background image

11

5472 726 - 02

Vitotron 100 Electric Space Heating Hot Water Heater Installation/Service

 Electrical Installation 

(continued)

Instructions for the Installer

5.   The circulating pump requires a separate 120VAC,

  

15 amp electrical circuit. Utilize 

b

 in. electrical  

 

knockout as marked on the left side of cabinet to  

 

access circulating pump wiring connections inside  

 

space heating water heater. Do not combine the high

  

voltage power for circulating pump with any    

 

thermostat or off peak low voltage wires.

 

An optional secondary pump can be installed in the  

 

system for hydronic applications plumbed with multiple  

 circulators 

and 

or primary/secondary applications. 

 

Utilize the Pump 2 connections to operate the   

 

secondary pump. The secondary pump will  

 

 

automatically turn on upon closure of thermostat  

 

connections on control panel. Spare fuses are taped  

 

into the inside cover. 

 

Fuses specified as:

 

Time-delay Glass Fuse 6.3 x 32 mm 2A.

6.   Thermostat - This space heating water heater can  

 

be signaled to turn on from a standard two wire  

 

thermostat, end switches of an actuating valve or a

  

zone control panel. These connections should all be

  

voltage free (dry contact). Extend wires from    

 

thermostat to TT connections on control panel using 

 

2 x 18 gauge wires. Utilize 

b

” electrical knockout  

 

to left side of control panel to gain entrance to this

  

connection. Install thermostat in a location where it  

 

will not be influenced by other heat sources.

7.   Off peak control (optional) -This space heating water  

 

heater is equipped with a connection (normally  

 

closed) to receive a utility signal for off peak denoted 

 

by OP on the control board. Ensure the  

 

 

interconnection from utility radio receiver is voltage  

 

free (dry contact). Consult with local utility on   

 

questions with off-peak installations. Keep blue/white  

 

jumper wire in place if not connected to a utility radio  

 receiver.
8.   Outdoor compensation - The space heating water

  

heater can utilize an outdoor sensor for outdoor  

 

compensation capability. Install the outdoor sensor  

 

preferably on the north side of the building. Keep the  

 

outdoor sensor away from any sources of heat. 

 

Refer to Advanced Settings on page 14 to set proper  

 

heat curve. If no outdoor sensor is wired to the Text  

 

terminals on the control panel, the space heating  

 

water heater will work in normal operation

9.   Final check. Verify all electrical connections are tight.

  

Loose connections can cause premature failures of

  

electrical components. Once you have finished the

  

above procedures and before starting the space  

 

heating water heater, understand the control buttons  

 

and indicators on the control panel in the following  

 page.
10. Re-fasten the screws on bottom (2) and top (1) to  

 

hold front door in place.

Содержание Vitotron 100

Страница 1: ...eating contractor Please file in Service Binder Read and save these instructions for future reference Product may not be exactly as shown IMPORTANT Vitotron 100 VLN2 Models 04 to 14 4 Wall mounted ele...

Страница 2: ...ace Heating Hot Water Heater View 19 Parts List 20 Space Heating Hot Water Heater Parts 21 Instructions for the Installer Instructions for the User Page Table of Contents This appliance is not intende...

Страница 3: ...ter is pre set by the manufacturer to work with hydronic radiant floor radiant ceiling hot water baseboard and water to air heat applications Temperature adjustments can be made on control panel to me...

Страница 4: ...0 33 3 50 0 60 0 Breaker Quantity Amps A 1 30 amp 1 40 amp 1 50 amp 1 60 70 amp 1 80 amp Heating Elements Quantity 3 Element Resistance each 43 3 28 8 21 6 14 4 12 0 Circulating Pump Wilo Star S 21 U...

Страница 5: ...or the Installer Space Heating Hot Water Heater Mounting Clearances After reading instructions please keep this manual with the space heating hot water heater for future reference Affix the plastic ho...

Страница 6: ...Space heating hot water heater 2 Additional expansion tank if needed Space heating hot water heater piped in a primary secondary P S configuration Consider P S when higher flow rates are necessary an...

Страница 7: ...e than a 50 50 ratio of water to propylene glycol be used Consult with radiant system designers for required freeze protection guidelines Designed Temperature Differential Radiant floor heating system...

Страница 8: ...ccess to the valve is only from the bottom of the space heating water heater From there it can be connected any pressure gauge to check the pressure or pump to refill the air inside the tank 5 The spa...

Страница 9: ...of 7 psi in order to operate Pressure levels for hydronic systems typically are above the pre charged expansion tank pressure level 12 psi If additional pressure gauges are installed verify reading a...

Страница 10: ...grounded in accordance with National Electrical Code ASNI NFPA70 or local codes 3 This space heating water heater operates with 240VAC single phase electrical power source 4 Connect the space heating...

Страница 11: ...ize b electrical knockout to left side of control panel to gain entrance to this connection Install thermostat in a location where it will not be influenced by other heat sources 7 Off peak control op...

Страница 12: ...perature Fahrenheit Buttons Space heating water heater power Up and down selection Scroll option Failures indication Indicator Status Details EEE Message on electronic display Data record error Parame...

Страница 13: ...he current working mode of the space heating water heater 2 Set the supply water temperature SWT set point Utilize the right arrow push button to scroll through working parameters of the space heating...

Страница 14: ...when the outdoor sensor is wired to Text terminals on control panel Manual setting see parameter 4 in advanced settings outlet temperature can be set manually in range 85 140 F Use buttons and to chan...

Страница 15: ...For example 30 F outdoor temperature and the desired 110 F for hydronic system can lead to a selection of curve 3 or 4 It should be checked periodically whether the choice was correct if not another c...

Страница 16: ...me when the space heating water heater is switched to summer mode For example if you turn the space heating water heater to stand by mode at 6 p m the timer will activate the pump every day for 15 min...

Страница 17: ...ount kW as indicated on identification label This value is factory preset 2 A n Working mode of pump PA automatic Pn manual continuous duty of pump 3 1 2 3 Maximum quantity of active heating elements...

Страница 18: ...eat and is above ambient temperature set point Verify connections on thermostat Failure of control board Check fuse on control panel glass fuse 6 3 x 32 mm 2A Heating status blinks Off Peak signal no...

Страница 19: ...19 5472 726 02Vitotron 100 Electric Space Heating Hot Water Heater Installation Service General Space Heating Water Heater View Instructions for the User...

Страница 20: ...vice Part List Instructions for the User Legend 1 Wiring Entrance 2 Control Panel 3 Pump 4 Pressure Relief Valve 5 Pressure Sensor 6 Magnetic Filter 7 Manual Reset High Limit Device 8 Heating Element...

Страница 21: ...NG BOX 14 4KW 240V VLN2 7873778 RETURN CONNECTION PIPE VLN2 7873779 PUMP CONNECTION PIPE INTERNAL VLN2 7873780 POWER BOARD WITHOUT CONNECTION VLN2 7873781 POWER BOARD W CONNECTION VLN2 7873782 FLOW CO...

Страница 22: ...22 5472 726 02 Vitotron 100 Electric Space Heating Hot Water Heater Installation Service...

Страница 23: ...23 5472 726 02Vitotron 100 Electric Space Heating Hot Water Heater Installation Service...

Страница 24: ...0 Electric Space Heating Hot Water Heater Installation Service Technical information subject to change without notice Printed on environmentally friendly recycled and recyclable paper Scan for digital...

Отзывы: