MICROFAST

®

 QUICK 

RESPONSE FUSIBLE 

ELEMENT PENDENT 

SPRINKLER VK353 (K8.0)

TECHNICAL DATA

Page 5 of 6

Form No. F_071814   19.02.21   Rev 19.1

The Viking Corporation, 210 N Industrial Park Drive, Hastings MI 49058

Telephone: 269-945-9501  Technical Services: 877-384-5464  Fax: 269-818-1680  Email: [email protected]

Visit the Viking website for the latest edition of this technical data page www.vikinggroupinc.com.

Approval Chart 2 (FM)

The Viking Microfast

®

 Quick Response 

Pendent Sprinkler 

VK353

 

Maximum 175 PSI (12 Bar) WWP

Base Part 

Number

1

SIN

Sprinkler 

Style

Thread Size

Nominal K-Factor

Overall Length

FM Approvals

(Refer also to Design Criteria.)

NPT

BSP

U.S.

metric

2

Inches

mm

18274

VK353

Pendent

3/4”

20 mm

8.0

115.2

2-5/16

59

A1X, B1Y

NOTICE - Product Below - Limited Availability (Contact Local Viking Office)

13975

VK353

Pendent

3/4”

20 mm

8.0

115.2

2-5/16

59

A1X, B1Y

Approved Temperature Ratings

A - 165 °F (74 °C), 205 °F (96 °C), and 280 °F (138 °C)

B - 165 °F (74 °C) and 205 °F (96 °C)

Approved Finishes

1 - Brass and Chrome

Approved Escutcheons

X - Standard surface-mounted escutcheon
Y - Standard surface-mounted escutcheon or recessed 

with the Viking Micromatic® Model E-1, E-2, or E-3 
Recessed Escutcheon

Footnotes

1

 Base part number shown. For complete part number, refer to Viking’s current price schedule.

2

 Metric K-factor measurement shown is when pressure is measured in Bar. When pressure is measured in kPa, divide the metric K-factor shown by 

10.0.

3

 This table shows the FM Approvals available at the time of printing. Other approvals may be in process.

4

 Other colors are available on request with the same Approvals as the standard colors.

5

 FM approved as corrosion resistant.

DESIGN CRITERIA - FM

 

(Also refer to Approval Chart 2 above.)

FM Approval Requirements:

 

The Viking Microfast

®

 Quick Response Fusible Element Pendent Sprinkler VK353 is FM Approved as quick response 

Non-storage

 

pendent sprinklers as indicated in the FM Approval Guide. For specific application and installation requirements, reference the latest 

applicable FM Loss Prevention Data Sheets (including Data Sheet 2-0). FM Global Loss Prevention Data Sheets contain guidelines 

relating to, but not limited to: minimum water supply requirements, hydraulic design, ceiling slope and obstructions, minimum and 

maximum allowable spacing, and deflector distance below the ceiling.

NOTE: The FM installation guidelines may differ from cULus and/or NFPA criteria.

IMPORTANT: Always refer to Bulletin Form No. F_091699 - Care and Handling of Sprinklers. Also refer to Form No. F_080614 

for general care, installation, and maintenance information. Viking sprinklers are to be installed in accordance with the latest 

edition of Viking technical data, the appropriate standards of NFPA, LPCB, APSAD, VdS or other similar organizations, and 

also with the provisions of governmental codes, ordinances, and standards, whenever applicable. 

Содержание 139676

Страница 1: ...Element Assembly Nickel Alloy Trigger and Support Stainless Steel UNS S31600 Belleville Spring Sealing Assembly Nickel Alloy coated on both sides with PTFE Tape Seat and Insert Assembly Copper UNS C1...

Страница 2: ...ges releasing the seat and spring assemblies to open the waterway Water flowing through the sprinkler orifice strikes the sprinkler deflector forming a uniform spray pattern to extinguish or control t...

Страница 3: ...ed not available from Viking TABLE 1 AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES Sprinkler Temperature Classification Sprinkler Nominal Temperature Rating1 Maximum Ambient Ceiling Temperature...

Страница 4: ...ecessed Escutcheon Footnotes 1 Base part number shown For complete part number refer to Viking s current price schedule 2 Metric K factor measurement shown is when pressure is measured in Bar When pre...

Страница 5: ...ressure is measured in Bar When pressure is measured in kPa divide the metric K factor shown by 10 0 3 This table shows the FM Approvals available at the time of printing Other approvals may be in pro...

Страница 6: ...Figure 4 Sprinkler Dimensions with the Model E 1 and E 2 Recessed Escutcheons Figure 3 Sprinkler Dimensions with a Standard Escutcheon 3 4 NPT 20 mm 2 5 16 59 mm 1 3 4 45 mm Installed with a standard...

Страница 7: ...tall sprinklers onto piping at the floor level Install sprinklers after the piping is in place to prevent mechanical damage DO NOT allow impacts such as hammer blows directly to sprinklers or to fitti...

Страница 8: ...CAPS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE Figure 1 Sprinkler shield being removed from a pendent sprinkler Figure 2 Sprinkler cap being removed from a pendent sprinkle...

Страница 9: ...these sprinklers NOTE The protective cap is temporarily removed during installation and then placed back on the sprinkler for protection until finish work is completed Do not over tighten the sprinkle...

Страница 10: ...the corrosion resistant properties of the sprinkler Use care when locating sprinklers near fixtures that can generate heat Do not install sprinklers where they would be exposed to temperatures exceed...

Страница 11: ...tion of fire protection products are provided herin as they relate to legally mandated jurisdictional regions WARNING STATE OF CALIFORNIA USA Installing or servicing fire protection products such as s...

Отзывы: