57
Value
address
00: ...
System
version
Description
7
3
One heating circuit with mixer (heating circuit 2) and one
heating circuit with mixer (heating circuit 3), without DHW
heating
8
3
One heating circuit with mixer (heating circuit 2) and one
heating circuit with mixer (heating circuit 3), with DHW heat-
ing
9
3
One heating circuit without mixer (heating circuit 1), one heat-
ing circuit with mixer (heating circuit 2) and one heating circuit
with mixer (heating circuit 3), without DHW heating (code is
adjusted automatically)
10
3
One heating circuit without mixer (heating circuit 1), one heat-
ing circuit with mixer (heating circuit 2) and one heating circuit
with mixer (heating circuit 3), with DHW heating (code is
adjusted automatically)
Coding in the delivered condition
Possible change
11:
≠
9
No access to the coding
addresses for the com-
bustion controller param-
eters
11:9
Access open to the coding
addresses for the combus-
tion controller parameters
25:0
Without outside tempera-
ture sensor (for constant
temperature control
units)
25:1
With outside temperature
sensor (automatic recogni-
tion)
32:0
Without extension AM1
32:1
With extension AM1 (auto-
matic recognition)
33:1
Function output A1 at
extension AM1: Heating
circuit pump
33:0
Function output A1: DHW
circulation pump
33:2
Function output A1: Circu-
lation pump for cylinder
heating
34:0
Function output A2 at
extension AM1: DHW cir-
culation pump
34:1
Function output A2: Heat-
ing circuit pump
34:2
Function output A2: Circu-
lation pump for cylinder
heating
35:0
Without extension EA1
35:1
With extension EA1 (auto-
matic recognition)
Code 2
General/Group "1"
(cont.)
5692 843 GB