102
Dis-
played
fault
code
Const.
Weath.-
comp.
System char-
acteristics
Cause
Measures
C6
X
Control mode,
max. pump
speed
Communica-
tion error,
external vari-
able speed
heating circuit
pump, heat-
ing circuit 2
(with mixer)
Check setting of
coding address
"E5"
C7
X
X
Control mode,
max. pump
speed
Communica-
tion error,
external vari-
able speed
heating circuit
pump, heat-
ing circuit 1
(without
mixer)
Check setting of
coding address
"E5"
C8
X
Control mode,
max. pump
speed
Communica-
tion error,
external vari-
able speed
heating circuit
pump, heat-
ing circuit 3
(with mixer)
Check setting of
coding address
"E5"
Cd
X
X
Control mode
Communica-
tion error,
Vitocom 100
(KM BUS)
Check connec-
tions, Vitocom 100
and coding
address "95"
CE
X
X
Control mode
Communica-
tion error, ext.
extension
Check connections
and coding
address "2E"
CF
X
Control mode
Communica-
tion error,
LON commu-
nication mod-
ule
Replace the LON
communication
module
Troubleshooting
Fault codes
(cont.)
5692 843 GB