10
2.
If the details do not match, convert
the burner to the available gas type,
in accordance with the information
provided by the gas supply utility or
the LPG supplier.
Conversion kit installation
instructions
3.
Record the gas type in the report on
page 35.
Wobbe index range
Natural gas E
Natural gas
LL
LPG P
G20
G25
G31
kWh/m
3
12.0 to 16.1
10.0 to 13.1
21.4 to 22.5
MJ/m
3
43.2 to 58.0
36.0 to 47.2
76.9 to 81.0
Changing the gas type (if required)
Conversion kit installation
instructions
Checking the static and supply pressure
Danger
CO build-up as a result of incor-
rect burner adjustment can have
serious health implications.
Carry out a CO test before and
after work on gas appliances.
Operation with LPG
Flush the LPG tank twice during com-
missioning or replacement. Vent the tank
and gas connection line thoroughly after
flushing.
Commissioning, inspection, maintenance
Further details regarding the individual steps
(cont.)