode:  

When programmed for Inbound/Outbound Call Mode the relay will activate

continuously for the duration of any inbound or outbound call to or from the Entry phone. This mode is useful for turning
on IR flood lights, for VoIP phones with cameras, etc. 

Doorbell Mode:  

When programmed for Doorbell Mode the relay will momentarily activate the relay for the

preprogrammed relay activation time at the beginning of any outbound call from the Entry phone. This mode is useful
for activating a door chime, etc. When activating door chimes, a 0.5 - 1 second relay activation time is recommended.

Alarm Mode:  

When programmed in Alarm Mode the relay will activate continuously while the Entry phone is powered

and registered to the SIP server. In the event the unit loses power and/or SIP registration the relay will turn off, which
can be used to signal an alarm device.  

Note: 

Relay 2 should be set to “Alarm Mode” when mounting a 

PRX-3

in close

proximity of the 

K-1205-IP 

(when mounting the 

K-1205-IP

and 

PRX-3

to a 

PRX-3-MK-GNP

gooseneck pedestal

mounting plate) See Pg. 6.

Содержание K-1205-IP Series

Страница 1: ...terproof scratch resistant lens and 12 buttons for single push auto dialing of a tenant s phone number or business extension When the K 1205 IP phone is connected to an apartment or business tenant a...

Страница 2: ...to www vikingelectronics com and enter 944 in the search box 2 Click Application Note DOD 944 to open and download the PDF Scan the QR code below to open and download the Viking VoIP SIP System Compat...

Страница 3: ...address also called a hardware address or physical address is a unique address assigned to a device at the factory It resides in the device s memory and is used by routers to send network traffic to...

Страница 4: ...ded or program as a output to connect to the card reader input of an Access Control System Note The gel filled water tight butt connectors are designed for insulation displacement on 19 26 gauge wire...

Страница 5: ...al St Hudson WI 54016 DEV RoHS J6 Q171570 8 2W J6 MAC 18E80FXXXXXX asdesaxtff Note Up to 150 ft video cable run length can be achieved using CAT5E or CAT6 cable Longer cable runs can be used if a pass...

Страница 6: ...nt the directory lens to the front of the K 1205 IP using the included Allen wrench Insert a paper directory behind the lens and secure the two back onto the front panel being careful to align the nam...

Страница 7: ...TUS LED Optional Viking model RC 4A Secure Remote Relay Controller see page 7 DOD 582 Extends range of cable keeps 1 Gbps network speed for other equipment on network IBM compatible personal computer...

Страница 8: ...you to trouble shoot the failure B Connect Disconnect Open the Viking IP Programming software on the PC and the start screen shown below will appear Any Viking IP phones that are connected to the net...

Страница 9: ...ettings tab Step 6 Select the appropriate value Static IP Settings or DHCP for Set Unit IP Address via Note changing the IP address will cause you to have to reconnect to the unit Enter the values for...

Страница 10: ...ld the key on keypad then reconnect the LAN Cable RJ45 plug Step 3 Continue to hold key until you hear 2 beeps approximately 6 seconds Continue to hold key until you hear 4 more beeps approximately 6...

Страница 11: ...must be set to Door Strike 22 18 In Band Audio Call Progress Enabled Disabled factory set to Enabled 23 18 In Band Audio Detect Sensitivity 1 9 1 minimum 9 maximum factory set to 5 power cycle unit a...

Страница 12: ...field blank 1 Unit Name Up to a 31 character unit name can be assigned to the K 1205 IP Series Phone being programmed When registered to a SIP server in the event that registration is lost you can pro...

Страница 13: ...he PC and are not uploaded The Index Number is the single digit number visitors enter on the K 1205 IP s keypad for the unit to call the tenant 3 seconds after the number is entered the unit will then...

Страница 14: ...ion which door gate was opened or closed entry code index and phone number index with tenant name The Event Log can store up to 4 095 events Events are stored in a first in first out format When the m...

Страница 15: ...ty Card entries but also log any errors incorrect codes or non valid card reads Keyless Entry Code and Proximity Card logging can also be set to Live Logging With Live logging selected and the K 1205...

Страница 16: ...er is sent over the Weigand output along with the facility code selected Since Wiegand data limits the entry code to 65535 maximum plus entry codes higher than 65535 are not sent over the Wiegand outp...

Страница 17: ...r strike relay is activated After the called party enters the correct relay activation command the called party will hear 2 short confirmation beeps and the entry phone will output a buzzing sound rel...

Страница 18: ...utomatically decrease When background noise decreases the mic gain will automatically increase The Auto mode is useful in applications where the background noise level can change drastically such as a...

Страница 19: ...dialing 9 from the connected phone If enabled and a busy is detected the K 1205 IP phone will dial the Roll Over speed dial number Factory Setting Enabled Note If the busy signal is interrupted with...

Страница 20: ...d like to update firmware An alternative method of updating can be done by clicking the IP firmware Update IP button You can then browse to the folder that contains the PIP file for updating the unit...

Страница 21: ...ne of the following actions based on the Relay Mode settings for each relay see section 22 Relay 1 Door Strike relay 2 other Relay 1 will be activated for the programmed Relay 1 Activation Time Relay...

Страница 22: ...mber can be programmed to activate relay 1 and or 2 in four different relay modes Momentary Latch Un Latch and Toggle To use a proximity card the tenant simply presents a preprogrammed proximity card...

Страница 23: ...netic Lock 120V AC Door near Entry Phone 3 1 IN1 C IN2 IN3 C IN4 2 3 4 5 6 Relay 1 Output Contacts 5A 30VDC 250VAC max Connect to Doorstrike Mag Lock Gate Controller etc Relay 3 Output Contacts 5A 30V...

Страница 24: ...The use of magnets to mount the VE Series enclosure to a metal surface can affect the operation of the enclosed product Caution Handsfree phones are not suitable for noisy applications see Important...

Страница 25: ...r strikes and gates when a remote relay is required for security reasons It can also be programmed to send an email or text message in response to a change in one or more of the sensor inputs Two RC 4...

Страница 26: ...the dispatcher the reason for the call Perform such tests in off peak hours such as early morning or late evenings PART 15 LIMITATIONS This equipment has been tested and found to comply with the limi...

Отзывы: