57
Coding in the delivered condition
Possible change
Room sensor offset
E2:50
Is available if code
"A0:1"
or
"A0:2"
, heating group, is set.
No correction of actual room tem-
perature
E2:0
to
E2:49
Correction - 5 K to display correction
- 0.1 K
E2:51
to
E2:99
Display corr 0.1 K to display
corr 4.9 K
Screed drying
F1:0
Screed drying not active
F1:1
to
F1:6
Screed drying adjustable in accord-
ance with 6 selectable temperature/
time profiles (for more information,
see chapter "Screed function").
Boiler
Coding
Coding in the delivered condition
Possible change
Max boiler flow temperature
7A:87
Limitation of the max. flow temper-
ature setting range for the user in
the main menu. The customer can
set a max. flow temperature of
87 °C.
7A:88
to
7A:90
Limitation of the max. flow tempera-
ture setting range for the user in the
main menu.
Type O2 probe
FF:1
Lambda probe used: Type NGK
FF:0
Lambda probe used: Type LSM11
DHW
Coding
Coding in the delivered condition
Possible change
DHW set temperature reheating suppression
67:0
Reheating suppression of external
solar control unit deactivated
67:1
to
67:90
DHW set value during active reheat-
ing suppression of the external solar
control unit in °C
Start hysteresis DHW
85:0
Cylinder heating
Start point: Set value
−
2.5 K
85:1
to
85:10
Start point adjustable from 1 to 10 K
below the set value
Codes
Code 2
(cont.)
5777 985 GB
Codes