CARE AND HANDLING 

OF SPRINKLERS

Page 2 of 4

Form No. F_091699     18.10.11    Rev 16.1.P65

PROTECTIVE SPRINKLER SHIELDS AND CAPS

General Handling and Storage:

Many Viking sprinklers are available with a plastic protective cap or shield temporarily covering the operating elements. The snap-

on shields and caps are factory installed and are intended to help protect the operating elements from mechanical damage during 

shipping, storage, and installation. NOTE: It is still necessary to follow the care and handling instructions on the appropriate sprin-

kler technical data sheets* when installing sprinklers with bulb shields or caps.

WHEN TO REMOVE THE SHIELDS AND CAPS:

NOTE: SHIELDS AND CAPS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE!

Remove the shield or cap from the sprinkler only after checking all of the following:

• 

The sprinkler has been installed*.

• 

The wall or ceiling finish work is completed where the sprinkler is installed and there no longer is a potential for mechanical damage 

to the sprinkler operating elements.

SHIELDS AND CAPS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE!

Figure 1: Sprinkler shield being 

removed from a pendent sprinkler.

Figure 2: Sprinkler cap being       

removed from a pendent sprinkler.

Figure 3: Sprinkler cap being re-

moved from and upright sprinkler.

HOW TO REMOVE SHIELDS AND CAPS:

No tools are necessary to remove the shields or caps from sprinklers. DO NOT use any sharp objects to remove them! 

Take care 

not to cause mechanical damage to sprinklers when removing the shields or caps.

 When removing caps from fusible ele-

ment sprinklers, use care to prevent dislodging ejector springs or damaging fusible elements. NOTE: Squeezing the sprinkler cap 

excessively could damage sprinkler fusible elements.

• 

To remove the shield, simply pull the ends of the shield apart where it is snapped together. Refer to Figure 1.

• 

To remove the cap, turn it slightly and pull it off the sprinkler. Refer to Figures 2 and 3.

Refer to the current sprinkler technical data page to determine the correct sprinkler wrench for the model of sprinkler used.

Never install sprinklers that have been dropped, damaged, or exposed to temperatures in excess of the maximum ambient
temperature allowed.

* Refer to the appropriate current technical data pages for complete care, handling, and installation instructions. Data 

pages are included with each shipment from Viking or Viking distributors. They can also be found on the Web site at www.

vikinggroupinc.com.

Содержание 139676

Страница 1: ...Element Assembly Nickel Alloy Trigger and Support Stainless Steel UNS S31600 Belleville Spring Sealing Assembly Nickel Alloy coated on both sides with PTFE Tape Seat and Insert Assembly Copper UNS C1...

Страница 2: ...ges releasing the seat and spring assemblies to open the waterway Water flowing through the sprinkler orifice strikes the sprinkler deflector forming a uniform spray pattern to extinguish or control t...

Страница 3: ...ed not available from Viking TABLE 1 AVAILABLE SPRINKLER TEMPERATURE RATINGS AND FINISHES Sprinkler Temperature Classification Sprinkler Nominal Temperature Rating1 Maximum Ambient Ceiling Temperature...

Страница 4: ...ecessed Escutcheon Footnotes 1 Base part number shown For complete part number refer to Viking s current price schedule 2 Metric K factor measurement shown is when pressure is measured in Bar When pre...

Страница 5: ...ressure is measured in Bar When pressure is measured in kPa divide the metric K factor shown by 10 0 3 This table shows the FM Approvals available at the time of printing Other approvals may be in pro...

Страница 6: ...Figure 4 Sprinkler Dimensions with the Model E 1 and E 2 Recessed Escutcheons Figure 3 Sprinkler Dimensions with a Standard Escutcheon 3 4 NPT 20 mm 2 5 16 59 mm 1 3 4 45 mm Installed with a standard...

Страница 7: ...tall sprinklers onto piping at the floor level Install sprinklers after the piping is in place to prevent mechanical damage DO NOT allow impacts such as hammer blows directly to sprinklers or to fitti...

Страница 8: ...CAPS MUST BE REMOVED FROM SPRINKLERS BEFORE PLACING THE SYSTEM IN SERVICE Figure 1 Sprinkler shield being removed from a pendent sprinkler Figure 2 Sprinkler cap being removed from a pendent sprinkle...

Страница 9: ...these sprinklers NOTE The protective cap is temporarily removed during installation and then placed back on the sprinkler for protection until finish work is completed Do not over tighten the sprinkle...

Страница 10: ...the corrosion resistant properties of the sprinkler Use care when locating sprinklers near fixtures that can generate heat Do not install sprinklers where they would be exposed to temperatures exceed...

Страница 11: ...tion of fire protection products are provided herin as they relate to legally mandated jurisdictional regions WARNING STATE OF CALIFORNIA USA Installing or servicing fire protection products such as s...

Отзывы: