PLAN THE WIRING

1.  This  downdraft  blower  using  the  Flex  Blower  (purchase 

separately) draws 3.0 Amps and requires a 120 VAC, 60 Hz 

circuit. If using a remote blower (purchase separately), the 

system draws 6.0 Amps (max.) and requires a 120 VAC, 60 

Hz circuit. 

2.  The unit has a 18 in. long power cord with a 3-pronged plug. 

Plan to provide a grounded outlet in a location which will 

allow the unit’s power cord to reach.

3.  Install electrical box according to local codes.
4.  The length of cable from the electrical box to the downdraft 

is 20 in.

5.  The length of blower (sold separately) cable to the electrical 

box is 5 ft.

PREPARE THE DOWNDRAFT

 Installations ducting through front panel opening only:

1.  Place the downdraft on its back on a table or flat work surface.
2.  Loosen the 

HEX NUTS

 on the 

CLAMP CHANNEL 

and remove 

the 

FRONT PANEL COVER

.

FRONT PANEL COVER

CLAMP 

CHANNEL

(4-6) HEX

NUTS

 Installations using FLEX BLOWER only:

(Purchase Model VDVI600 Flex Blower separately.)

3.  Determine its location on 

FRONT PANEL

 and whether it will 

discharge to the left, right, or down. 

 

Use a combination of 

COVER PLATES

 (3" and/or 6" wide) to 

close the opening on side(s) of blower.

 

Slide  the  blower  and  cover  plates  between  the 

LOWER 

CHANNEL 

and the clamp channel. Tighten the hex nuts to 

secure blower and panels in place. 

LOWER 

CHANNEL

COVER

PLATE

COVER PLATES

(included 

with blower)

FLEX

BLOWER

FRONT

PANEL

If blower

discharge is

down,

electrical

panel must be relocated. 

See Step 6.

PLAN CABINET CUTOUTS

CAUTION:

BEFORE CUTTING 

HOLE IN CABINET 

FOR DUCTWORK, 

check for interference with 

floor joists, wall studs, 

electrical wiring, or plumbing.

Use the dimensions in the above illustration to help plan how and 

where to provide duct access through your cabinet. Generally, 

1-7/8" x 19" rectangular duct will be used through left, right, 

and back of cabinet - while 8" round duct will be used through 

cabinet floor.

For left, right, or rear exhaust:

 

Allow at least 18" for transition and elbow or blower.

For left/right exhaust:

 

A 30" deep cabinet is recommended to align properly with 

flex blower. Flex blower can be mounted to rear cabinet 

wall or to a platform/frame (not provided) on the base of the 

cabinet floor. (See flex blower instructions).
Cabinet depths of 24" to 30" are required - depending on the 

type of cooking appliance.

Electrical panel

can be mounted

remotely.

INSTALLATION

CENTER LINE

 HOLE FOR 8” or

10” ROUND DUCT

(*Adjustable 6” Left and 6” Right)

(When using Remote Discharge Plate - Hole is

adjustable 6” Left and 6” Right from

Installation Center Line.)

 HOLE

FOR

2” X 19

¼

DUCT

INSIDE

CABINET BACK

INSIDE

CABINET

FLOOR

 1

½

 6”*

 6”*

 19

¼

” centered

 2”

 26

¾

 6   ”

/

8

7

FLUSH

 19

¼

 2”

7

/

8

"

COUNTERTOP

CABINET

BACK

SIDE

VIEW

FLUSH

Содержание CVDD5300

Страница 1: ...USE INSTALLATION GUIDE 5 Series Rear Downdraft Ventilators ...

Страница 2: ...ktop 10 Children should not be left alone or unattended in the area where this appliance is in use 11 This unit must be grounded TO REDUCE THE RISK OF A RANGE TOP GREASE FIRE a Never leave surface units unattended at high settings Boilovers cause smoking and greasy spillovers that may ignite Heat oils slowly on low or medium settings b Always turn hood ON when cooking at high heat or when cooking ...

Страница 3: ...ired behind cooktop and that 2 1 2 is necessary between the back edge of the cooktop and the inside of cabinet back A B C D E F HOUSING 1 The downdraft blower system is designed for use with 8 round ductwork using a flex blower or 10 Round ductwork using a remote blower Purchase blowers separately Six 6 different discharge connections are available with side to side adjustment for accurate alignme...

Страница 4: ... Tighten the hex nuts to secure blower and panels in place LOWER CHANNEL COVER PLATE COVER PLATES included with blower FLEX BLOWER FRONT PANEL If blower discharge is down electrical panel must be relocated See Step 6 PLAN CABINET CUTOUTS CAUTION BEFORE CUTTING HOLE IN CABINET FOR DUCTWORK check for interference with floor joists wall studs electrical wiring or plumbing Use the dimensions in the ab...

Страница 5: ...ex nuts to secure the plates in place LOWER CHANNEL 8 OR 10 ROUND REMOTE DISCHARGE PLATE Purchase Separatly FRONT PANEL All Installations 5 Slide UPPER SUPPORT BRACKETS into SLIDE CHANNEL at top left and right of unit Attach LONG OR SHORT SUPPORT LEGS depending upon cabinet height to bottom sides of unit with HEX SCREWS provided Do not tighten hex screws completely at this time UPPER SUPPORT BRACK...

Страница 6: ...ere ELECTRICAL PANEL needs to be mounted in a remote location only 6 Remove 4 8 32 HEX NUTS and ELECTRICAL PANEL 5 ft extension cables purchase separately may be needed to mount electrical panel in a remote location Do not use more that 2 extension cables Installations ducting through left right or rear only Requires purchase of 1 7 8 x 19 to 8 or 10 round transition and 1 7 8 x 19 rectangular duc...

Страница 7: ...BINET 1 Remove cooktop 2 Set housing into cabinet countertop opening as far back as possible and make sure it is level 3 Extend SUPPORT LEGS and attach to bottom of cabinet with 2 SCREWS through each leg Tighten HEX SCREWS If cabinet bottom is removed Use blocks as spacers between floor and support legs SUPPORT LEG 2 10 X 500 WOOD SCREWS HEX SCREW 4 Extend UPPER SUPPORT BRACKETS and attached to si...

Страница 8: ...a qualified person s in accordance with all applicable codes and standards Installations using FLEX BLOWER only Installations using REMOTE BLOWER only 4 Run 2 wire plus ground power cable from the exterior or in line blower to wiring box on adaptor plate Remove WIRING BOX COVER 5 Connect blower wires to power cable from exterior or in line blower Black to black white to white and green to ground s...

Страница 9: ...t is necessary to ensure that there is no interference when air vent is raised and lowered There should be a gap of 1 32 1 16 between the back of the cooktop and the front of the downdraft cover MAKE UP AIR DAMPER OPTIONAL Connects to 2 CONTACTS on WIRING BOX Compatible with G6MD and G8MDdamper MAKE UP AIR DAMPER CONTACTS WIRING BOX FINISH TRIM SCREW COUNTERTOP CHIMNEY DOWNDRAFT HOUSING Available ...

Страница 10: ...for 2 or more seconds Indicator will turn off 4 Speed Fan Speed Control 2 Level Task Light 30 Hour Filter Clean Reminder Up Down Button Up Down Button To raise lower chimney touch up down button Any feature that is active will shut off when chimney is retracting All functions will return to their previous settings when chimney is raised Heat Sentry Whentheoperatingtemperatureistoohigh thefanspeedw...

Страница 11: ...l up and out Use a mild detergent DO NOT USE ABRASIVE CLOTH STEEL WOOL PADS OR SCOURING POWDERS Replace front panel and filters before using downdraft SERVICE INFORMATION Only authorized replacement parts may be used in performing service on the appliance All servicing should be referred to a qualified technician Contact Viking Range LLC 1 888 845 4641 for the nearest service parts distributor in ...

Страница 12: ...malfunction the owner is entitled to either a refund or replacement of the product or its component part or parts Replacement of a component part includes its free installation except as specified under the limited warranty Under the terms of this warranty service must be performed by a factory authorized Viking Range LLC service agent or representative Service will be provided during normal busin...

Отзывы: