CARE AND HANDLING 

OF SPRINKLERS

Page 4 of 4

Form No. F_091699     18.10.11    Rev 16.1.P65

USE THE FOLLOWING PRECAUTIONS WHEN HANDLING WAX-COATED SPRINKLERS

Many of Viking’s sprinklers are available with factory-applied wax coating for corrosion resistance. These sprinklers MUST receive 

appropriate care and handling to avoid damaging the wax coating and to assure satisfactory performance of the product.

General Handling and Storage of Wax-Coated Sprinklers:

• 

Store the sprinklers in a cool, dry place (in temperatures below the maximum ambient temperature allowed for the sprinkler temperature rating. Refer 

to Table 1 below.)

• 

Store containers of wax-coated sprinklers separate from other sprinklers.

• 

Protect the sprinklers during storage, transport, handling, and after installation.

• 

Use original shipping containers.

• 

Do not place sprinklers in loose boxes, bins, or buckets.

Installation of Wax-Coated Sprinklers:

Use only the special sprinkler head wrench designed for installing wax-coated Viking sprinklers (any other wrench may damage 

the unit).

• 

Take care not to crack the wax coating on the units.

• 

For touching up the wax coating after installation, wax is available from Viking in bar form. Refer to Table 1 below. The coating MUST be repaired after 

sprinkler installation to protect the corrosion-resistant properties of the sprinkler.

• 

Use care when locating sprinklers near fixtures that can generate heat. Do not install sprinklers where they would be exposed to temperatures exceed-

ing the maximum recommended ambient temperature for the temperature rating used.

• 

Inspect the coated sprinklers frequently soon after installation to verify the integrity of the corrosion resistant coating. Thereafter, inspect representative 

samples of the coated sprinklers in accordance with NFPA 25. Close up visual inspections are necessary to determine whether the sprinklers are being 

affected by corrosive conditions. 

Never install sprinklers that have been dropped, damaged, or exposed to temperatures in excess of the maximum ambi-

ent temperature allowed. 

Refer to the appropriate current technical data pages for complete care, handling, and installation instructions. Data 

pages are included with each shipment from Viking or Viking distributors. They can also be found on the Web site at www.

vikinggroupinc.com.

TABLE 1 

Sprinkler Temperature Rating 

(Fusing Point)

Wax Part 

Number

Wax Melting Point

Maximum Ambient 

Ceiling Temperature

1

Wax Color

155 °F (68 °C) / 165 °F (74 °C)

02568A

148 °F (64 °C)

100 °F (38 °C)

Light Brown

175 °F (79 °C)

04146A

161 °F (71 °C)

150 °F (65 °C)

Brown

200 °F (93 °C)

04146A

161 °F (71 °C)

150 °F (65 °C)

Brown

220 °F (104 °C)

02569A

170 °F (76 °C)

150 °F (65 °C)

Dark Brown

286 °F (141 °C)

02569A

170 °F (76 °C)

150 °F (65 °C)

Dark Brown

Based on NFPA-13. Other limits may apply, depending on fire loading, sprinkler location, and other requirements of the Authority Having 

Jurisdiction. Refer to specific installation standards.

Replaces Form No. F_091699 Rev 16.1

(Added P65 Warning)

Содержание 139676

Страница 1: ...Element Assembly Nickel Alloy Trigger and Support Stainless Steel UNS S31600 Belleville Spring Sealing Assembly Nickel Alloy coated on both sides with PTFE Tape Seat and Insert Assembly Copper UNS C1...

Страница 2: ...ges releasing the seat and spring assemblies to open the waterway Water flowing through the sprinkler orifice strikes the sprinkler deflector forming a uniform spray pattern to extinguish or control t...

Страница 3: ...ed not available from Viking TABLE 1 AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES Sprinkler Temperature Classification Sprinkler Nominal Temperature Rating1 Maximum Ambient Ceiling Temperature...

Страница 4: ...ecessed Escutcheon Footnotes 1 Base part number shown For complete part number refer to Viking s current price schedule 2 Metric K factor measurement shown is when pressure is measured in Bar When pre...

Страница 5: ...ressure is measured in Bar When pressure is measured in kPa divide the metric K factor shown by 10 0 3 This table shows the FM Approvals available at the time of printing Other approvals may be in pro...

Страница 6: ...Figure 4 Sprinkler Dimensions with the Model E 1 and E 2 Recessed Escutcheons Figure 3 Sprinkler Dimensions with a Standard Escutcheon 3 4 NPT 20 mm 2 5 16 59 mm 1 3 4 45 mm Installed with a standard...

Страница 7: ...tall sprinklers onto piping at the floor level Install sprinklers after the piping is in place to prevent mechanical damage DO NOT allow impacts such as hammer blows directly to sprinklers or to fitti...

Страница 8: ...CAPS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE Figure 1 Sprinkler shield being removed from a pendent sprinkler Figure 2 Sprinkler cap being removed from a pendent sprinkle...

Страница 9: ...these sprinklers NOTE The protective cap is temporarily removed during installation and then placed back on the sprinkler for protection until finish work is completed Do not over tighten the sprinkle...

Страница 10: ...the corrosion resistant properties of the sprinkler Use care when locating sprinklers near fixtures that can generate heat Do not install sprinklers where they would be exposed to temperatures exceed...

Страница 11: ...tion of fire protection products are provided herin as they relate to legally mandated jurisdictional regions WARNING STATE OF CALIFORNIA USA Installing or servicing fire protection products such as s...

Отзывы: