Sizing of the Space Heating Hot Water Heater

Instructions for the Installer

It is very important to conduct a heatloss analysis of 

the intended heated space. Select the space heating hot 

water heater size in kW based on its Btu/hr. rating that 

best meets the designed heatloss.

It is important not to overly exceed the kW sizing as

this will lead to unnecessary costs of space heating hot 

water heater, wiring and materials. Consequentially it is 

extremely imperative NOT to undersize the space heating 

hot water heater.

How to choose the correct space heating hot water heater 

size? Convert BTU to kW by dividing the BTU load by 

3,413.

(Ex. 33,513 BTU / 3,413 = 9.81kW). Choose a space 

heating hot water heater that slightly exceeds this kW 

requirement by no more than 20%.

For larger BTU loads consider cascading the space 

heating hot water heaters together and pipe the system 

in a parallel configuration as described in the piping 

arrangement section.

Note:

 that utilizing propylene glycol freeze protection will  

 

  reduce the heat transfer and cause the system to 

 

  be less efficient. Under no circumstance should  

 

  more than a 50/50 ratio of water to propylene  

 

  glycol be used. Consult with radiant system   

 

  designers for required freeze protection guidelines.

 

Designed Temperature Differential

Radiant floor heating systems are typically designed for a 

10°- 20°F temperature differential determined by when

the heating fluid leaves the space heating hot water 

heater and where it enters the radiant heat source. i.e. 

radiant PEX/tubing.

 

Circulating Pump Information

This space heating hot water heater is equipped with 

a Wilo Star S 21 U 15, 3 speed circulating pump. To 

determine the speed or setting of the pump, confirm with 

radiant design completed by others and or complete a 

pressure-loss calculation. 

Refer to calculations of loop lengths to determine proper 

speed. The pump will automatically operate based on a 

thermostat call for heat. After the thermostat temperature 

set point has been reached, the pump will continue to 

circulate water for 3 additional minutes as part of a post 

purge operation to push heated water away from the heat 

exchanger.
This space heating hot water heater is also equipped 

with an additional pump relay. This will aid the installer if 

there is any need to pipe the systems with a secondary 

circulating pump to overcome pressure drop due to piping 

or hydronic tubing design.

This is commonly referred to as primary/secondary 

applications described in the piping arrangement section.

Содержание Vitotron 100

Страница 1: ...eating contractor Please file in Service Binder Read and save these instructions for future reference Product may not be exactly as shown IMPORTANT Vitotron 100 VLN2 Models 04 to 14 4 Wall mounted ele...

Страница 2: ...ace Heating Hot Water Heater View 19 Parts List 20 Space Heating Hot Water Heater Parts 21 Instructions for the Installer Instructions for the User Page Table of Contents This appliance is not intende...

Страница 3: ...ter is pre set by the manufacturer to work with hydronic radiant floor radiant ceiling hot water baseboard and water to air heat applications Temperature adjustments can be made on control panel to me...

Страница 4: ...0 33 3 50 0 60 0 Breaker Quantity Amps A 1 30 amp 1 40 amp 1 50 amp 1 60 70 amp 1 80 amp Heating Elements Quantity 3 Element Resistance each 43 3 28 8 21 6 14 4 12 0 Circulating Pump Wilo Star S 21 U...

Страница 5: ...or the Installer Space Heating Hot Water Heater Mounting Clearances After reading instructions please keep this manual with the space heating hot water heater for future reference Affix the plastic ho...

Страница 6: ...Space heating hot water heater 2 Additional expansion tank if needed Space heating hot water heater piped in a primary secondary P S configuration Consider P S when higher flow rates are necessary an...

Страница 7: ...e than a 50 50 ratio of water to propylene glycol be used Consult with radiant system designers for required freeze protection guidelines Designed Temperature Differential Radiant floor heating system...

Страница 8: ...ccess to the valve is only from the bottom of the space heating water heater From there it can be connected any pressure gauge to check the pressure or pump to refill the air inside the tank 5 The spa...

Страница 9: ...of 7 psi in order to operate Pressure levels for hydronic systems typically are above the pre charged expansion tank pressure level 12 psi If additional pressure gauges are installed verify reading a...

Страница 10: ...grounded in accordance with National Electrical Code ASNI NFPA70 or local codes 3 This space heating water heater operates with 240VAC single phase electrical power source 4 Connect the space heating...

Страница 11: ...ize b electrical knockout to left side of control panel to gain entrance to this connection Install thermostat in a location where it will not be influenced by other heat sources 7 Off peak control op...

Страница 12: ...perature Fahrenheit Buttons Space heating water heater power Up and down selection Scroll option Failures indication Indicator Status Details EEE Message on electronic display Data record error Parame...

Страница 13: ...he current working mode of the space heating water heater 2 Set the supply water temperature SWT set point Utilize the right arrow push button to scroll through working parameters of the space heating...

Страница 14: ...when the outdoor sensor is wired to Text terminals on control panel Manual setting see parameter 4 in advanced settings outlet temperature can be set manually in range 85 140 F Use buttons and to chan...

Страница 15: ...For example 30 F outdoor temperature and the desired 110 F for hydronic system can lead to a selection of curve 3 or 4 It should be checked periodically whether the choice was correct if not another c...

Страница 16: ...me when the space heating water heater is switched to summer mode For example if you turn the space heating water heater to stand by mode at 6 p m the timer will activate the pump every day for 15 min...

Страница 17: ...ount kW as indicated on identification label This value is factory preset 2 A n Working mode of pump PA automatic Pn manual continuous duty of pump 3 1 2 3 Maximum quantity of active heating elements...

Страница 18: ...eat and is above ambient temperature set point Verify connections on thermostat Failure of control board Check fuse on control panel glass fuse 6 3 x 32 mm 2A Heating status blinks Off Peak signal no...

Страница 19: ...19 5472 726 02Vitotron 100 Electric Space Heating Hot Water Heater Installation Service General Space Heating Water Heater View Instructions for the User...

Страница 20: ...vice Part List Instructions for the User Legend 1 Wiring Entrance 2 Control Panel 3 Pump 4 Pressure Relief Valve 5 Pressure Sensor 6 Magnetic Filter 7 Manual Reset High Limit Device 8 Heating Element...

Страница 21: ...NG BOX 14 4KW 240V VLN2 7873778 RETURN CONNECTION PIPE VLN2 7873779 PUMP CONNECTION PIPE INTERNAL VLN2 7873780 POWER BOARD WITHOUT CONNECTION VLN2 7873781 POWER BOARD W CONNECTION VLN2 7873782 FLOW CO...

Страница 22: ...22 5472 726 02 Vitotron 100 Electric Space Heating Hot Water Heater Installation Service...

Страница 23: ...23 5472 726 02Vitotron 100 Electric Space Heating Hot Water Heater Installation Service...

Страница 24: ...0 Electric Space Heating Hot Water Heater Installation Service Technical information subject to change without notice Printed on environmentally friendly recycled and recyclable paper Scan for digital...

Отзывы: