Page14
15” & 24” Series
Technical Services Manual
SMR-0014
Controller Alarm Signals
The controllers come with a set of alarm messages, which show in the display when something, pos-
sibly wrong with the cabinet or controller. The message will display until the alarm condition recovers.
All alarm conditions flash alternating between the alarm and the cabinet (zone) temperature, except for
a cabinet (zone) probe failure.
Message
Cause
Outputs
“P1”
Thermostat probe failure
Compressor output according to param-
eters “Con” & “COF”
“HA”
Maximum temperature alarm
Other outputs unchanged
“LA”
Minimum temperature alarm
Other outputs unchanged
“DA”
Door alarm
Compressor and fans restart
Alarm Recovery
Probe alarm:
“
P1
”” automatically stops 10 seconds after the probe restarts normal operation. Always
check probe connections and resistance before replacing the probe.
Temperature Alarms:
“
HA
” and “
LA
” automatically stop as soon as the thermostat temperature re-
turns to normal values.
Controller Programming
There are no adjustments to the programs that can be done from a service standpoint. The only meth-
od of programming is through the replacement of the controller for a beverage center, a refrigerator or
a wine cellar, all look the same in appearance but there are three different part numbers.
MODEL
A
B
C
D
E
F
FBCI/VBCI 1150G
13
-2
6
2
8
6
FWCI1/VWCI 150G
24
2
6
4
20
6
FRCI/VRCI 1240G
9
-2
6
-2
6
1
VRCO1240D
9
-2
6
-2
6
1
FBCI/VBCI 1240G
13
-2
6
2
8
6
FWCI/VWCI 1240G
24
2
6
4
20
6
FRDI/VRDI 1240D
9
-2
6
-2
6
1
VRDO1240D
9
-2
6
-2
6
1
Table 1
Maximum
Alarm
Temperature
Set point where
compressor
shuts off
Minimum
Alarm
Temperature
Differential
(Cut-in versus
cut-out)
Minimum Set
Point
Maximum Set
Point