35
Settings and actual val-
ues
Set value
Commis-
sioning
Mainte-
nance/Serv-
ice
Date
By
Static pressure
mbar
kPa
max. 57.5
max. 5.75
Supply pressure (flow
pressure)
Tick gas type
=
for natural gas E
mbar
kPa
17.4 - 25
1.74 - 2.5
=
for natural gas LL
mbar
kPa
17.4 - 25
1.74 - 2.5
=
for LPG (at 50 mbar pre-
charge pressure)
mbar
kPa
42.5 - 57.5
4.25 - 5.75
Nozzle pressure
mbar
Carbon dioxide content
CO
2
% by vol.
Oxygen content O
2
% by vol.
Carbon monoxide con-
tent CO
ppm
Flue gas temperature
(gross)
°C
Flue gas loss
%
Ionisation current when
the pilot burner is lit
µA
min. 1.5
Draught
Max.
Pa
mbar
10
0.1
Min.
Pa
mbar
3
0.03
Commissioning/service reports
Commissioning/service reports
5692 704 GB